{"id":{"repo_id":"whiterose","oai_identifier":"oai:etheses.whiterose.ac.uk:20785"},"canonical_url":"https://search.ndltd.org/etd/whiterose/oai:etheses.whiterose.ac.uk:20785","repository":{"repo_id":"whiterose","name":"White Rose University Consortium","base_url":"https://etheses.whiterose.ac.uk/cgi/oai2"},"display":{"title":"Analysis of Thermal and Compute Performance of Data Centre Servers","abstract":"Data centres are an increasingly large contributing factor to the consumption of electricity globally, and any improvements to their effectiveness are important in minimising their effect on the environment. This study aims to achieve this by looking at ways of understanding and more effectively utilising IT in data centre spaces. This was achieved through the testing of a range of ways of creating virtual load, and employing them on servers in a controlled thermal environment. A Generic Server Wind-tunnel was designed and built which afforded control of thermal environment and six different servers were tested within, yielding results on performance and thermal effect. Further testing was also conducted on a High Performance Computing server with a view to understanding the effect of internal temperature on performance. Transfer functions were created for each of the six servers, predicting behaviour reliability for five output functions and validating the developed methodology to an appropriate accuracy. The trends seen and the methodology presented should allowed data centre managers better insight into the behaviour of their servers.","abstract_html":"Data centres are an increasingly large contributing factor to the consumption of electricity globally, and any improvements to their effectiveness are important in minimising their effect on the environment. This study aims to achieve this by looking at ways of understanding and more effectively utilising IT in data centre spaces. This was achieved through the testing of a range of ways of creating virtual load, and employing them on servers in a controlled thermal environment. A Generic Server Wind-tunnel was designed and built which afforded control of thermal environment and six different servers were tested within, yielding results on performance and thermal effect. Further testing was also conducted on a High Performance Computing server with a view to understanding the effect of internal temperature on performance. Transfer functions were created for each of the six servers, predicting behaviour reliability for five output functions and validating the developed methodology to an appropriate accuracy. The trends seen and the methodology presented should allowed data centre managers better insight into the behaviour of their servers.","abstract_has_math":false,"creators":["Burdett, Daniel Simon"],"institution":"University of Leeds","degree_name":"Ph.D","degree_level":"doctoral","degree_discipline":null,"degree_department":null,"school":null,"contributors":[],"advisors":["Summers, Jon"],"committee_chairs":[],"committee_members":[],"year":2018,"date_issued":"2018-01","date_published":"2018-01","updated_at":"2026-11-18T22:27:46Z","subjects":[],"languages":["eng"],"rights":[],"rights_urls":[],"identifier_entries":[{"key":"dc:identifier","label":"Identifier","values":["uk.bl.ethos.745617"],"render_values":[{"text":"uk.bl.ethos.745617","href":null,"code":true}]}],"person_identifier_entries":[]},"links":{"outbound_url":null,"outbound_label":null,"outbound_source":null,"record_url":null,"record_label":null,"record_kind":null,"record_source":null,"download_url":"https://etheses.whiterose.ac.uk/id/eprint/20785/1/Burdett_DS_MechanicalEngineering_PhD_2018.pdf","download_label":"Download PDF","download_source":"dc:identifier.uri","access_status":null,"embargo_until":null,"access_note":null},"source_record":{"url":"https://etheses.whiterose.ac.uk/cgi/oai2?verb=GetRecord&metadataPrefix=uketd_dc&identifier=oai%3Aetheses.whiterose.ac.uk%3A20785","prefix":"uketd_dc"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Summers, Jon"]},{"key":"dc:contributor.sponsor","label":"Sponsor","values":["aql"]},{"key":"dc:creator","label":"Author","values":["Burdett, Daniel Simon"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date","label":"Dc Date","values":["2018-01"]},{"key":"dc:date.issued","label":"Date","values":["2018-01"]},{"key":"dc:publisher.commercial","label":"Dc Publisher Commercial","values":["University of Leeds"]},{"key":"dc:publisher.department","label":"Dc Publisher Department","values":["School of Mechanical Engineering (Leeds)"]},{"key":"dc:publisher.institution","label":"Dc Publisher Institution","values":["University of Leeds"]},{"key":"dc:relation.isreferencedby","label":"Dc Relation Isreferencedby","values":["https://etheses.whiterose.ac.uk/id/eprint/20785/"]},{"key":"dc:relation.references","label":"Dc Relation References","values":["[1] aql, “Colocation in Leeds,” [Online]. Available: https://www.aql.com/news/268/. [Accessed 16 12 2014]. [2] SearchMicroServices, “colocation (colo),” 08 2015. [Online]. Available: http://searchmicroservices.techtarget.com/definition/colocation-colo. [Accessed 20 11 2017]. [3] J. Mitchell-Jackson, J. G. Koomey, M. Blazek and B. Nordman, “National and regional implications of internet data center growth in the US,” Resources, conservation and Recycling, vol. 36, no. 3, pp. 175-185, 2002. [4] J. Glanz, “THE CLOUD FACTORIES - Power, Pollution and the Internet,” The New York Times, 22 9 2012. [Online]. Available: http://www.nytimes.com/2012/09/23/technology/data-centers-waste-vast-amounts-of-energy-belying-industry-image.html?pagewanted=all&_r=1&. [Accessed 14 12 2014]. [5] Uptime Institute, “2013 Data Center Survey Results,” 14 08 2013. [Online]. Available: http://blog.uptimeinstitute.com/2013/08/2013-data-center-industry-survey-results/. [Accessed 14 12 2014]. [6] J. Koomey, “Growth in data center electricity use 2005 to 2010.,” A report by Analytical Press, completed at the request of The New York Times, 2011. [7] J. Karlsson and B. Moshfegh, “Investigation of indoor climate and power usage in a data center,” Energy and Buildings, vol. 37, no. 10, pp. 1075-1083, 2005. [8] H. S. Dunn, “Thematic Reports, Global information society watch 2010, Focus on ICTs and environmental sustainability (APC & HIVOS).,” 2010. [9] G. Cook and D. Pomerantz, “Clicking clean: A guide to building the green Internet.,” 05 2015. [Online]. Available: http://www. greenpeace. org/usa/wp-content/uploads/legacy/Global/usa/planet3/PDFs/2015ClickingClean. pdf. [Accessed 16 01 2017]. [10] M. Avgerinou, P. Bertoldi and L. Castellazzi, “Trends in Data Centre Energy Consumption under the European Code of Conduct for Data Centre Energy Efficiency.,” Energies, vol. 10, no. 10, 2017. [11] M. Acton, L. Newcombe, J. Booth, S. Flucker, P. Latham, S. Strutt and T. Tozer, “2017 Best Practice Guidelines for the EU