{"id":{"repo_id":"whiterose","oai_identifier":"oai:etheses.whiterose.ac.uk:21185"},"canonical_url":"https://search.ndltd.org/etd/whiterose/oai:etheses.whiterose.ac.uk:21185","repository":{"repo_id":"whiterose","name":"White Rose University Consortium","base_url":"https://etheses.whiterose.ac.uk/cgi/oai2"},"display":{"title":"Holistic Study of Thermal Management in Direct Liquid Cooled Data Centres: from the Chip to the Environment","abstract":"The IT (Information Technology) infrastructure power consumption constitutes a large portion of global electricity consumption and a large proportion of this energy is to maintain an acceptable thermal environment for the IT equipment. Therefore, it is important to understand and improve the thermal and energy management of data centres for lower cost and higher sustainability. Toward this goal, Direct Contact Liquid Cooled (DCLC) servers, where liquid loop heat exchangers are attached to the CPU, were proposed to study the use of chiller-less energy efficient data centre. Thirty Sun Fire V20z servers in a data centre rack have their CPUs water cooled with the remaining components air cooled, together with a rear door heat exchanger to capture this air heat flow. The heat generated by the servers is ultimately transferred to the environment using an Air Handling Unit (AHU). The AHU was fitted with a water spray system to increase the heat transfer capacity. The designed DCLC system was tested and characterised in terms of power consumption and thermal performance. The design successfully provided stable inlet coolant temperature (±1℃) to the IT despite the variation in the IT workload and environmental conditions. Activating the spray reduced the thermal resistance of the AHU heat exchanger (HE) by 50%. However, the power consumption and pressure drop across the HE was increased. The flow distribution and the coolant pumping configurations of centralised (where the coolant is pumped by two central pumps connected in series) and distributed (where small pumps inside the servers are activated) was investigated. The EPANET software was used to analyse the flow and showed that the servers in the top of the rack receive a higher flow rate (by approximately 30%) than the servers in the bottom of the rack. This resulted in a variation in the CPU temperatures of different servers. Optimisation analysis proposed increasing the manifolds size to improve the flow rate and reduce the flow maldistribution. In the distributed pumping case, the CPUs temperature showed to be 2℃ higher compared with the central pumping case for the high IT workload. The rack inlet temperature was tested in the range of the ASHRAE W4 envelope in terms of CPU temperatures, power consumption and computational efficiency. Increasing the coolant inlet temperature resulted in high energy saving in the AHU, while the rack energy consumption increases marginally in idle operation and considerably more in high IT workloads. This results in an improvement in the energy effectiveness of 17% but a deterioration in the computational efficiency of 4%. Finally, a parallel study was carried out to investigate the droplet evaporation over heated surfaces which ultimately be used in studying sprays in the AHU or in direct on chip cooling via evaporation. A novel experimental design was proposed to track the lifetime of any droplet size that span the surface tension to gravitydominated regimes. A theoretical model was also proposed to predict the droplet lifetime based on the initial contact angle, contact radius and the receding contact angle. The model predicted the droplet evaporation over hydrophobic surfaces with good accuracy of an error less than 4% while under estimated the evaporation with hydrophilic surfaces.","abstract_html":"The IT (Information Technology) infrastructure power consumption constitutes a large portion of global electricity consumption and a large proportion of this energy is to maintain an acceptable thermal environment for the IT equipment. Therefore, it is important to understand and improve the thermal and energy management of data centres for lower cost and higher sustainability. Toward this goal, Direct Contact Liquid Cooled (DCLC) servers, where liquid loop heat exchangers are attached to the CPU, were proposed to study the use of chiller-less energy efficient data centre. Thirty Sun Fire V20z servers in a data centre rack have their CPUs water cooled with the remaining components air cooled, together with a rear door heat exchanger to capture this air heat flow. The heat generated by the servers is ultimately transferred to the environment using an Air Handling Unit (AHU). The AHU was fitted with a water spray system to increase the heat transfer capacity. The designed DCLC system was tested and characterised in terms of power consumption and thermal performance. The design successfully provided stable inlet coolant temperature (±1℃) to the IT despite the variation in the IT workload and environmental conditions. Activating the spray reduced the thermal resistance of the AHU heat exchanger (HE) by 50%. However, the power consumption and pressure drop across the HE was increased. The flow distribution and the coolant pumping configurations of centralised (where the coolant is pumped by two central pumps connected in series) and distributed (where small pumps inside the servers are activated) was investigated. The EPANET software was used to analyse the flow and showed that the servers in the top of the rack receive a higher flow rate (by approximately 30%) than the servers in the bottom of the rack. This resulted in a variation in the CPU temperatures of different servers. Optimisation analysis proposed increasing the manifolds size to improve the flow rate and reduce the flow maldistribution. In the distributed pumping case, the CPUs temperature showed to be 2℃ higher compared with the central pumping case for the high IT workload. The rack inlet temperature was tested in the range of the ASHRAE W4 envelope in terms of CPU temperatures, power consumption and computational efficiency. Increasing the coolant inlet temperature resulted in high energy saving in the AHU, while the rack energy consumption increases marginally in idle operation and considerably more in high IT workloads. This results in an improvement in the energy effectiveness of 17% but a deterioration in the computational efficiency of 4%. Finally, a parallel study was carried out to investigate the droplet evaporation over heated surfaces which ultimately be used in studying sprays in the AHU or in direct on chip cooling via evaporation. A novel experimental design was proposed to track the lifetime of any droplet size that span the surface tension to gravitydominated regimes. A theoretical model was also proposed to predict the droplet lifetime based on the initial contact angle, contact radius and the receding contact angle. The model predicted the droplet evaporation over hydrophobic surfaces with good accuracy of an error less than 4% while under estimated the evaporation with hydrophilic surfaces.","abstract_has_math":false,"creators":["Kadhim, Mustafa Alaa Kadhim"],"institution":"University of Leeds","degree_name":"Ph.D","degree_level":"doctoral","degree_discipline":null,"degree_department":null,"school":null,"contributors":[],"advisors":["Kapur, Nikil","Summers, Jonathan","Thompson, Harvey"],"committee_chairs":[],"committee_members":[],"year":2018,"date_issued":"2018-04","date_published":"2018-04","updated_at":"2026-11-18T22:28:23Z","subjects":[],"languages":["eng"],"rights":[],"rights_urls":[],"identifier_entries":[{"key":"dc:identifier","label":"Identifier","values":["uk.bl.ethos.749438"],"render_values":[{"text":"uk.bl.ethos.749438","href":null,"code":true}]}],"person_identifier_entries":[]},"links":{"outbound_url":null,"outbound_label":null,"outbound_source":null,"record_url":null,"record_label":null,"record_kind":null,"record_source":null,"download_url":"https://etheses.whiterose.ac.uk/id/eprint/21185/1/Holistic%20study%20of%20thermal%20management%20in%20direct%20liquid%20cooled%20data%20centres%20from%20chip%20to%20the%20environment.pdf","download_label":"Download