Code of Conduct on Data Centre Energy Efficiency,” Publications Office of the European Union, 2017. [12] Y. Joshi and P. Kumar, “Introduction to Data Center Energy Flow and Thermal Management,” in Energy Efficient Thermal Management of Data Centers, Springer US, 2012, pp. 1-38. [13] B. Fakhim, M. Behnia, S. Armfield and N. Srinarayana, “Cooling solutions in an operational data centre: A case study,” Applied Thermal Engineering, vol. 31, no. 14, pp. 2279-2291, 2011. [14] S. Shrivastava, B. Sammakia, R. Schmidt, M. Iyengar and J. Van Gilder, “Experimental-Numerical Comparison for a High-Density Data Center: Hot Spot Heat Fluxes in Excess of 500 W/ft2.,” in Thermal and Thermomechanical Phenomena in Electronics Systems, 2006. ITHERM'06. The Tenth Intersociety Conference on., 2006. [15] L. A. Barroso and U. Hölzle, “The case for energy-proportional computing.,” Computer, vol. 40, no. 12, 2007. [16] A. Greenberg, J. Hamilton, D. Maltz and P. Patel, “The cost of a cloud: research problems in data center networks,” ACM SIGCOMM computer communication review, vol. 39, no. 1, pp. 68-73, 2008. [17] M. K. Patterson, “Energy Efficiency Metrics,” in Energy Efficient Thermal Management of Data Centres, 2012. [18] M. Arregoces and M. Portolani, Data center fundamentals, Cisco Systems, Inc, 2004. [19] R. Lindsay, “Trend: Colocation facilities provide tools to manage data center infrastructure,” Network World, 22 6 2017. [Online]. Available: https://www.networkworld.com/article/3203026/data-center/trend-colocation-facilities-provide-enterprises-with-tools-to-manage-data-center-infrastructure.html. [Accessed 1 8 2016]. [20] K. Kant, “Data center evolution: A tutorial on state of the art, issues, and challenges,” Computer Networks, vol. 53, no. 17, pp. 2939-2965, 2009. [21] K. Ebrahimi, G. Jones and A. Fleischer, “A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities,” Renewable and Sustainable Energy Reviews, vol. 31, pp. 622-638, 2014. [22] X. Fan, W. D. Weber and L. A. Barroso, “Power provisioning for a warehouse-sized computer,” ACM SIGARCH Computer Architecture News., vol. 35, no. 2, 2007. [23] L. A. Barroso, J. Clidaras and U. Hölzle, “Datacenter Basics,” in The Datacenter as a Computer: An Introduction to the Design of Warehouse-Scale Machines, Madison, Morgan & Claypool Publishers, 2009, pp. 47-66. [24] R. Miller, “Facebook Has Spent $210 Million on Oregon Data Center,” Data Center Knowledge, 30 01 2012. [Online]. Available: http://www.datacenterknowledge.com/archives/2012/01/30/facebook-has-spent-210-million-on-oregon-data-center. [Accessed 10 04 2017]. [25] P. Kumar and Y. Joshi, “Fundamentals of Data Center Airflow Management,” in Energy Efficient Thermal Management of Data Centers, Springer, 2012. [26] D. Anderson, “IEEE Annals of the History of Computing,” in Tom Kilburn: A Pioneer of Computer Design, IEEE, 2009, pp. 82-86. [27] A. Bartels, “Data Center Evolution: 1960 to 2000,” CLOUD INDUSTRY INSIGHTS , 31 8 2011. [Online]. Available: http://www.rackspace.com/blog/datacenter-evolution-1960-to-2000/. [Accessed 12 12 2014]. [28] M. Ellsworth, L. Campbell, R. Simons, M. Iyengar, R. Schmidt and R. Chu, “The evolution of water cooling for IBM large server systems: Back to the future.,” in Thermal and Thermomechanical Phenomena in Electronic Systems, 2008. ITHERM 2008. 11th Intersociety Conference on, 2008. [29] J. Woods, “The evolution of the data center : Timeline from the Mainframe to the Cloud,” Silicon Angle, 5 3 2014. [Online]. Available: http://siliconangle.com/blog/2014/03/05/the-evolution-of-the-data-center-timeline-from-the-mainframe-to-the-cloud-tc0114/?. [Accessed 5 12 14]. [30] M. Walport, “The Internet of Things: making the most of the Second Digital Revolution,” UK Government, London, 2014. [31] G. Moore, “Cramming more components onto integrated circuits.,” Electronics, vol. 38, 1965. [32] G. Moore, “Progress in digital integrated electronics,” Electron Devices Meeting, vol. 21, 1975. [33] P. Huber and M. Mills, “Dig more coal -- the PCs are coming,” Forbes, 1999. [34] Lawrence Berkeley National Laboratory , “COMPUTERS ARE GREEN AFTER ALL,” Wired, 2001. [35] R. E. Brown, E. R. Masanet, B. Nordman, W. F. Tschudi, A. Shehabi, J. Stanley, J. G. S. D. A. Koomey and P. T. Chan, “Report to Congress on Server and Data Center Energy Efficiency: Public Law 109-431,” Environmental Protection Agency, 2008. [36] A. Shehabi, S. Smith, D. Sartor, R. Brown, M. Herrlin, J. Koomey, E. Masanet, N. Horner, I. Azevedo and W. Lintner, “United States Data Center Energy Usage Report,” Lawrence Berkeley National Laboratory, 2016. [37] J. Koomey, “A Decade of Data Center Efficiency: What’s Past is Prologue!,” in Semi-Therm 2017, San Jose, 2017. [38] International Energy Agency, Worlds Energy Outlook 2012, 2012. [39] D. Mascola, “CRAC VS CRAH,” Data Center Huddle, 11 08 2011. [Online]. Available: http://www.dchuddle.com/2011/crac-v-crah/. [Accessed 20 12 2017]. [40] S. Yeo and H. H. S. Lee, “Peeling the Power Onion of Data Centers,” in Energy Efficient Thermal Management of Data Centers, Atlanta, Springer Science+Business Media, 2012, pp. 137-169. [41] S. Greenberg, E. Mills, B. Tschudi, P. Rumsey and B. Myatt, “Best practices for data centers: Lessons learned from benchmarking 22 data centers.,” Proceedings of the ACEEE Summer Study on Energy Efficiency in Buildings in Asilomar, CA. ACEEE,, pp. 76-87, 2006. [42] S. Mittal, “Power Management Techniques for Data Centers: A Survey,” 2014. [43] C. D. Patel, “A vision of energy aware computing from chips to data centers,” in The International Symposium on Micro-Mechanical Engineering. , 2003. [44] T. Lu, X. Lü, M. Remes and M. Viljanen, “Investigation of air management and energy performance in a data center in Finland: Case study,” Energy and Buildings , vol. 43, no. 12, pp. 3360-3372, 2011. [45] LBNL, “Data centre website of Lawrence Berkeley National Laboratory;,” 2003. [Online]. Available: http://hightech.lbl.gov/datacenters. [Accessed 1 12 2014]. [46] H. S. Sun and S. E. Lee, “Case study of data centers' energy performance,” Energy and Buildings, vol. 38, no. 5, pp. 522-533, 2006. [47] Uptime Institute, “Heat Density Trends in Data Processing, Computer Systems and Telecommunications Equipment,” The Upsite Network, Santa Fe, NM, 2000. [48] D. Lazarus, “Net Complex A Dilemma For San Jose / SERVER FARM: Plant would tax grid,” San Francisco Chronicle, 22 3 2001. [49] J. Mitchell-Jackson, J. G. Koomey, B. Nordman and M. Blazek, “Data center power requirements: measurements from Silicon Valley,” Energy, vol. 28, no. 8, pp. 837-850, 2003. [50] P. Parida, M. David, M. Iyengar, M. Schultz, M. Gaynes, V. Kamath, B. Kochuparambil and T. Chainer, “Experimental investigation of water cooled server microprocessors and memory devices in an energy efficient chiller-less data center,” in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE, 