PDF","download_source":"dc:identifier.uri","access_status":null,"embargo_until":null,"access_note":null},"source_record":{"url":"https://etheses.whiterose.ac.uk/cgi/oai2?verb=GetRecord&metadataPrefix=uketd_dc&identifier=oai%3Aetheses.whiterose.ac.uk%3A21185","prefix":"uketd_dc"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Kapur, Nikil","Summers, Jonathan","Thompson, Harvey"]},{"key":"dc:contributor.sponsor","label":"Sponsor","values":["The Iraqi Ministry of Higher Education and Scientific Research","Airedale International Air Conditioning Ltd"]},{"key":"dc:creator","label":"Author","values":["Kadhim, Mustafa Alaa Kadhim"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date","label":"Dc Date","values":["2018-04"]},{"key":"dc:date.issued","label":"Date","values":["2018-04"]},{"key":"dc:publisher.commercial","label":"Dc Publisher Commercial","values":["University of Leeds"]},{"key":"dc:publisher.department","label":"Dc Publisher Department","values":["Faculty of Engineering (Leeds)","School of Mechanical Engineering (Leeds)","Institute of Engineering Thermofluids, Surfaces & Interfaces (iETSI) (Leeds)"]},{"key":"dc:publisher.institution","label":"Dc Publisher Institution","values":["University of Leeds"]},{"key":"dc:relation.isreferencedby","label":"Dc Relation Isreferencedby","values":["https://etheses.whiterose.ac.uk/id/eprint/21185/"]},{"key":"dc:relation.references","label":"Dc Relation References","values":["1. Joshi, Y. and P. Kumar, Energy efficient thermal management of data centers. 2012: Springer Science & Business Media. 2. Khalaj, A.H. and S.K. Halgamuge, A Review on efficient thermal management of air-and liquid-cooled data centers: From chip to the cooling system. Applied Energy, 2017. 205: p. 1165-1188. 3. Patankar, S.V., Airflow and cooling in a data center. Journal of Heat Transfer, 2010. 132(7): p. 073001. 4. Rahmat Romadhon, Maisarah Ali, Ayub Mohd Mahdzir, and Y.A. Abakr, Optimization of Cooling Systems in Data Centre by Computational Fluid Dynamics Model and Simulation, in Conference on Innovative Technologies in Intelligent Systems and Industrial Applications (CITISIA 2009). 2009: Monash University, Sunway campus, Malaysia,. p. 322-327. 5. Mitchell-Jackson, J., J.G. Koomey, B. Nordman, and M. Blazek, Data center power requirements: measurements from Silicon Valley. Energy, 2003. 28(8): p. 837-850. 6. Schultz, M., M. Gaynes, P. Parida, and T. Chainer. Experimental investigation of direct attach microprocessors in a liquid-cooled chiller-less data center. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on. 2014. IEEE. 7. Brown, R.E., R. Brown, E. Masanet, B. Nordman, B. Tschudi, A. Shehabi, J. Stanley, J. Koomey, D. Sartor, and P. Chan, Report to congress on server and data center energy efficiency: Public law 109-431. 2007, Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US). 8. Koomey, J., Growth in data center electricity use 2005 to 2010. A report by Analytical Press, completed at the request of The New York Times, 2011. 9. Ebrahimi, K., G.F. Jones, and A.S. Fleischer, A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities. Renewable and Sustainable Energy Reviews, 2014. 31: p. 622-638. 10. Koomey, J.G., Worldwide electricity used in data centers. Environmental research letters, 2008. 3(3): p. 034008. 11. Garimella, S.V., T. Persoons, J. Weibel, and L.-T. Yeh, Technological drivers in data centers and telecom systems: Multiscale thermal, electrical, and energy management. Applied energy, 2013. 107: p. 66-80. 12. VanGeet, O., Best practices guide for energy-efficient data center design. 2010, EERE Publication and Product Library. 13. Alkharabsheh, S., J. Fernandes, B. Gebrehiwot, D. Agonafer, K. Ghose, A. Ortega, Y. Joshi, and B. Sammakia, A Brief Overview of Recent Developments in Thermal Management in Data Centers. Journal of Electronic Packaging, 2015. 137(4): p. 040801. 14. Rambo, J.D., Reduced-order modeling of multiscale turbulent convection: application to data center thermal management. 2006, Georgia Institute of Technology. 15. ASHRAE, T., Datacom equipment power trends and cooling applications. 2012, American Society of Heating, Refrigeration and Air-Conditioning Engineers Atlanta, GA. 16. Kheirabadi, A.C. and D. Groulx, Cooling of server electronics: A design review of existing technology. Applied Thermal Engineering, 2016. 17. Chu, R.C., R.E. Simons, M.J. Ellsworth, R.R. Schmidt, and V. Cozzolino, Review of cooling technologies for computer products. IEEE Transactions on Device and materials Reliability, 2004. 4(4): p. 568-585. 18. Ohadi, M., S. Dessiatoun, K. Choo, M. Pecht, and J.V. Lawler. A comparison analysis of air, liquid, and two-phase cooling of data centers. in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE. 2012. IEEE. 19. Steinbrecher, R.A., Data Center Environments ASHRAE's Evolving Thermal Guidelines. ASHRAE Journal, 2011. 53(12): p. 42. 20. ASHRAE, Thermal Guidelines for Data Processing Environments, ed. T. Edition. 2012. 152. 21. Jamalzadeh, M. and N. Behravan, An exhaustive framework for better data centers’ energy efficiency and greenness by using metrics. Indian Journal of Computer Science and Engineering, 2012. 2(6): p. 813-822. 22. Mathew, P., Self-benchmarking guide for data centers: Metrics, benchmarks, actions. Lawrence Berkeley National Laboratory, 2010. 23. Sharma, R.K., C.E. Bash, and C.D. Patel. Dimensionless parameters for evaluation of thermal design and performance of large-scale data centers. in 8th ASME/AIAA Joint Thermophysics and Heat Transfer Conference. 2002. 24. Herrlin, M.K., Rack cooling effectiveness in data centers and telecom central offices: The rack cooling index (RCI). Transactions-American Society of Heating Refrigerating and Air conditioning Engineers, 2005. 111(2): p. 725. 25. Herrlin, M.K. Improved data center energy efficiency and thermal performance by advanced airflow analysis. in Digital Power Forum. 2007. 26. Vangilder, J.W. and S.K. Shrivastava, Capture Index: An Airflow-Based Rack Cooling Performance Metric. ASHRAE transactions, 2007. 113(1). 27. Lettieri, D.J., C.R. Hannemann, V.P. Carey, and A.J. Shah. Lifetime exergy consumption as a sustainability metric for information technologies. in Sustainable Systems and Technology, 2009. ISSST'09. IEEE International Symposium on. 2009. IEEE. 28. Brady, G.A., Energy Efficiency in Data Centres and the Barriers to Further Improvements: An Interdisciplinary Investigation. 2016, University of Leeds. 29. Malone, C. and C. Belady. Metrics to characterize data center & IT equipment energy use. in Proceedings of the Digital Power Forum, Richardson, TX. 2006. 30. Consortium, G.G.I., Green Grid Metrics Describing Data Center Power Efficiency. Technical Committee White Paper, available at http://www. thegreengrid. org/~/media/WhitePapers/Green_Grid_Metrics_WP. pdf, 2007. 31. Stansberry, M., uptime institute annual data center industry survey report and full results.”. 2013. 32. Brady, G.A., N. Kapur, J.L. Summers, and H.M. Thompson, A case study and critical assessment in calculating power usage effectiveness for a data centre. Energy Conversion and Management, 2013. 76: p. 155-161. 33. Horner, N. and I. Azevedo, Power usage effectiveness in data centers: overloaded and underachieving. The Electricity Journal, 2016. 29(4): p. 61-69. 34. BS EN 50600-4-2:2016: Information technology. Data centre facilities and infrastructures. Power Usage Effectiveness. 2017, British Standards Institute. 35. Sun, H. and S. Lee, Case study of data centers’ energy performance. Energy and Buildings, 2006. 38(5): p. 522-533. 36. Tschudi, B., O. Vangeet, J. Cooley, and D. Azevedo, ERE: A metric for measuring the benefit of reuse energy from a data center. White Paper, 2010. 29. 37. Shah, A.J., C.E. Bash, N. Kumari, T. Cader, T.J. Breen, E.J. Walsh, and J. Punch. On the need for energy efficiency metrics that span integrated IT-facility infrastructures. in ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems. 2011. American Society of Mechanical Engineers. 38. Patterson, M.K., S.W. Poole, C.-H. Hsu, D. Maxwell, W. Tschudi, H. Coles, D.J. Martinez, and N. Bates. TUE, a new energy-efficiency metric applied at ORNL’s Jaguar. in International Supercomputing Conference. 2013. Springer. 39. Green500. Available from: https://www.Green500.org/. 40. Minartz, T., J.M. Kunkel, and T. Ludwig, Simulation of power consumption of energy efficient cluster hardware. Computer Science-Research and Development, 2010. 25(3-4): p. 165-175. 41. Newcombe, L., Z. Limbuwala, P. Latham, and V. Smith, Data centre fixed to variable energy ratio metric (dc-fver). British Computer Society, 2012. 42. Subramaniam, B. and W.-c. Feng. The Green Index: A metric for evaluating system-wide energy efficiency in HPC systems. in Parallel and Distributed Processing Symposium Workshops & PhD Forum (IPDPSW), 2012 IEEE 26th International. 2012. IEEE. 43. Beitelmal, A. and D. Fabris, Servers and data centers energy performance metrics. Energy and Buildings, 2014. 80: p. 562-569. 44. Wilde, T., A. Auweter, M.K. Patterson, H. Shoukourian, H. Huber, A. Bode, D. Labrenz, and C. Cavazzoni. DWPE, a new data center energy-efficiency metric bridging the gap between infrastructure and workload. in High Performance Computing & Simulation (HPCS), 2014 International Conference on. 2014. IEEE. 45. Sharma, R., A. Shah, C. Bash, T. Christian, and C. Patel. Water efficiency management in datacenters: Metrics and methodology. in Sustainable Systems and Technology, 2009. ISSST'09. IEEE International Symposium on. 2009. IEEE. 46. Azevedo, D., M. Patterson, J. Pouchet, and R. Tipley, Carbon usage effectiveness (CUE): a green grid data center sustainability metric. White Paper, 2010. 32. 47. Li, Z. and S.G. Kandlikar, Current status and future trends in data-center cooling technologies. Heat Transfer Engineering, 2015. 36(6): p. 523-538. 48. Geng, H., Data center handbook. 2014: John Wiley & Sons. 49. Chiriac, V.A. and F. Chiriac. Novel energy recovery systems for the efficient cooling of data centers using absorption chillers and renewable energy resources. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 50. Fakhim, B., M. Behnia, S. Armfield, and N. Srinarayana, Cooling solutions in an operational data centre: A case study. Applied thermal engineering, 2011. 31(14): p. 2279-2291. 51. Oró, E., V. Depoorter, A. Garcia, and J. Salom, Energy efficiency and renewable energy integration in data centres. Strategies and modelling review. Renewable and Sustainable Energy Reviews, 2015. 42: p. 429-445. 52. Committee, A.T., Thermal guidelines for data processing environments-expanded data center classes and usage guidance. Atlanta, 2011. 53. Xu, G., B. Guenin, and M. Vogel. Extension of air cooling for high power processors. in Thermal and Thermomechanical Phenomena in Electronic Systems, 2004. ITHERM'04. The Ninth Intersociety Conference on. 2004. IEEE. 54. Katoh, T., G. Xu, M. Vogel, and S. Novotny. New attempt of forced-air cooling for high heat-flux applications. in Thermal and Thermomechanical Phenomena in Electronic Systems, 2004. ITHERM'04. The Ninth Intersociety Conference on. 2004. IEEE. 55. Zhang, H., S. Shao, H. Xu, H. Zou, and C. Tian, Free cooling of data centers: A review. Renewable and Sustainable Energy Reviews, 2014. 35: p. 171-182. 56. Patankar, S.V. and K.C. Karki, Distribution of Cooling Airflow in a Raised-Floor Data Center. ASHRAE Transactions, 2004. 110(2). 57. Muralidharan, B., M. Ibrahim, S. Shrivistava, S. Alkharabsheh, and B. Sammakia, Impact of cold aisle containment on thermal performance of data center. ASME Paper No. IPACK2013-73201, 2013. 58. Garimella, S.V., L.-T. Yeh, and T. Persoons, Thermal management challenges in telecommunication systems and data centers. IEEE Transactions on Components, Packaging and Manufacturing Technology, 2012. 2(8): p. 1307-1316. 59. Srinarayana, N., B. Fakhim, M. Behnia, and S.W. Armfield, Thermal performance of an air-cooled data center with raised-floor and non-raised-floor configurations. Heat Transfer Engineering, 2014. 35(4): p. 384-397. 60. Walsh, E.J., T.J. Breen, J. Punch, A.J. Shah, and C.E. Bash. From chip to cooling tower data center modeling: Part II influence of chip temperature control philosophy. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2010 12th IEEE Intersociety Conference on. 2010. IEEE. 61. Tuma, P.E. The merits of open bath immersion cooling of datacom equipment. in Semiconductor Thermal Measurement and Management Symposium, 2010. SEMI-THERM 2010. 26th Annual IEEE. 2010. IEEE. 62. Tuma, P.E. Design considerations relating to non-thermal aspects of passive 2-phase immersion cooling. in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2011 27th Annual IEEE. 2011. IEEE. 63. El-Genk, M.S., Immersion cooling nucleate boiling of high power computer chips. Energy conversion and management, 2012. 53(1): p. 205-218. 64. Asadi, M., G. Xie, and B. Sunden, A review of heat transfer and pressure drop characteristics of single and two-phase microchannels. International Journal of Heat and Mass Transfer, 2014. 79: p. 34-53. 65. Kadam, S.T. and R. Kumar, Twenty first century cooling solution: Microchannel heat sinks. International Journal of Thermal Sciences, 2014. 85: p. 73-92. 66. Al-Neama, A.F., N. Kapur, J. Summers, and H.M. Thompson, An experimental and numerical investigation of the use of liquid flow in serpentine microchannels for microelectronics cooling. Applied Thermal Engineering, 2017. 116: p. 709-723. 67. Ellsworth, M.J., G.F. Goth, R.J. Zoodsma, A. Arvelo, L.A. Campbell, and W.J. Anderl, An overview of the IBM power 775 supercomputer water cooling system. Journal of Electronic Packaging, 2012. 134(2): p. 020906. 68. Burd, T.D. and R.W. Brodersen, Processor design for portable systems, in Technologies for wireless computing. 1996, Springer. p. 119-137. 69. Sarood, O., A. Gupta, and L.V. Kale. Temperature aware load balancing for parallel applications: Preliminary work. in Parallel and distributed processing workshops and phd forum (IPDPSW), 2011 IEEE international symposium on. 2011. IEEE. 70. Menon, H., B. Acun, S.G. De Gonzalo, O. Sarood, and L. Kalé. Thermal aware automated load balancing for hpc applications. in Cluster Computing (CLUSTER), 2013 IEEE International Conference on. 2013. IEEE. 71. Ge, R., X. Feng, and K.W. Cameron. Performance-constrained distributed dvs scheduling for scientific applications on power-aware clusters. in Supercomputing, 2005. Proceedings of the ACM/IEEE SC 2005 Conference. 2005. IEEE. 72. Meijer, G.I., Cooling energy-hungry data centers. Science, 2010. 328(5976): p. 318-319. 73. Kandlikar, S.G. and C.N. Hayner, Liquid cooled cold plates for industrial high-power electronic devices—Thermal design and manufacturing considerations. Heat Transfer Engineering, 2009. 30(12): p. 918-930. 74. Ouchi, M., Y. Abe, M. Fukagaya, H. Ohta, Y. Shinmoto, M. Sato, and K.-i. Iimura. Thermal management systems for data centers with liquid cooling technique of CPU. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 75. Goth, G.F., A. Arvelo, J. Eagle, M.J. Ellsworth, K.C. Marston, A.K. Sinha, and J.A. Zitz. Thermal and mechanical analysis and design of the IBM Power 775 water cooled supercomputing central electronics complex. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 76. Kheirabadi, A.C. and D. Groulx, Experimental Evaluation of a Thermal Contact Water Cooling System for Server Electronics 2017. 