2012. [51] M. David, M. Iyengar, P. Parida, R. Simons, M. Schultz, M. Gaynes, R. Schmidt and T. Chainer, “Experimental characterization of an energy efficient chiller-less data center test facility with warm water cooled servers,” in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE, 2012. [52] J. Summers, N. Kapur and H. Thompson, “Design of Data Centre Rack Arrangements Using Open Source Software,” in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2013 29th Annual IEEE, 2013. [53] E. Samadiani, Y. Joshi and F. Mistree, “The thermal design of a next generation data center: a conceptual exposition,” Journal of Electronic Packaging, vol. 130, no. 4, 2008. [54] J. Marcinichen, J. Olivier and J. Thome, “On-chip two-phase cooling of datacenters: Cooling system and energy recovery evaluation,” Applied Thermal Engineering, vol. 41, pp. 36-51, 2012. [55] A. Shah and C. Patel, “Designing environmentally sustainable electronic cooling systems using exergo‐thermo‐volumes,” International Journal of Energy Research, vol. 33, no. 14, pp. 1266-1277, 2009. [56] J. Marcinichen, J. Thome and B. Michel, “Cooling of microprocessors with micro-evaporation: A novel two-phase cooling cycle,” International Journal of Refrigeration, vol. 33, no. 7, pp. 1264-1276, 2010. [57] M. Iyengar, M. David, P. Parida, V. Kamath, B. Kochuparambil, D. Graybill, M. Schultz, M. Gaynes, R. Simons, R. Schmidt and T. Chainer, “Server liquid cooling with chiller-less data center design to enable significant energy savings,” in Iyengar, Madhusudan, et al. \"Server liquid cooling with chiller-less data center design to enable significant energy savings.\" Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE, 2012. [58] G. A. Brady, N. Kapur, J. L. Summers and H. M. Thompson, “A case study and critical assessment in calculating power usage effectiveness for a data centre,” Energy Conversion and Management, vol. 76, pp. 155-161, 2013. [59] C. Longbottom, “Water cooling vs. air cooling: The rise of water use in data centres,” Computer Weekly, 08 2011. [Online]. Available: http://www.computerweekly.com/tip/Water-cooling-vs-air-cooling-The-rise-of-water-use-in-data-centres. [Accessed 20 11 2017]. [60] R. Schmidt, E. Cruz and M. Iyengar, “Challenges of data center thermal management,” IBM Journal of Research and Development, vol. 49, no. 4.5, pp. 709-723, 2005. [61] D. Dyer, “Current trends/challenges in datacenter thermal management—a facilities perspective,” in presentation at ITHERM, San Diego, CA, 2006. [62] A. Radmehr, R. Schmidt, K. Karki and S. Patankar, “Distributed leakage flow in raised-floor data centers,” in ASME 2005 Pacific Rim Technical Conference and Exhibition on Integration and Packaging of MEMS, NEMS, and Electronic Systems collocated with the ASME 2005 Heat Transfer Summer Conference., 2005. [63] R. Schmidt and E. Cruz, “Cluster of high powered racks within a raised floor computer data center: effect of perforated tile flow distribution on rack inlet air temperatures,” in ASME 2003 International Mechanical Engineering Congress and Exposition. American Society of Mechanical Engineers, 2003. [64] R. Schmidt, K. Karki and S. and Patankar, “Raised-floor data center: perforated tile flow rates for various tile layouts,” in Thermal and Thermomechanical Phenomena in Electronic Systems, 2004. ITHERM'04. The Ninth Intersociety Conference on, 2004. [65] R. Schmidt, K. Karki, K. Kelkar, A. Radmehr and S. Patankar, “Measurements and predictions of the flow distribution through perforated tiles in raised floor data centers,” in Proc. of Pacific Rim/ASME International Electronic Packaging Technical Conferenceof (IPACK), Kauai, HI, 2001. [66] J. VanGilder and R. Schmidt, “Airflow Uniformity through perforated tiles in a raised-floor Data Center,” in ASME 2005 Pacific Rim Technical Conference and Exhibition on Integration and Packaging of MEMS, NEMS, and Electronic Systems collocated with the ASME 2005 Heat Transfer Summer Conference, 2005. [67] ASHRAE, Thermal Guidelines for Data Processing Environments, Atlanta: ASHRAE, 2012. [68] S. Shrivastava, A. Calder and M. Ibrahim, “Quantitative comparison of air containment systems.,” in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. IEEE, 2012. [69] J. Niemann, K. Brown and V. Avelar, “Impact of hot and cold aisle containment on data center temperature and efficiency.,” Schneider Electric Data Center Science Center, 2011. [70] J. Sasser, “A Look at Data Center Cooling Technologies,” Uptime Institute, 30 05 2015. [Online]. Available: https://journal.uptimeinstitute.com/a-look-at-data-center-cooling-technologies/. [Accessed 30 09 2017]. [71] A. Bar-Cohen, M. Arik and M. Ohadi, “Direct liquid cooling of high flux micro and nano electronic components.,” Proceedings of the IEEE, vol. 94, no. 8, pp. 1549-1570, 2006. [72] R. Miller, “Rise of Direct Liquid Cooling in Data Centers Likely Inevitable,” Data Center Knowledge, 09 012 2014. [Online]. Available: http://www.datacenterknowledge.com/archives/2014/12/09/rise-direct-liquid-cooling-data-centers-likely-inevitable. [Accessed 29 09 2017]. [73] M. Ellsworth and M. Iyengar, “Energy efficiency analyses and comparison of air and water cooled high performance servers,” in ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability, 2009. [74] G. F. Davies, G. G. Maidment and R. M. Tozer, “Using data centres for combined heating and cooling: An investigation for London,” Applied Thermal Engineering, vol. 94, pp. 296-304, 2016. [75] G. McFarland, “The Evolution of the Microprocessor,” in Microprocessor Design: A practical design guide from design planning to manufacturing., McGraw-Hill, 2006, pp. 1-37. [76] M. Vogel, T. Chen, S. Doan, H. Harrison and R. Nair, “New approach to system server air flow/thermal design development, validation and advancement in green fan performance.,” in Semiconductor Thermal Measurement and Management Symposium, 2010. SEMI-THERM 2010. 