77. Ramakrishnan, B., S. Alkharabsheh, Y. Hadad, B. Sammakia, P.R. Chiarot, M. Seymour, and R. Tipton. Experimental characterization of a cold plate used in warm water cooling of data centers. in 2017 33rd Thermal Measurement, Modeling & Management Symposium (SEMI-THERM). 2017. 78. Inc, C.S., Operation and Maintenance Manual 2015. 79. Sahini, M., U. Chowdhury, A. Siddarth, T. Pradip, D. Agonafer, R. Zeigham, J. Metcalf, and S. Branton. Comparative study of high ambient inlet temperature effects on the performance of air vs. liquid cooled IT equipment. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2017 16th IEEE Intersociety Conference on. 2017. IEEE. 80. Zimmermann, S., I. Meijer, M.K. Tiwari, S. Paredes, B. Michel, and D. Poulikakos, Aquasar: A hot water cooled data center with direct energy reuse. Energy, 2012. 43(1): p. 237-245. 81. Zimmermann, S., M.K. Tiwari, I. Meijer, S. Paredes, B. Michel, and D. Poulikakos, Hot water cooled electronics: exergy analysis and waste heat reuse feasibility. International Journal of Heat and Mass Transfer, 2012. 55(23): p. 6391-6399. 82. Addagatla, A., J. Fernandes, D. Mani, D. Agonafer, and V. Mulay. Effect of warm water cooling for an isolated hybrid liquid cooled server. in Thermal Measurement, Modeling & Management Symposium (SEMI-THERM), 2015 31st. 2015. IEEE. 83. Druzhinin, E., A. Shmelev, A. Moskovsky, Y. Migal, V. Mironov, and A. Semin. High temperature coolant demonstrated for a computational cluster. in High Performance Computing & Simulation (HPCS), 2016 International Conference on. 2016. IEEE. 84. Druzhinin, E.A., A.B. Shmelev, A.A. Moskovsky, V.V. Mironov, and A. Semin, Server Level Liquid Cooling: Do Higher System Temperatures Improve Energy Efﬁciency? Supercomputing frontiers and innovations, 2016. 3(1): p. 67-74. 85. Garraghan, P., Y. Al-Anii, J. Summers, H. Thompson, N. Kapur, and K. Djemame. A unified model for holistic power usage in cloud datacenter servers. in Proceedings of the 9th International Conference on Utility and Cloud Computing. 2016. ACM. 86. Zeighami, R., W.A. Saunders, H. Coles, and S. Branton. Thermal performance modeling of hybrid liquid-air cooled servers. in Thermal and thermomechanical phenomena in electronic systems (itherm), 2014 ieee intersociety conference on. 2014. IEEE. 87. Li, L., W. Zheng, X. Wang, and X. Wang. Placement optimization of liquid-cooled servers for power minimization in data centers. in Green Computing Conference (IGCC), 2014 International. 2014. IEEE. 88. Ovaska, S.J., R.E. Dragseth, and S.A. Hanssen. Impact of retrofitted CPU water cooling on supercomputer performance and power consumption. in SoutheastCon, 2016. 2016. IEEE. 89. Ovaska, S.J., R.E. Dragseth, and S.A. Hanssen, Direct-to-chip liquid cooling for reducing power consumption in a subarctic supercomputer centre. International Journal of High Performance Computing and Networking, 2016. 9(3): p. 242-249. 90. Kelkar, K.M. and S.V. Patankar. Analysis and design of liquid-cooling systems using flow network modeling (FNM). in ASME 2003 International Electronic Packaging Technical Conference and Exhibition (InterPACK2003). 2003. 91. Ellsworth, M.J. Flow network analysis of the IBM power 775 supercomputer water cooling system. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on. 2014. IEEE. 92. Alkharabsheh, S., B. Ramakrishnan, and B. Sammakia. Pressure drop analysis of direct liquid cooled (DLC) rack. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2017 16th IEEE Intersociety Conference on. 2017. IEEE. 93. Sahini, M., C. Kshirsagar, M. Kumar, D. Agonafer, J. Fernandes, J. Na, V. Mulay, P. McGinn, and M. Soares. Rack-level study of hybrid cooled servers using warm water cooling for distributed vs. centralized pumping systems. in 2017 33rd Thermal Measurement, Modeling & Management Symposium (SEMI-THERM). 2017. 94. Chu, R.C., M.K. Iyengar, V. Kamath, and R.R. Schmidt, Energy efficient apparatus and method for cooling an electronics rack. 2010, Google Patents. 95. Iyengar, M., M. David, P. Parida, V. Kamath, B. Kochuparambil, D. Graybill, M. Schultz, M. Gaynes, R. Simons, and R. Schmidt. Server liquid cooling with chiller-less data center design to enable significant energy savings. in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE. 2012. IEEE. 96. David, M.P., M.K. Iyengar, P. Parida, R.E. Simons, M. Schultz, M. Gaynes, R. Schmidt, and T. Chainer. Impact of operating conditions on a chiller-less data center test facility with liquid cooled servers. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 97. Iyengar, M., M. David, P. Parida, V. Kamath, B. Kochuparambil, D. Graybill, M. Schultz, M. Gaynes, R. Simons, and R. Schmidt. Extreme energy efficiency using water cooled servers inside a chiller-less data center. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 98. Parida, P.R., T. Chainer, M. Iyengar, M. David, M. Schultz, M. Gaynes, V. Kamath, B. Kochuparambil, R. Simons, and R. Schmidt. System-Level Design for Liquid Cooled Chiller-Less Data Center. in ASME 2012 International Mechanical Engineering Congress and Exposition. 2012. American Society of Mechanical Engineers. 99. Parida, P.R., T.J. Chainer, M.D. Schultz, and M.P. David. Cooling Energy Reduction during dynamically controlled data center operation. in ASME 2013 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems. 2013. American Society of Mechanical Engineers. 100. Meyer, N., M. Ries, S. Solbrig, and T. Wettig. iDataCool: HPC with hot-water cooling and energy reuse. in International Supercomputing Conference. 2013. Springer. 101. Douchet, F., D. Nortershauser, S. Le Masson, and P. Glouannec, Experimental and numerical study of water-cooled datacom equipment. Applied Thermal Engineering, 2015. 84: p. 350-359. 102. Schmidt, R., R.C. Chu, M. Ellsworth, M. Iyengar, D. Porter, V. Kamath, and B. Lehman. Maintaining datacom rack inlet air temperatures with water cooled heat exchanger. in Asme 2005 pacific rim technical conference and exhibition on integration and packaging of mems, nems, and electronic systems collocated with the asme 2005 heat transfer summer conference. 2005. American Society of Mechanical Engineers. 103. Schmidt, R., M. Iyengar, D. Porter, G. Weber, D. Graybill, and J. Steffes. Open side car heat exchanger that removes entire server heat load without any added fan power. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2010 12th IEEE Intersociety Conference on. 2010. IEEE. 104. Gao, T., E. Samadiani, B. Sammakia, and R. Schmidt. Comparative thermal and energy analysis of a hybrid cooling data center with rear door heat exchangers. in ASME 2013 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems. 2013. American Society of Mechanical Engineers. 105. Wemhoff, A.P. and A. Ortega. An exergy-based analysis of the effects of rear door heat exchange systems on data center energy efficiency. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on. 2014. IEEE. 106. Mulay, V., D. Agonafer, and R. Schmidt. Liquid Cooling for Thermal Management of Data Centers. in ASME 2008 International Mechanical Engineering Congress and Exposition. 2008. American Society of Mechanical Engineers. 107. Ellsworth, M., L. Campbell, R. Simons, M. Iyengar, R. Schmidt, and R. Chu. The evolution of water cooling for IBM large server systems: Back to the future. in Thermal and Thermomechanical Phenomena in Electronic Systems, 2008. ITHERM 2008. 11th Intersociety Conference on. 2008. IEEE. 108. Schmidt, R. and M. Iyengar. Server rack rear door heat exchanger and the new ASHRAE recommended environmental guidelines. in ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability. 2009. American Society of Mechanical Engineers. 109. Almoli, A., A. Thompson, N. Kapur, J. Summers, H. Thompson, and G. Hannah, Computational fluid dynamic investigation of liquid rack cooling in data centres. Applied energy, 2012. 89(1): p. 150-155. 110. Gao, T., M. David, J. Geer, R. Schmidt, and B. Sammakia, Experimental and numerical dynamic investigation of an energy efficient liquid cooled chiller-less data center test facility. Energy and Buildings, 2015. 91: p. 83-96. 111. Sun Microsystems, I., Sun Fire V20z and Sun Fire V40z Servers. 2005. 112. Minyard, C., IPMI–A Gentle Introduction with OpenIPMI. 2004. 113. CoolIT. 2012; Available from: http://www.coolitsystems.com/. 114. Delta. FFB 40 X 40 X 25 mm series. 2017; Available from: http://www.deltaww.com/. 115. Al-Anii, Y.T.S., Holistic and Energy-Efficient Management of Datacentres. 2017, University of Leeds. 116. 3COM, SuperStack® 3 Switch 3870 Family Getting Started Guide, 3COM, Editor. 2004. 117. Airedale International Air Conditioning Limited. 2015; Available from: http://www.airedale.com/. 118. Wang, C.-C., J.-Y. Chang, and N.-F. Chiou, Effects of waffle height on the air-side performance of wavy fin-and-tube heat exchangers. Heat Transfer Engineering, 1999. 20(3): p. 45-56. 119. Wang, C.-C. and K.-Y. Chi, Heat transfer and friction characteristics of plain fin-and-tube heat exchangers, part I: new experimental data. International Journal of Heat and Mass Transfer, 2000. 43(15): p. 2681-2691. 120. Wongwises, S. and Y. Chokeman, Effect of fin pitch and number of tube rows on the air side performance of herringbone wavy fin and tube heat exchangers. Energy Conversion and Management, 2005. 46(13): p. 2216-2231. 121. Youn, B. and N. Kim, An experimental investigation on the airside performance of fin-and-tube heat exchangers having sinusoidal wave fins. Heat and Mass Transfer, 2007. 43(12): p. 1249-1262. 122. Wang, C.-C., J.-S. Liaw, and B.-C. Yang, Airside performance of herringbone wavy fin-and-tube heat exchangers–data with larger diameter tube. International Journal of Heat and Mass Transfer, 2011. 54(5): p. 1024-1029. 123. Pongsoi, P., S. Pikulkajorn, C.-C. Wang, and S. Wongwises, Effect of number of tube rows on the air-side performance of crimped spiral fin-and-tube heat exchanger with a multipass parallel and counter cross-flow configuration. International Journal of Heat and Mass Transfer, 2012. 55(4): p. 1403-1411. 124. Yu, R., A. Sommers, and N. Okamoto, Effect of a micro-grooved fin surface design on the air-side thermal-hydraulic performance of a plain fin-and-tube heat exchanger. International Journal of Refrigeration, 2013. 36(3): p. 1078-1089. 125. Ma, X., G. Ding, Y. Zhang, and K. Wang, Airside characteristics of heat, mass transfer and pressure drop for heat exchangers of tube-in hydrophilic coating wavy fin under dehumidifying conditions. International Journal of Heat and Mass Transfer, 2009. 52(19): p. 4358-4370. 126. Min, J., X. Wu, L. Shen, and F. Gao, Hydrophilic treatment and performance evaluation of copper finned tube evaporators. Applied Thermal Engineering, 2011. 31(14): p. 2936-2942. 127. Wang, C.-C. and C.-T. Chang, Heat and mass transfer for plate fin-and-tube heat exchangers, with and without hydrophilic coating. International Journal of Heat and Mass Transfer, 1998. 41(20): p. 3109-3120. 128. Kim, H.-Y. and B. Kang, Effects of hydrophilic surface treatment on evaporation heat transfer at the outside wall of horizontal tubes. Applied thermal engineering, 2003. 23(4): p. 449-458. 129. Hwang, Y., S. Popli, and R. Radermacher, Enhancement of Round Tube and Flat Tube-Louver Fin Heat Exchanger Performance Using Deluge Water Cooling, in International Refrigeration and Air Conditioning Conference 2012: Purdue University. 130. Bogan, N. and C. Park, Effects of Tube Row on Heat Transfer and Surface Wetting of Microscale Porous-Layer Coated, Horizontal-Tube, Falling-Film Evaporator. Journal of Heat Transfer (ASME), 2013. 131. Popli, S., Y. Hwang, and R. Radermacher. Performance Enhancement of Enhanced Herringbone Wavy-Fin Round Tube Inclined Heat Exchangers With and Without Hydrophilic Coating Using Evaporative Spray and Deluge Cooling. in ASME 2013 International Mechanical Engineering Congress and Exposition. 2013. American Society of Mechanical Engineers. 132. Wang, C., P. Chen, and J. Jang, Heat transfer and friction characteristics of convex-louver fin-and-tube heat exchangers. Experimental heat transfer, 1996. 9(1): p. 61-78. 133. Wang, C., W. Fu, and C. Chang, Heat transfer and friction characteristics of typical wavy fin-and-tube heat exchangers. Experimental thermal and fluid science, 1997. 14(2): p. 174-186. 134. Wang, C.-C., W.-S. Lee, W.-J. Sheu, and Y.-J. Chang, A comparison of the airside performance of the fin-and-tube heat exchangers in wet conditions; with and without hydrophilic coating. Applied Thermal Engineering, 2002. 22(3): p. 267-278. 135. Liu, L., Effects of air-side surface wettability on the performance of dehumidifying heat exchangers. 2011, University of Illinois at Urbana-Champaign. 136. KG, e.-p.M.G.C.; Available from: www.ebmpapst.com. 137. ebmpapst, EC axial fan - HyBlade. 2015. 138. CAREL. optiMist evaporative cooling 2013; Available from: http://www.carel.com/. 139. GRUNDFOS. CME 1-2 A-R-I-E-AQQE. Available from: http://www.grundfos.com/. 140. Books, H., Legionnaires’ disease: Technical guidance. 141. Clifton, J.R., W.J. Rossiter, and P.W. Brown, Degraded aqueous glycol solutions: pH values and the effects of common ions on suppressing pH decreases. Solar energy materials, 1985. 12(1): p. 77-86. 142. Rossiter, W.J., M. Godette, P.W. Brown, and K.G. Galuk, An investigation of the degradation of aqueous ethylene glycol and propylene glycol solutions using ion chromatography. Solar Energy Materials, 1985. 11(5-6): p. 455-467. 143. Note, T.A., Traversing a Duct to Determine Average Air Velocity. TI-106, 2014. 144. SPEC2008. Standard Performance Evaluation Corporation. 2017; Available from: https://www.spec.org/sfs2008/. 145. SPEC, S., Power and Performance, Benchmark Methodology V2. 1. 2011. 146. Voltech, PM1000+ POWER ANALYZER USER MANUAL. 2011. 147. Rossman, L.A., EPANET 2: users manual. 2000. 148. Cengel, Y.A. and J.M. Cimbala, Fluid Mechanics. Vol. 1. 2006, Tata McGraw-Hill Education, New York. 149. Xylem Inc. Electronically commutated spherical motor with permanent magnet rotor/impeller. Available from: www.xyleminc.com/brands/laingthermotech. 150. Gorti, N.P.K., Application aware performance, power consumption, and reliability tradeoff. 2014, Iowa State University. 151. Cader, T., V. Sorel, L. Westra, and A. Marquez, Liquid Cooling in Data Centers. ASHRAE Transactions, 2009. 115(1). 152. Dhavaleswarapu, H.K., C.P. Migliaccio, S.V. Garimella, and J.Y. Murthy, Experimental investigation of evaporation from low-contact-angle sessile droplets. Langmuir, 2009. 26(2): p. 880-888. 153. Kumari, N. and S.V. Garimella, Characterization of the heat transfer accompanying electrowetting or gravity-induced droplet motion. International Journal of Heat and Mass Transfer, 2011. 54(17): p. 4037-4050. 154. Nguyen, T.A., A.V. Nguyen, M.A. Hampton, Z.P. Xu, L. Huang, and V. Rudolph, Theoretical and experimental analysis of droplet evaporation on solid surfaces. Chemical Engineering Science, 2012. 69(1): p. 522-529. 155. Onan, C., D.B. Ozkan, and S. Erdem, CFD and Experimental Analysis of a Falling Film outside Smooth and Helically Grooved Tubes. Advances in Mechanical Engineering, 2014. 2014. 156. Wang, X. and A.M. Jacobi, A Thermodynamic Basis for Predicting Falling-Film Mode Transitions. International Journal of Refrigeration, 2014. 157. Paterson, C., Thin fluid films subject to external airflows. 2013, University of Strathclyde. 158. Wang, X., P. Hrnjak, S. Elbel, A. Jacobi, and M. He, Heat transfer performance for a falling-film on horizontal flat tubes. Journal of Heat Transfer, 2013. 135(7): p. 072901. 159. Jani, S. and M. Amini, Heat Transfer Analysis of Falling Film Evaporation on a Horizontal Elliptical Tube. Journal of Heat Transfer, 2012. 134(6): p. 064505. 