26th Annual IEEE., 2010. [77] K. Muroya, T. Kinoshita, H. Tanaka and M. Youro, “Power reduction effect of higher room temperature operation in data centers.,” in Network Operations and Management Symposium (NOMS), 2010 IEEE., 2010. [78] M. Zapater, O. Tuncer, J. Ayala, J. Moya, K. Vaidyanathan, K. Gross and A. Coskun, “Leakage-aware cooling management for improving server energy efficiency,” IEEE Transactions on Parallel and Distributed Systems, vol. 26, no. 10, pp. 2764-2777, 2015. [79] ASHRAE, “ASHRAE TC9.9 Data Center Power Equipment Thermal,” 2015. [80] ASHRAE, “2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope,” 2004. [81] “2011 Thermal Guidelines for Data Processing Environments – Expanded Data Center Classes and Usage Guidance,” 2011. [82] The Green Grid, “UPDATED AIR-SIDE FREE COOLING MAPS: THE IMPACT OF ASHRAE 2011 ALLOWABLE RANGES,” 2012. [83] M. G. Patterson, “What is energy efficiency?: Concepts, indicators and methodological issues.,” Energy policy, vol. 24, no. 5, pp. 377-390, 1996. [84] P. Bhattacharya, “Data Center Monitoring,” in Energy Efficient Thermal Management of Data Centers, 2012. [85] C. Malone and C. Belady, “Metrics to characterize data center & IT equipment energy use.,” in Proceedings of the Digital Power Forum, Richardson, Texas, 2006. [86] The Green Grid, “The Green Grid data center power efficiency metrics: PUE and DCiE,” Green Grid report , 2007. [87] EPA, “Recommendations for Measuring and Reporting Overall Data Center Efficiency,” Energystar, 2010. [88] International Organzation for Standardization, “ISO/IEC 30134-2:2016,” 04 2016. [Online]. Available: https://www.iso.org/standard/63451.html. [Accessed 1 12 2017]. [89] Uptime Institute, “2013 Data Center Industry Survey,” 2013. [90] R. Miller, “Uptime Institute: The Average PUE is 1.8,” Data Center Knowledge, 10 05 2011. [Online]. Available: http://www.datacenterknowledge.com/archives/2011/05/10/uptime-institute-the-average-pue-is-1-8. [Accessed 14 09 2017]. [91] A. Sullivan, “ENERGY STAR® for Data Centers,” Energy Star, 2010. [92] M. Salim and R. Tozer, “Data Centers’ Energy Auditing and Benchmarking-Progress,” in ASHRAE Winter Conference, 2010. [93] Y. Jumie and M. Roshan, “A critical analysis of Power Usage Effectiveness and its use in communicating data center energy consumption,” Energy and Buildings, vol. 64, pp. 90-94, 2013. [94] The Green Grid, “ERE: A metric for measuring the benefit of reuse energy from a data center,” 2010. [95] J. Kaplan, W. Forrest and N. Kindler, “Revolutionizing data center energy efficiency,” McKinsey & Company, 2008. [96] S. Walker, “Three ways to boost datacenter utilization,” Ericsson, 22 03 2016. [Online]. Available: http://cloudblog.ericsson.com/digital-services/3-ways-to-boost-datacenter-utilization. [Accessed 01 11 2017]. [97] J. Barr, “Cloud Computing, Server Utilization, & the Environment,” Amazon, 05 05 2015. [Online]. Available: https://aws.amazon.com/blogs/aws/cloud-computing-server-utilization-the-environment/. [Accessed 1 11 2017]. [98] The Green Grid, “Proxy Proposals for Measuring Data Center Productivity,” 2009. [99] Standard Performance Evaluation Corporation, “SPECpower_ssj2008,” SPEC, 05 10 2017. [Online]. Available: https://www.spec.org/power_ssj2008/. [Accessed 2017 10 12]. [100] Fontecchio, “SPEC benchmark measures servers' performance-to-power ratio,” 12 12 2007. [Online]. Available: http://searchdatacenter.techtarget.com/news/1286006/SPEC-benchmark-measures-servers-performance-to-power-ratio. [Accessed 2017 10 07]. [101] SPECpower, “SPEC_ssj2008 - ssj Design Document,” 30 05 2012. [Online]. Available: https://www.spec.org/power/docs/SPECpower_ssj2008-Design_ssj.pdf. [Accessed 12 07 2017]. [102] Java Oracle, “Interface ScheduledExecutorService,” 2016. [Online]. Available: https://docs.oracle.com/javase/7/docs/api/java/util/concurrent/ScheduledExecutorService.html. [Accessed 11 07 2017]. [103] Standard Performance Evaluation Corporation, “Design Document - Control and Collect System SPECpower_ssj2008,” 30 05 2012. [Online]. Available: https://www.spec.org/power/docs/SPECpower_ssj2008-Design_ccs.pdf. [Accessed 04 07 2017]. [104] Top500, “THE LINPACK BENCHMARK,” 05 2012. [Online]. Available: https://www.top500.org/project/linpack/. [Accessed 05 07 2017]. [105] Green500, “TOP500 Meanderings: Supercomputers Take Big Green Leap in 2017,” 5 09 2017. [Online]. Available: https://www.top500.org/green500/. [Accessed 12 10 2017]. [106] ARM, “Arm Processors for the Widest Range of Devices—from Sensors to Servers,” 2017. [Online]. Available: https://www.arm.com/products/processors. [Accessed 12 07 2017]. [107] Intel, “INTEL® CORE™ PROCESSORS,” 2017. [Online]. Available: https://www.intel.com/content/www/us/en/products/processors/core.html. [Accessed 12 08 2017]. [108] StressLinux, “Welcome to stresslinux,” 2016 03 15. [Online]. Available: https://www.stresslinux.org/sl/. [Accessed 25 08 2016]. [109] T. Morgan, “Brit server maker Avantek puts its back into ARM servers,” The Register, 05 07 2013. [Online]. Available: https://www.theregister.co.uk/2013/07/05/avantek_calxeda_arm_server/. [Accessed 20 10 2017]. [110] Zabbix, “Zabbix Documentation 2.2,” Zabbix SIA, 2014. [Online]. Available: https://www.zabbix.com/documentation/2.2/manual/appendix/config/zabbix_server. [Accessed 31 10 2016]. [111] Omega, “Thermal Handheld Anemometer with Real-Time Data Logger,” Omega, 2017. [Online]. Available: https://www.omega.co.uk/pptst/HHF2005HW.html. [Accessed 20 11 2017]. [112] Java Oracle, “Java SE 7 Advanced and Java SE 7 Support (formerly known as Java for Business 7),” 2014. [Online]. Available: http://www.oracle.com/technetwork/java/javase/documentation/javase7supportreleasenotes-1601161.html. [Accessed 23 07 2017]. [113] SPECpower Committee, “Power and Performance Benchmark Methodology v2.2,” 12 03 2014. [Online]. Available: https://www.spec.org/power/docs/SPEC-Power_and_Performance_Methodology.pdf. [Accessed 27 08 2017]. [114] die.net, “ipmitool(1) - Linux man page,” 2017. [Online]. Available: https://linux.die.net/man/1/ipmitool. [Accessed 12 06 2017]. [115] MySQL, “MySQL Downloads,” 2017. [Online]. Available: https://www.mysql.com/downloads/. [Accessed 31 01 2017]. [116] jboss.org, “RichFaces Photo Album Application Guide,” Red Hat, 2009. [Online]. Available: https://docs.jboss.org/richfaces/latest_3_3_X/en/realworld/html_single/. [Accessed 31 01 2017]. [117] Apache, “Apache JMeter™,” [Online]. [Accessed 22 04 2017]. [118] M. Tatchell-Evans, N. Kapur, J. Summers, H. Thompson and D. Oldham, “An experimental and theoretical investigation of the extent of bypass air within data centres employing aisle containment, and its impact on power consumption.,” Applied Energy, vol. 186, pp. 457-469, 2017. [119] ebmpapst, “Compact Fans for AC and DC - ebmpapst,” 03 2014. [Online]. Available: http://www.farnell.com/datasheets/1945647.pdf. [Accessed 30 11 2015]. [120] Furness Controls, “Single point Pitot Static Tube (FCO65),” 2017. [Online]. Available: https://www.furness-controls.com/product/fco65/?back=products&category=flow-elementsSingle point Pitot Static Tube (FCO65). [Accessed 12 07 2017]. [121] CGPM, “Comptes Rendus de la 10e,” 1956. [122] Brocade Communications Systems, Inc, “DATA CENTER SWITCHES,” 2017. [Online]. Available: http://www.brocade.com/en/products-services/switches/data-center-switches.html. [Accessed 15 10 2017]. [123] APC, “Rack PDU, Switched, 1U, 12A/208V, 10A/230V, (8)C13,” Schneider Electric, 2017. [Online]. Available: http://www.apc.com/shop/uk/en/products/Rack-PDU-Switched-1U-12A-208V-10A-230V-8-C13/P-AP7920B?isCurrentSite=true. [Accessed 15 10 2017]. [124] SigmaZone, “Quantum XL Software for Microsoft® Excel®,” SigmaZone, 2013. [Online]. Available: http://www.sigmazone.com/QuantumXL.htm. [Accessed 1 11 2017]. [125] J. Domingo, “Sun Fire V20z,” PCMag, 11 07 2005. [Online]. Available: http://uk.pcmag.com/sun-fire-v20z/27118/review/sun-fire-v20z. [Accessed 20 10 2017]. [126] J. Burt, “30 Percent of Servers Worldwide Sit Idle, Report Says,” eWeek, 15 06 2015. [Online]. Available: http://www.eweek.com/servers/30-percent-of-servers-worldwide-sit-idle-report-says. [Accessed 04 12 2017]."]