160. David, S., K. Sefiane, and L. Tadrist, Experimental investigation of the effect of thermal properties of the substrate in the wetting and evaporation of sessile drops. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2007. 298(1): p. 108-114. 161. Mollaret, R., K. Sefiane, J. Christy, and D. Veyret, Experimental and numerical investigation of the evaporation into air of a drop on a heated surface. Chemical Engineering Research and Design, 2004. 82(4): p. 471-480. 162. Sobac, B. and D. Brutin, Thermal effects of the substrate on water droplet evaporation. Physical Review E, 2012. 86(2): p. 021602. 163. Shin, D.H., S.H. Lee, J.-Y. Jung, and J.Y. Yoo, Evaporating characteristics of sessile droplet on hydrophobic and hydrophilic surfaces. Microelectronic Engineering, 2009. 86(4): p. 1350-1353. 164. Gelderblom, H., A.G. Marin, H. Nair, A. van Houselt, L. Lefferts, J.H. Snoeijer, and D. Lohse, How water droplets evaporate on a superhydrophobic substrate. Physical Review E, 2011. 83(2): p. 026306. 165. Yu, Y.-S., Z. Wang, and Y.-P. Zhao, Experimental and theoretical investigations of evaporation of sessile water droplet on hydrophobic surfaces. Journal of Colloid and Interface Science, 2012. 365(1): p. 254-259. 166. Dash, S. and S.V. Garimella, Droplet evaporation on heated hydrophobic and superhydrophobic surfaces. Physical Review E, 2014. 89(4): p. 042402. 167. Sefiane, K., L. Tadrist, and M. Douglas, Experimental study of evaporating water–ethanol mixture sessile drop: Influence of concentration. International Journal of Heat and Mass Transfer, 2003. 46(23): p. 4527-4534. 168. Sefiane, K. and L. Tadrist, Experimental investigation of the de-pinning phenomenon on rough surfaces of volatile drops. International Communications in Heat and Mass Transfer, 2006. 33(4): p. 482-490. 169. Lee, K., C. Cheah, R. Copleston, V. Starov, and K. Sefiane, Spreading and evaporation of sessile droplets: Universal behaviour in the case of complete wetting. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2008. 323(1): p. 63-72. 170. Dunn, G., S. Wilson, B. Duffy, S. David, and K. Sefiane, The strong influence of substrate conductivity on droplet evaporation. Journal of Fluid Mechanics, 2009. 623: p. 329-351. 171. Stauber, J., S. Wilson, B. Duffy, and K. Sefiane, On the lifetimes of evaporating droplets. Journal of Fluid Mechanics, 2014. 744: p. R2. 172. Deegan, R.D., O. Bakajin, T.F. Dupont, G. Huber, S.R. Nagel, and T.A. Witten, Contact line deposits in an evaporating drop. Physical Review E, 2000. 62(1): p. 756. 173. Popov, Y.O., Evaporative deposition patterns: spatial dimensions of the deposit. Physical Review E, 2005. 71(3): p. 036313. 174. Dash, S. and S.V. Garimella, Droplet evaporation dynamics on a superhydrophobic surface with negligible hysteresis. Langmuir, 2013. 29(34): p. 10785-10795. 175. Gleason, K. and S.A. Putnam, Microdroplet evaporation with a forced pinned contact line. Langmuir, 2014. 30(34): p. 10548-10555. 176. Pan, Z., S. Dash, J.A. Weibel, and S.V. Garimella, Assessment of water droplet evaporation mechanisms on hydrophobic and superhydrophobic substrates. Langmuir, 2013. 29(51): p. 15831-15841. 177. Carle, F., B. Sobac, and D. Brutin, Experimental evidence of the atmospheric convective transport contribution to sessile droplet evaporation. Applied Physics Letters, 2013. 102(6): p. 061603. 178. Chen, Y., W. Hu, J. Wang, F. Hong, and P. Cheng, Transient effects and mass convection in sessile droplet evaporation: The role of liquid and substrate thermophysical properties. International Journal of Heat and Mass Transfer, 2017. 108: p. 2072-2087. 179. Park, J.K., J. Ryu, B.C. Koo, S. Lee, and K.H. Kang, How the change of contact angle occurs for an evaporating droplet: effect of impurity and attached water films. Soft Matter, 2012. 8(47): p. 11889-11896. 180. Nguyen, T.A. and A.V. Nguyen, Increased evaporation kinetics of sessile droplets by using nanoparticles. Langmuir, 2012. 28(49): p. 16725-16728. 181. Pittoni, P.G., C.-C. Chang, T.-S. Yu, and S.-Y. Lin, Evaporation of water drops on polymer surfaces: pinning, depinning and dynamics of the triple line. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2013. 432: p. 89-98. 182. Putnam, S.A., A.M. Briones, L.W. Byrd, J.S. Ervin, M.S. Hanchak, A. White, and J.G. Jones, Microdroplet evaporation on superheated surfaces. International Journal of Heat and Mass Transfer, 2012. 55(21-22): p. 5793-5807. 183. Bormashenko, E., A. Musin, and M. Zinigrad, Evaporation of droplets on strongly and weakly pinning surfaces and dynamics of the triple line. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2011. 385(1-3): p. 235-240. 184. Blake, T. and J. De Coninck, The influence of solid–liquid interactions on dynamic wetting. Advances in colloid and interface science, 2002. 96(1-3): p. 21-36. 185. Anantharaju, N., M. Panchagnula, and S. Neti, Evaporating drops on patterned surfaces: Transition from pinned to moving triple line. Journal of colloid and interface science, 2009. 337(1): p. 176-182. 186. Kulinich, S. and M. Farzaneh, Effect of contact angle hysteresis on water droplet evaporation from super-hydrophobic surfaces. Applied Surface Science, 2009. 255(7): p. 4056-4060. 187. Stauber, J.M., S.K. Wilson, B.R. Duffy, and K. Sefiane, On the lifetimes of evaporating droplets with related initial and receding contact angles. Physics of Fluids, 2015. 27(12): p. 122101. 188. Hu, D. and H. Wu, Volume evolution of small sessile droplets evaporating in stick-slip mode. Physical Review E, 2016. 93(4): p. 042805. 189. Sefiane, K. and R. Bennacer, Nanofluids droplets evaporation kinetics and wetting dynamics on rough heated substrates. Advances in Colloid and Interface Science, 2009. 147: p. 263-271. 190. Bazargan, V., Effect of substrate cooling and droplet shape and composition on the droplet evaporation and the deposition of particles, in 2014, The University Of British Columbia. p. 120. 191. Srinivasan, S., G.H. McKinley, and R.E. Cohen, Assessing the accuracy of contact angle measurements for sessile drops on liquid-repellent surfaces. Langmuir, 2011. 27(22): p. 13582-13589. 192. Lopes, M.C., E. Bonaccurso, T. Gambaryan-Roisman, and P. Stephan, Influence of the substrate thermal properties on sessile droplet evaporation: Effect of transient heat transport. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2013. 432: p. 64-70. 193. Berthier, J., Micro-drops and digital microfluidics. 2012: William Andrew. 194. Oxford nanoSystems. Available from: http://oxfordnanosystems.com/. 195. FTA4000. Available from: http://www.firsttenangstroms.com. 196. Lebedev, N.N., Special functions and their applications, ed. R.A. Silverman. 1965, United States of America: Prentice-Hall, Inc. 322. 197. MATLAB, Reference manual. The Mathworks Inc. Natick, Massachusetts, United States, 2013. 198. Incropera, F.P., Fundamentals of heat and mass transfer. 2011: John Wiley & Sons. 199. Cengel, Y.A. and M.A. Boles, Thermodynamics: an engineering approach. Sea, 2002. 1000: p. 8862. 200. Marrero, T.R. and E.A. Mason, Gaseous diffusion coefficients. Journal of Physical and Chemical Reference Data, 1972. 1(1): p. 3-118. 201. Faghri, A. and Y. Zhang, Transport phenomena in multiphase systems. 2006: Academic Press. 202. Girard, F., M. Antoni, S. Faure, and A. Steinchen, Influence of heating temperature and relative humidity in the evaporation of pinned droplets. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2008. 