},{"key":"dc:type","label":"Dc Type","values":["Thesis"]},{"key":"dc:type.qualificationlevel","label":"Dc Type Qualificationlevel","values":["doctoral"]},{"key":"dc:type.qualificationname","label":"Dc Type Qualificationname","values":["Ph.D"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.dcterms_iso639_2","label":"Language (ISO 639-2)","values":["eng"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier","label":"Identifier","values":["uk.bl.ethos.745617"]},{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://etheses.whiterose.ac.uk/id/eprint/20785/1/Burdett_DS_MechanicalEngineering_PhD_2018.pdf"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["Data centres are an increasingly large contributing factor to the consumption of electricity globally, and any improvements to their effectiveness are important in minimising their effect on the environment. This study aims to achieve this by looking at ways of understanding and more effectively utilising IT in data centre spaces. This was achieved through the testing of a range of ways of creating virtual load, and employing them on servers in a controlled thermal environment. A Generic Server Wind-tunnel was designed and built which afforded control of thermal environment and six different servers were tested within, yielding results on performance and thermal effect. Further testing was also conducted on a High Performance Computing server with a view to understanding the effect of internal temperature on performance. Transfer functions were created for each of the six servers, predicting behaviour reliability for five output functions and validating the developed methodology to an appropriate accuracy. The trends seen and the methodology presented should allowed data centre managers better insight into the behaviour of their servers."]},{"key":"dc:format","label":"Dc Format","values":["text"]},{"key":"dcterms:accessrights","label":"Dcterms Accessrights","values":["public"]},{"key":"dc:title","label":"Title","values":["Analysis of Thermal and Compute Performance of Data Centre Servers"]}]}],"canonical_facts":{"dc:contributor.advisor":["Summers, Jon"],"dc:contributor.sponsor":["aql"],"dc:creator":["Burdett, Daniel Simon"],"dc:date":["2018-01"],"dc:date.issued":["2018-01"],"dc:description.abstract":["Data centres are an increasingly large contributing factor to the consumption of electricity globally, and any improvements to their effectiveness are important in minimising their effect on the environment. This study aims to achieve this by looking at ways of understanding and more effectively utilising IT in data centre spaces. This was achieved through the testing of a range of ways of creating virtual load, and employing them on servers in a controlled thermal environment. A Generic Server Wind-tunnel was designed and built which afforded control of thermal environment and six different servers were tested within, yielding results on performance and thermal effect. Further testing was also conducted on a High Performance Computing server with a view to understanding the effect of internal temperature on performance. Transfer functions were created for each of the six servers, predicting behaviour reliability for five output functions and validating the developed methodology to an appropriate accuracy. The trends seen and the methodology presented should allowed data centre managers better insight into the behaviour of their servers."],"dc:format":["text"],"dc:identifier":["uk.bl.ethos.745617"],"dc:identifier.uri":["https://etheses.whiterose.ac.uk/id/eprint/20785/1/Burdett_DS_MechanicalEngineering_PhD_2018.pdf"],"dc:language.dcterms_iso639_2":["eng"],"dc:publisher.commercial":["University of Leeds"],"dc:publisher.department":["School of Mechanical Engineering (Leeds)"],"dc:publisher.institution":["University of Leeds"],"dc:relation.isreferencedby":["https://etheses.whiterose.ac.uk/id/eprint/20785/"],"dc:relation.references":["[1] aql, “Colocation in Leeds,” [Online]. Available: https://www.aql.com/news/268/. [Accessed 16 12 2014]. [2] SearchMicroServices, “colocation (colo),” 08 2015. [Online]. Available: http://searchmicroservices.techtarget.com/definition/colocation-colo. [Accessed 20 11 2017]. [3] J. Mitchell-Jackson, J. G. Koomey, M. Blazek and B. Nordman, “National and regional implications of internet data center growth in the US,” Resources, conservation and Recycling, vol. 36, no. 3, pp. 175-185, 2002. [4] J. Glanz, “THE CLOUD FACTORIES - Power, Pollution and the Internet,” The New York Times, 22 9 2012. [Online]. Available: http://www.nytimes.com/2012/09/23/technology/data-centers-waste-vast-amounts-of-energy-belying-industry-image.html?pagewanted=all&_r=1&. [Accessed 14 12 2014]. [5] Uptime Institute, “2013 Data Center Survey Results,” 14 08 2013. [Online]. Available: http://blog.uptimeinstitute.com/2013/08/2013-data-center-industry-survey-results/. [Accessed 14 12 2014]. [6] J. Koomey, “Growth in data center electricity use 2005 to 2010.,” A report by Analytical Press, completed at the request of The New York Times, 2011. [7] J. Karlsson and B. Moshfegh, “Investigation of indoor climate and power usage in a data center,” Energy and Buildings, vol. 37, no. 10, pp. 1075-1083, 2005. [8] H. S. Dunn, “Thematic Reports, Global information society watch 2010, Focus on ICTs and environmental sustainability (APC & HIVOS).,” 2010. [9] G. Cook and D. Pomerantz, “Clicking clean: A guide to building the green Internet.,” 05 2015. [Online]. Available: http://www. greenpeace. org/usa/wp-content/uploads/legacy/Global/usa/planet3/PDFs/2015ClickingClean. pdf. [Accessed 16 01 2017]. [10] M. Avgerinou, P. Bertoldi and L. Castellazzi, “Trends in Data Centre Energy Consumption under the European Code of Conduct for Data Centre Energy Efficiency.,” Energies, vol. 10, no. 10, 2017. [11] M. Acton, L. Newcombe, J. Booth, S. Flucker, P. Latham, S. Strutt and T. Tozer, “2017 Best Practice Guidelines for the EU Code of Conduct on Data Centre Energy Efficiency,” Publications Office of the European Union, 2017. [12] Y. Joshi and P. Kumar, “Introduction to Data Center Energy Flow and Thermal Management,” in Energy Efficient Thermal Management of Data Centers, Springer US, 2012, pp. 1-38. [13] B. Fakhim, M. Behnia, S. Armfield and N. Srinarayana, “Cooling solutions in an operational data centre: A case study,” Applied Thermal Engineering, vol. 31, no. 14, pp. 2279-2291, 2011. [14] S. Shrivastava, B. Sammakia, R. Schmidt, M. Iyengar and J. Van Gilder, “Experimental-Numerical Comparison for a