323(1): p. 36-49. Appendix A -"]},{"key":"dc:type","label":"Dc Type","values":["Thesis"]},{"key":"dc:type.qualificationlevel","label":"Dc Type Qualificationlevel","values":["doctoral"]},{"key":"dc:type.qualificationname","label":"Dc Type Qualificationname","values":["Ph.D"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.dcterms_iso639_2","label":"Language (ISO 639-2)","values":["eng"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier","label":"Identifier","values":["uk.bl.ethos.749438"]},{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://etheses.whiterose.ac.uk/id/eprint/21185/1/Holistic%20study%20of%20thermal%20management%20in%20direct%20liquid%20cooled%20data%20centres%20from%20chip%20to%20the%20environment.pdf"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["The IT (Information Technology) infrastructure power consumption constitutes a large portion of global electricity consumption and a large proportion of this energy is to maintain an acceptable thermal environment for the IT equipment. Therefore, it is important to understand and improve the thermal and energy management of data centres for lower cost and higher sustainability. Toward this goal, Direct Contact Liquid Cooled (DCLC) servers, where liquid loop heat exchangers are attached to the CPU, were proposed to study the use of chiller-less energy efficient data centre. Thirty Sun Fire V20z servers in a data centre rack have their CPUs water cooled with the remaining components air cooled, together with a rear door heat exchanger to capture this air heat flow. The heat generated by the servers is ultimately transferred to the environment using an Air Handling Unit (AHU). The AHU was fitted with a water spray system to increase the heat transfer capacity. The designed DCLC system was tested and characterised in terms of power consumption and thermal performance. The design successfully provided stable inlet coolant temperature (±1℃) to the IT despite the variation in the IT workload and environmental conditions. Activating the spray reduced the thermal resistance of the AHU heat exchanger (HE) by 50%. However, the power consumption and pressure drop across the HE was increased. The flow distribution and the coolant pumping configurations of centralised (where the coolant is pumped by two central pumps connected in series) and distributed (where small pumps inside the servers are activated) was investigated. The EPANET software was used to analyse the flow and showed that the servers in the top of the rack receive a higher flow rate (by approximately 30%) than the servers in the bottom of the rack. This resulted in a variation in the CPU temperatures of different servers. Optimisation analysis proposed increasing the manifolds size to improve the flow rate and reduce the flow maldistribution. In the distributed pumping case, the CPUs temperature showed to be 2℃ higher compared with the central pumping case for the high IT workload. The rack inlet temperature was tested in the range of the ASHRAE W4 envelope in terms of CPU temperatures, power consumption and computational efficiency. Increasing the coolant inlet temperature resulted in high energy saving in the AHU, while the rack energy consumption increases marginally in idle operation and considerably more in high IT workloads. This results in an improvement in the energy effectiveness of 17% but a deterioration in the computational efficiency of 4%. Finally, a parallel study was carried out to investigate the droplet evaporation over heated surfaces which ultimately be used in studying sprays in the AHU or in direct on chip cooling via evaporation. A novel experimental design was proposed to track the lifetime of any droplet size that span the surface tension to gravitydominated regimes. A theoretical model was also proposed to predict the droplet lifetime based on the initial contact angle, contact radius and the receding contact angle. The model predicted the droplet evaporation over hydrophobic surfaces with good accuracy of an error less than 4% while under estimated the evaporation with hydrophilic surfaces."]},{"key":"dc:format","label":"Dc Format","values":["text"]},{"key":"dcterms:accessrights","label":"Dcterms Accessrights","values":["public"]},{"key":"dc:title","label":"Title","values":["Holistic Study of Thermal Management in Direct Liquid Cooled Data Centres: from the Chip to the Environment"]}]}],"canonical_facts":{"dc:contributor.advisor":["Kapur, Nikil","Summers, Jonathan","Thompson, Harvey"],"dc:contributor.sponsor":["The Iraqi Ministry of Higher Education and Scientific Research","Airedale International Air Conditioning Ltd"],"dc:creator":["Kadhim, Mustafa Alaa Kadhim"],"dc:date":["2018-04"],"dc:date.issued":["2018-04"],"dc:description.abstract":["The IT (Information Technology) infrastructure power consumption constitutes a large portion of global electricity consumption and a large proportion of this energy is to maintain an acceptable thermal environment for the IT equipment. Therefore, it is important to understand and improve the thermal and energy management of data centres for lower cost and higher sustainability. Toward this goal, Direct Contact Liquid Cooled (DCLC) servers, where liquid loop heat exchangers are attached to the CPU, were proposed to study the use of chiller-less energy efficient data centre. Thirty Sun Fire V20z servers in a data centre rack have their CPUs water cooled with the remaining components air cooled, together with a rear door heat exchanger to capture this air heat flow. The heat generated by the servers is ultimately transferred to the environment using an Air Handling Unit (AHU). The AHU was fitted with a water spray system to increase the heat transfer capacity. The designed DCLC system was tested and characterised in terms of power consumption and thermal performance. The design successfully provided stable inlet coolant temperature (±1℃) to the IT despite the variation in the IT workload and environmental conditions. Activating the spray reduced the thermal resistance of the AHU heat exchanger (HE) by 50%. However, the power consumption and pressure drop across the HE was increased. The flow distribution and the coolant pumping configurations of centralised (where the coolant is pumped by two central pumps connected in series) and distributed (where small pumps inside the servers are activated) was investigated. The EPANET software was used to analyse the flow and showed that the servers in the top of the rack receive a higher flow rate (by approximately 30%) than the servers in the bottom of the rack. This resulted in a variation in the CPU temperatures of different servers. Optimisation analysis proposed increasing the manifolds size to improve the flow rate and reduce the flow maldistribution. In the distributed pumping case, the CPUs temperature showed to be 2℃ higher compared with the central pumping case for the high IT workload. The rack inlet temperature was tested in the range of the ASHRAE W4 envelope in terms of CPU temperatures, power consumption and computational efficiency. Increasing the coolant inlet temperature resulted in high energy saving in the AHU, while the rack energy consumption increases marginally in idle operation and considerably more in high IT workloads. This results in an improvement in the energy effectiveness of 17% but a deterioration in the computational efficiency of 4%. Finally, a parallel study was carried out to investigate the droplet evaporation over heated surfaces which ultimately be used in studying sprays in the AHU or in direct on chip cooling via evaporation. A novel experimental design was proposed to track the lifetime of any droplet size that span the surface tension to gravitydominated regimes. A theoretical model was also proposed to predict the droplet lifetime based on the initial contact angle, contact radius and the receding contact angle. The model predicted the droplet evaporation over hydrophobic surfaces with good accuracy of an error less than 4% while under estimated the evaporation with hydrophilic surfaces."],"dc:format":["text"],"dc:identifier":["uk.bl.ethos.749438"],"dc:identifier.uri":["https://etheses.whiterose.ac.uk/id/eprint/21185/1/Holistic%20study%20of%20thermal%20management%20in%20direct%20liquid%20cooled%20data%20centres%20from%20chip%20to%20the%20environment.pdf"],"dc:language.dcterms_iso639_2":["eng"],"dc:publisher.commercial":["University of Leeds"],"dc:publisher.department":["Faculty of Engineering (Leeds)","School of Mechanical Engineering (Leeds)","Institute of Engineering Thermofluids, Surfaces & Interfaces (iETSI) (Leeds)"],"dc:publisher.institution":["University of Leeds"],"dc:relation.isreferencedby":["https://etheses.whiterose.ac.uk/id/eprint/21185/"],"dc:relation.references":["1. Joshi, Y. and P. Kumar, Energy efficient thermal management of data centers. 