High-Density Data Center: Hot Spot Heat Fluxes in Excess of 500 W/ft2.,” in Thermal and Thermomechanical Phenomena in Electronics Systems, 2006. ITHERM'06. The Tenth Intersociety Conference on., 2006. [15] L. A. Barroso and U. Hölzle, “The case for energy-proportional computing.,” Computer, vol. 40, no. 12, 2007. [16] A. Greenberg, J. Hamilton, D. Maltz and P. Patel, “The cost of a cloud: research problems in data center networks,” ACM SIGCOMM computer communication review, vol. 39, no. 1, pp. 68-73, 2008. [17] M. K. Patterson, “Energy Efficiency Metrics,” in Energy Efficient Thermal Management of Data Centres, 2012. [18] M. Arregoces and M. Portolani, Data center fundamentals, Cisco Systems, Inc, 2004. [19] R. Lindsay, “Trend: Colocation facilities provide tools to manage data center infrastructure,” Network World, 22 6 2017. [Online]. Available: https://www.networkworld.com/article/3203026/data-center/trend-colocation-facilities-provide-enterprises-with-tools-to-manage-data-center-infrastructure.html. [Accessed 1 8 2016]. [20] K. Kant, “Data center evolution: A tutorial on state of the art, issues, and challenges,” Computer Networks, vol. 53, no. 17, pp. 2939-2965, 2009. [21] K. Ebrahimi, G. Jones and A. Fleischer, “A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities,” Renewable and Sustainable Energy Reviews, vol. 31, pp. 622-638, 2014. [22] X. Fan, W. D. Weber and L. A. Barroso, “Power provisioning for a warehouse-sized computer,” ACM SIGARCH Computer Architecture News., vol. 35, no. 2, 2007. [23] L. A. Barroso, J. Clidaras and U. Hölzle, “Datacenter Basics,” in The Datacenter as a Computer: An Introduction to the Design of Warehouse-Scale Machines, Madison, Morgan & Claypool Publishers, 2009, pp. 47-66. [24] R. Miller, “Facebook Has Spent $210 Million on Oregon Data Center,” Data Center Knowledge, 30 01 2012. [Online]. Available: http://www.datacenterknowledge.com/archives/2012/01/30/facebook-has-spent-210-million-on-oregon-data-center. [Accessed 10 04 2017]. [25] P. Kumar and Y. Joshi, “Fundamentals of Data Center Airflow Management,” in Energy Efficient Thermal Management of Data Centers, Springer, 2012. [26] D. Anderson, “IEEE Annals of the History of Computing,” in Tom Kilburn: A Pioneer of Computer Design, IEEE, 2009, pp. 82-86. [27] A. Bartels, “Data Center Evolution: 1960 to 2000,” CLOUD INDUSTRY INSIGHTS , 31 8 2011. [Online]. Available: http://www.rackspace.com/blog/datacenter-evolution-1960-to-2000/. [Accessed 12 12 2014]. [28] M. Ellsworth, L. Campbell, R. Simons, M. Iyengar, R. Schmidt and R. Chu, “The evolution of water cooling for IBM large server systems: Back to the future.,” in Thermal and Thermomechanical Phenomena in Electronic Systems, 2008. ITHERM 2008. 11th Intersociety Conference on, 2008. [29] J. Woods, “The evolution of the data center : Timeline from the Mainframe to the Cloud,” Silicon Angle, 5 3 2014. [Online]. Available: http://siliconangle.com/blog/2014/03/05/the-evolution-of-the-data-center-timeline-from-the-mainframe-to-the-cloud-tc0114/?. [Accessed 5 12 14]. [30] M. Walport, “The Internet of Things: making the most of the Second Digital Revolution,” UK Government, London, 2014. [31] G. Moore, “Cramming more components onto integrated circuits.,” Electronics, vol. 38, 1965. [32] G. Moore, “Progress in digital integrated electronics,” Electron Devices Meeting, vol. 21, 1975. [33] P. Huber and M. Mills, “Dig more coal -- the PCs are coming,” Forbes, 1999. [34] Lawrence Berkeley National Laboratory , “COMPUTERS ARE GREEN AFTER ALL,” Wired, 2001. [35] R. E. Brown, E. R. Masanet, B. Nordman, W. F. Tschudi, A. Shehabi, J. Stanley, J. G. S. D. A. Koomey and P. T. Chan, “Report to Congress on Server and Data Center Energy Efficiency: Public Law 109-431,” Environmental Protection Agency, 2008. [36] A. Shehabi, S. Smith, D. Sartor, R. Brown, M. Herrlin, J. Koomey, E. Masanet, N. Horner, I. Azevedo and W. Lintner, “United States Data Center Energy Usage Report,” Lawrence Berkeley National Laboratory, 2016. [37] J. Koomey, “A Decade of Data Center Efficiency: What’s Past is Prologue!,” in Semi-Therm 2017, San Jose, 2017. [38] International Energy Agency, Worlds Energy Outlook 2012, 2012. [39] D. Mascola, “CRAC VS CRAH,” Data Center Huddle, 11 08 2011. [Online]. Available: http://www.dchuddle.com/2011/crac-v-crah/. [Accessed 20 12 2017]. [40] S. Yeo and H. H. S. Lee, “Peeling the Power Onion of Data Centers,” in Energy Efficient Thermal Management of Data Centers, Atlanta, Springer Science+Business Media, 2012, pp. 137-169. [41] S. Greenberg, E. Mills, B. Tschudi, P. Rumsey and B. Myatt, “Best practices for data centers: Lessons learned from benchmarking 22 data centers.,” Proceedings of the ACEEE Summer Study on Energy Efficiency in Buildings in Asilomar, CA. ACEEE,, pp. 76-87, 2006. [42] S. Mittal, “Power Management Techniques for Data Centers: A Survey,” 2014. [43] C. D. Patel, “A vision of energy aware computing from chips to data centers,” in The International Symposium on Micro-Mechanical Engineering. , 2003. [44] T. Lu, X. Lü, M. Remes and M. Viljanen, “Investigation of air management and energy performance in a data center in Finland: Case study,” Energy and Buildings , vol. 43, no. 12, pp. 3360-3372, 2011. [45] LBNL, “Data centre website of Lawrence Berkeley National Laboratory;,” 2003. [Online]. Available: http://hightech.lbl.gov/datacenters. [Accessed 1 12 2014]. [46] H. S. Sun and S. E. Lee, “Case study of data centers' energy performance,” Energy and Buildings, vol. 38, no. 5, pp. 522-533, 2006. [47] Uptime Institute, “Heat Density Trends in Data Processing, Computer Systems and Telecommunications Equipment,” The Upsite Network, Santa Fe, NM, 2000. [48] D. Lazarus, “Net Complex A Dilemma For San Jose / SERVER FARM: Plant would tax grid,” San Francisco Chronicle, 22 3 2001. [49] J. Mitchell-Jackson, J. G. Koomey, B. Nordman and M. Blazek, “Data center power requirements: measurements from Silicon Valley,” Energy, vol. 28, no. 8, pp. 837-850, 2003. [50] P. Parida, M. David, M. Iyengar, M. Schultz, M. Gaynes, V. Kamath, B. Kochuparambil and T. Chainer, “Experimental investigation of water cooled server microprocessors and memory devices in an energy efficient chiller-less data center,” in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE, 2012. [51] M. David, M. Iyengar, P. Parida, R. Simons, M. Schultz, M. Gaynes, R. Schmidt and T. Chainer, “Experimental characterization of an energy efficient chiller-less data center test facility with warm water cooled servers,” in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE, 2012. [52] J. Summers, N. Kapur and H. Thompson, “Design of Data Centre Rack Arrangements Using Open Source Software,” in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2013 29th Annual IEEE, 2013. [53] E. Samadiani, Y. Joshi and F. Mistree, “The thermal design of a next generation data center: a conceptual exposition,” Journal of Electronic Packaging, vol. 130, no. 4, 2008. [54] J. Marcinichen, J. Olivier and J. Thome, “On-chip two-phase cooling of datacenters: Cooling system and energy recovery evaluation,” Applied Thermal Engineering, vol. 41, pp. 36-51, 2012. [55] A. Shah and C. Patel, “Designing environmentally sustainable electronic cooling systems using exergo‐thermo‐volumes,” International Journal of Energy Research, vol. 33, no. 14, pp. 1266-1277, 2009. [56] J. Marcinichen, J. Thome and B. Michel, “Cooling of microprocessors with micro-evaporation: A novel two-phase cooling cycle,” International Journal of Refrigeration, vol. 33, no. 7, pp. 1264-1276, 2010. [57] M. Iyengar, M. David, P. Parida, V. Kamath, B. Kochuparambil, D. Graybill, M. Schultz, M. Gaynes, R. Simons, R. Schmidt and T. Chainer, “Server liquid cooling with chiller-less data center design to enable significant energy savings,” in Iyengar, Madhusudan, et al. \"Server liquid cooling with chiller-less data center design to enable significant energy savings.\" Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE, 2012. [58] G. A. Brady, N. Kapur, J. L. Summers and H. M. Thompson, “A case study and critical assessment in calculating power usage effectiveness for a data centre,” Energy Conversion and Management, vol. 76, pp. 155-161, 2013. [59] C. Longbottom, “Water cooling vs. air cooling: The rise of water use in data centres,” Computer Weekly, 08 2011. [Online]. Available: http://www.computerweekly.com/tip/Water-cooling-vs-air-cooling-The-rise-of-water-use-in-data-centres. [Accessed 20 11 2017]. [60] R. Schmidt, E. Cruz and M. Iyengar, “Challenges of data center thermal management,” IBM Journal of Research and Development, vol. 49, no. 4.5, pp. 709-723, 2005. [61] D. Dyer, “Current trends/challenges in datacenter thermal management—a facilities perspective,” in presentation at ITHERM, San Diego, CA, 2006. [62] A. Radmehr, R. Schmidt, K. Karki and S. Patankar, “Distributed leakage flow in raised-floor data centers,” in ASME 2005 Pacific Rim Technical Conference and Exhibition on Integration and Packaging of MEMS, NEMS, and Electronic Systems collocated with the ASME 2005 Heat Transfer Summer Conference., 2005. [63] R. Schmidt and E. Cruz, “Cluster of high powered racks within a raised floor computer data center: effect of perforated tile flow distribution on rack inlet air temperatures,” in ASME 2003 International Mechanical Engineering Congress and Exposition. American Society of Mechanical Engineers, 2003. [64] R. Schmidt, K. Karki and S. and Patankar, “Raised-floor data center: perforated tile flow rates for various tile layouts,” in Thermal and Thermomechanical Phenomena in Electronic Systems, 2004. ITHERM'04. The Ninth Intersociety Conference on, 2004. [65] R. Schmidt, K. Karki, K. Kelkar, A. Radmehr and S. Patankar, “Measurements and predictions of the flow distribution through perforated tiles in raised floor data centers,” in Proc. of Pacific Rim/ASME International Electronic Packaging Technical Conferenceof (IPACK), Kauai, HI, 2001. [66] J. VanGilder and R. Schmidt, “Airflow Uniformity through perforated tiles in a raised-floor Data Center,” in ASME 2005 Pacific Rim Technical Conference and Exhibition on Integration and Packaging of MEMS, NEMS, and Electronic Systems collocated with the ASME 2005 Heat Transfer Summer Conference, 2005. [67] ASHRAE, Thermal Guidelines for Data Processing Environments, Atlanta: ASHRAE, 2012. [68] S. Shrivastava, A. Calder and M. Ibrahim, “Quantitative comparison of air containment systems.,” in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. IEEE, 2012. [69] J. Niemann, K. Brown and V. Avelar, “Impact of hot and cold aisle containment on data center temperature and efficiency.,” Schneider Electric Data Center Science Center, 2011. [70] J. Sasser, “A Look at Data Center Cooling Technologies,” Uptime Institute, 30 05 2015. [Online]. Available: https://journal.uptimeinstitute.com/a-look-at-data-center-cooling-technologies/. [Accessed 30 09 2017]. [71] A. Bar-Cohen, M. Arik and M. Ohadi, “Direct liquid cooling of high flux micro and nano electronic components.,” Proceedings of the IEEE, vol. 94, no. 8, pp. 1549-1570, 2006. [72] R. Miller, “Rise of Direct Liquid Cooling in Data Centers Likely Inevitable,” Data Center Knowledge, 09 012 2014. [Online]. Available: http://www.datacenterknowledge.com/archives/2014/12/09/rise-direct-liquid-cooling-data-centers-likely-inevitable. [Accessed 29 09 2017]. [73] M. Ellsworth and M. Iyengar, “Energy efficiency analyses and comparison of air and water cooled high performance servers,” in ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability, 2009. [74] G. F. Davies, G. G. Maidment and R. M. Tozer, “Using data centres for combined heating and cooling: An investigation for London,” Applied Thermal Engineering, vol. 94, pp. 296-304, 2016. [75] G. McFarland, “The Evolution of the Microprocessor,” in Microprocessor Design: A practical design guide from design planning to manufacturing., McGraw-Hill, 2006, pp. 1-37. [76] M. Vogel, T. Chen, S. Doan, H. Harrison and R. Nair, “New approach to system server air flow/thermal design development, validation and advancement in green fan performance.,” in Semiconductor Thermal Measurement and Management Symposium, 2010. SEMI-THERM 2010. 26th Annual IEEE., 2010. [77] K. Muroya, T. Kinoshita, H. Tanaka and M. Youro, “Power reduction effect of higher room temperature operation in data centers.,” in Network Operations and Management Symposium (NOMS), 2010 IEEE., 2010. [78] M. Zapater, O. Tuncer, J. Ayala, J. Moya, K. Vaidyanathan, K. Gross and A. Coskun, “Leakage-aware cooling management for improving server energy efficiency,” IEEE Transactions on Parallel and Distributed Systems, vol. 26, no. 10, pp. 2764-2777, 2015. [79] ASHRAE, “ASHRAE TC9.9 Data Center Power Equipment Thermal,” 2015. [80] ASHRAE, “2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope,” 2004. [81] “2011 Thermal Guidelines for Data Processing Environments – Expanded Data Center Classes and Usage Guidance,” 2011. [82] The Green Grid, “UPDATED AIR-SIDE FREE COOLING MAPS: THE IMPACT OF ASHRAE 2011 ALLOWABLE RANGES,” 2012. [83] M. G. Patterson, “What is energy efficiency?: Concepts, indicators and methodological issues.,” Energy policy, vol. 24, no. 5, pp. 377-390, 1996. [84] P. Bhattacharya, “Data Center Monitoring,” in Energy Efficient Thermal Management of Data Centers, 2012. [85] C. Malone and C. Belady, “Metrics to characterize data center & IT equipment energy use.,” in Proceedings of the Digital Power Forum, Richardson, Texas, 2006. [86] The Green Grid, “The Green Grid data center power efficiency metrics: PUE and DCiE,” Green Grid report , 2007. [87] EPA, “Recommendations for Measuring and Reporting Overall Data Center Efficiency,” Energystar, 2010. [88] International Organzation for Standardization, “ISO/IEC 30134-2:2016,” 04 2016. [Online]. Available: https://www.iso.org/standard/63451.html. [Accessed 1 12 2017]. [89] Uptime Institute, “2013 Data Center Industry Survey,” 2013. [90] R. Miller, “Uptime Institute: The Average PUE is 1.8,” Data Center Knowledge, 10 05 2011. [Online]. Available: http://www.datacenterknowledge.com/archives/2011/05/10/uptime-institute-the-average-pue-is-1-8. [Accessed 14 09 2017]. [91] A. Sullivan, “ENERGY STAR® for Data Centers,” Energy Star, 2010. [92] M. Salim and R. Tozer, “Data Centers’ Energy Auditing and Benchmarking-Progress,” in ASHRAE Winter Conference, 2010. [93] Y. Jumie and M. Roshan, “A critical analysis of Power Usage Effectiveness and its use in communicating data center energy consumption,” Energy and Buildings, vol. 64, pp. 90-94, 2013. [94] The Green Grid, “ERE: A metric for measuring the benefit of reuse energy from a data center,” 2010. [95] J. Kaplan, W. Forrest and N. Kindler, “Revolutionizing data center energy efficiency,” McKinsey & Company, 2008. [96] S. Walker, “Three ways to boost datacenter utilization,” Ericsson, 22 03 2016. [Online]. Available: http://cloudblog.ericsson.com/digital-services/3-ways-to-boost-datacenter-utilization. [Accessed 01 11 2017]. [97] J. Barr, “Cloud Computing, Server Utilization, & the Environment,” Amazon, 05 05 2015. [Online]. Available: https://aws.amazon.com/blogs/aws/cloud-computing-server-utilization-the-environment/. [Accessed 1 11 2017]. [98] The Green Grid, “Proxy Proposals for Measuring Data Center Productivity,” 2009. [99] Standard Performance Evaluation Corporation, “SPECpower_ssj2008,” SPEC, 05 10 2017. [Online]. Available: https://www.spec.org/power_ssj2008/. [Accessed 2017 10 12]. [100] Fontecchio, “SPEC benchmark measures servers' performance-to-power ratio,” 12 12 2007. [Online]. Available: http://searchdatacenter.techtarget.com/news/1286006/SPEC-benchmark-measures-servers-performance-to-power-ratio. [Accessed 2017 10 07]. [101] SPECpower, “SPEC_ssj2008 - ssj Design Document,” 30 05 2012. [Online]. Available: https://www.spec.org/power/docs/SPECpower_ssj2008-Design_ssj.pdf. [Accessed 12 07 2017]. [102] Java Oracle, “Interface ScheduledExecutorService,” 2016. [Online]. Available: https://docs.oracle.com/javase/7/docs/api/java/util/concurrent/ScheduledExecutorService.html. [Accessed 11 07 2017]. [103] Standard Performance Evaluation Corporation, “Design Document - Control and Collect System SPECpower_ssj2008,” 30 05 2012. [Online]. Available: https://www.spec.org/power/docs/SPECpower_ssj2008-Design_ccs.pdf. [Accessed 04 07 2017]. [104] Top500, “THE LINPACK BENCHMARK,” 05 2012. [Online]. Available: https://www.top500.org/project/linpack/. [Accessed 05 07 2017]. [105] Green500, “TOP500 Meanderings: Supercomputers Take Big Green Leap in 2017,” 5 09 2017. [Online]. Available: https://www.top500.org/green500/. [Accessed 12 10 2017]. [106] ARM, “Arm Processors for the Widest Range of Devices—from Sensors to Servers,” 2017. [Online]. Available: https://www.arm.com/products/processors. [Accessed 12 07 2017]. [107] Intel, “INTEL® CORE™ PROCESSORS,” 2017. [Online]. Available: https://www.intel.com/content/www/us/en/products/processors/core.html. [Accessed 12 08 2017]. [108] StressLinux, “Welcome to stresslinux,” 2016 03 15. [Online]. Available: https://www.stresslinux.org/sl/. [Accessed 25 08 2016]. [109] T. Morgan, “Brit server maker Avantek puts its back into ARM servers,” The Register, 05 07 2013. [Online]. Available: https://www.theregister.co.uk/2013/07/05/avantek_calxeda_arm_server/. [Accessed 20 10 2017]. [110] Zabbix, “Zabbix Documentation 2.2,” Zabbix SIA, 2014. [Online]. Available: https://www.zabbix.com/documentation/2.2/manual/appendix/config/zabbix_server. [Accessed 31 10 2016]. [111] Omega, “Thermal Handheld Anemometer with Real-Time Data Logger,” Omega, 2017. [Online]. Available: https://www.omega.co.uk/pptst/HHF2005HW.html. [Accessed 20 11 2017]. [112] Java Oracle, “Java SE 7 Advanced and Java SE 7 Support (formerly known as Java for Business 7),” 2014. [Online]. Available: http://www.oracle.com/technetwork/java/javase/documentation/javase7supportreleasenotes-1601161.html. [Accessed 23 07 2017]. [113] SPECpower Committee, “Power and Performance Benchmark Methodology v2.2,” 12 03 2014. [Online]. Available: https://www.spec.org/power/docs/SPEC-Power_and_Performance_Methodology.pdf. [Accessed 27 08 2017]. [114] die.net, “ipmitool(1) - Linux man page,” 2017. [Online]. Available: https://linux.die.net/man/1/ipmitool. [Accessed 12 06 2017]. [115] MySQL, “MySQL Downloads,” 2017. [Online]. Available: https://www.mysql.com/downloads/. [Accessed 31 01 2017]. [116] jboss.org, “RichFaces Photo Album Application Guide,” Red Hat, 2009. [Online]. Available: https://docs.jboss.org/richfaces/latest_3_3_X/en/realworld/html_single/. [Accessed 31 01 2017]. [117] Apache, “Apache JMeter™,” [Online]. [Accessed 22 04 2017]. [118] M. Tatchell-Evans, N. Kapur, J. Summers, H. Thompson and D. Oldham, “An experimental and theoretical investigation of the extent of bypass air within data centres employing aisle containment, and its impact on power consumption.,” Applied Energy, vol. 186, pp. 457-469, 2017. [119] ebmpapst, “Compact Fans for AC and DC - ebmpapst,” 03 2014. [Online]. Available: http://www.farnell.com/datasheets/1945647.pdf. [Accessed 30 11 2015]. [120] Furness Controls, “Single point Pitot Static Tube (FCO65),” 2017. [Online]. Available: https://www.furness-controls.com/product/fco65/?back=products&category=flow-elementsSingle point Pitot Static Tube (FCO65). [Accessed 12 07 2017]. [121] CGPM, “Comptes Rendus de la 10e,” 1956. [122] Brocade Communications Systems, Inc, “DATA CENTER SWITCHES,” 2017. [Online]. Available: http://www.brocade.com/en/products-services/switches/data-center-switches.html. [Accessed 15 10 2017]. [123] APC, “Rack PDU, Switched, 1U, 12A/208V, 10A/230V, (8)C13,” Schneider Electric, 2017. [Online]. Available: http://www.apc.com/shop/uk/en/products/Rack-PDU-Switched-1U-12A-208V-10A-230V-8-C13/P-AP7920B?isCurrentSite=true. [Accessed 15 10 2017]. [124] SigmaZone, “Quantum XL Software for Microsoft® Excel®,” SigmaZone, 2013. [Online]. Available: http://www.sigmazone.com/QuantumXL.htm. [Accessed 1 11 2017]. [125] J. Domingo, “Sun Fire V20z,” PCMag, 11 07 2005. [Online]. Available: http://uk.pcmag.com/sun-fire-v20z/27118/review/sun-fire-v20z. [Accessed 20 10 2017]. [126] J. Burt, “30 Percent of Servers Worldwide Sit Idle, Report Says,” eWeek, 15 06 2015. [Online]. Available: http://www.eweek.com/servers/30-percent-of-servers-worldwide-sit-idle-report-says. [Accessed 04 12 2017]."],"dcterms:accessrights":["public"],"dc:title":["Analysis of Thermal and Compute Performance of Data Centre Servers"],"dc:type":["Thesis"],"dc:type.qualificationlevel":["doctoral"],"dc:type.qualificationname":["Ph.D"]},"updated_at":"2026-11-18T22:27:46Z"}