2012: Springer Science & Business Media. 2. Khalaj, A.H. and S.K. Halgamuge, A Review on efficient thermal management of air-and liquid-cooled data centers: From chip to the cooling system. Applied Energy, 2017. 205: p. 1165-1188. 3. Patankar, S.V., Airflow and cooling in a data center. Journal of Heat Transfer, 2010. 132(7): p. 073001. 4. Rahmat Romadhon, Maisarah Ali, Ayub Mohd Mahdzir, and Y.A. Abakr, Optimization of Cooling Systems in Data Centre by Computational Fluid Dynamics Model and Simulation, in Conference on Innovative Technologies in Intelligent Systems and Industrial Applications (CITISIA 2009). 2009: Monash University, Sunway campus, Malaysia,. p. 322-327. 5. Mitchell-Jackson, J., J.G. Koomey, B. Nordman, and M. Blazek, Data center power requirements: measurements from Silicon Valley. Energy, 2003. 28(8): p. 837-850. 6. Schultz, M., M. Gaynes, P. Parida, and T. Chainer. Experimental investigation of direct attach microprocessors in a liquid-cooled chiller-less data center. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on. 2014. IEEE. 7. Brown, R.E., R. Brown, E. Masanet, B. Nordman, B. Tschudi, A. Shehabi, J. Stanley, J. Koomey, D. Sartor, and P. Chan, Report to congress on server and data center energy efficiency: Public law 109-431. 2007, Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US). 8. Koomey, J., Growth in data center electricity use 2005 to 2010. A report by Analytical Press, completed at the request of The New York Times, 2011. 9. Ebrahimi, K., G.F. Jones, and A.S. Fleischer, A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities. Renewable and Sustainable Energy Reviews, 2014. 31: p. 622-638. 10. Koomey, J.G., Worldwide electricity used in data centers. Environmental research letters, 2008. 3(3): p. 034008. 11. Garimella, S.V., T. Persoons, J. Weibel, and L.-T. Yeh, Technological drivers in data centers and telecom systems: Multiscale thermal, electrical, and energy management. Applied energy, 2013. 107: p. 66-80. 12. VanGeet, O., Best practices guide for energy-efficient data center design. 2010, EERE Publication and Product Library. 13. Alkharabsheh, S., J. Fernandes, B. Gebrehiwot, D. Agonafer, K. Ghose, A. Ortega, Y. Joshi, and B. Sammakia, A Brief Overview of Recent Developments in Thermal Management in Data Centers. Journal of Electronic Packaging, 2015. 137(4): p. 040801. 14. Rambo, J.D., Reduced-order modeling of multiscale turbulent convection: application to data center thermal management. 2006, Georgia Institute of Technology. 15. ASHRAE, T., Datacom equipment power trends and cooling applications. 2012, American Society of Heating, Refrigeration and Air-Conditioning Engineers Atlanta, GA. 16. Kheirabadi, A.C. and D. Groulx, Cooling of server electronics: A design review of existing technology. Applied Thermal Engineering, 2016. 17. Chu, R.C., R.E. Simons, M.J. Ellsworth, R.R. Schmidt, and V. Cozzolino, Review of cooling technologies for computer products. IEEE Transactions on Device and materials Reliability, 2004. 4(4): p. 568-585. 18. Ohadi, M., S. Dessiatoun, K. Choo, M. Pecht, and J.V. Lawler. A comparison analysis of air, liquid, and two-phase cooling of data centers. in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE. 2012. IEEE. 19. Steinbrecher, R.A., Data Center Environments ASHRAE's Evolving Thermal Guidelines. ASHRAE Journal, 2011. 53(12): p. 42. 20. ASHRAE, Thermal Guidelines for Data Processing Environments, ed. T. Edition. 2012. 152. 21. Jamalzadeh, M. and N. Behravan, An exhaustive framework for better data centers’ energy efficiency and greenness by using metrics. Indian Journal of Computer Science and Engineering, 2012. 2(6): p. 813-822. 22. Mathew, P., Self-benchmarking guide for data centers: Metrics, benchmarks, actions. Lawrence Berkeley National Laboratory, 2010. 23. Sharma, R.K., C.E. Bash, and C.D. Patel. Dimensionless parameters for evaluation of thermal design and performance of large-scale data centers. in 8th ASME/AIAA Joint Thermophysics and Heat Transfer Conference. 2002. 24. Herrlin, M.K., Rack cooling effectiveness in data centers and telecom central offices: The rack cooling index (RCI). Transactions-American Society of Heating Refrigerating and Air conditioning Engineers, 2005. 111(2): p. 725. 25. Herrlin, M.K. Improved data center energy efficiency and thermal performance by advanced airflow analysis. in Digital Power Forum. 2007. 26. Vangilder, J.W. and S.K. Shrivastava, Capture Index: An Airflow-Based Rack Cooling Performance Metric. ASHRAE transactions, 2007. 113(1). 27. Lettieri, D.J., C.R. Hannemann, V.P. Carey, and A.J. Shah. Lifetime exergy consumption as a sustainability metric for information technologies. in Sustainable Systems and Technology, 2009. ISSST'09. IEEE International Symposium on. 2009. IEEE. 28. Brady, G.A., Energy Efficiency in Data Centres and the Barriers to Further Improvements: An Interdisciplinary Investigation. 2016, University of Leeds. 29. Malone, C. and C. Belady. Metrics to characterize data center & IT equipment energy use. in Proceedings of the Digital Power Forum, Richardson, TX. 2006. 30. Consortium, G.G.I., Green Grid Metrics Describing Data Center Power Efficiency. Technical Committee White Paper, available at http://www. thegreengrid. org/~/media/WhitePapers/Green_Grid_Metrics_WP. pdf, 2007. 31. Stansberry, M., uptime institute annual data center industry survey report and full results.”. 2013. 32. Brady, G.A., N. Kapur, J.L. Summers, and H.M. Thompson, A case study and critical assessment in calculating power usage effectiveness for a data centre. Energy Conversion and Management, 2013. 76: p. 155-161. 33. Horner, N. and I. Azevedo, Power usage effectiveness in data centers: overloaded and underachieving. The Electricity Journal, 2016. 29(4): p. 61-69. 34. BS EN 50600-4-2:2016: Information technology. Data centre facilities and infrastructures. Power Usage Effectiveness. 2017, British Standards Institute. 35. Sun, H. and S. Lee, Case study of data centers’ energy performance. Energy and Buildings, 2006. 38(5): p. 522-533. 36. Tschudi, B., O. Vangeet, J. Cooley, and D. Azevedo, ERE: A metric for measuring the benefit of reuse energy from a data center. White Paper, 2010. 29. 37. Shah, A.J., C.E. Bash, N. Kumari, T. Cader, T.J. Breen, E.J. Walsh, and J. Punch. On the need for energy efficiency metrics that span integrated IT-facility infrastructures. in ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems. 2011. American Society of Mechanical Engineers. 38. Patterson, M.K., S.W. Poole, C.-H. Hsu, D. Maxwell, W. Tschudi, H. Coles, D.J. Martinez, and N. Bates. TUE, a new energy-efficiency metric applied at ORNL’s Jaguar. in International Supercomputing Conference. 2013. Springer. 39. Green500. Available from: https://www.Green500.org/. 40. Minartz, T., J.M. Kunkel, and T. Ludwig, Simulation of power consumption of energy efficient cluster hardware. Computer Science-Research and Development, 2010. 25(3-4): p. 165-175. 41. Newcombe, L., Z. Limbuwala, P. Latham, and V. Smith, Data centre fixed to variable energy ratio metric (dc-fver). British Computer Society, 2012. 42. Subramaniam, B. and W.-c. Feng. The Green Index: A metric for evaluating system-wide energy efficiency in HPC systems. in Parallel and Distributed Processing Symposium Workshops & PhD Forum (IPDPSW), 2012 IEEE 26th International. 2012. IEEE. 43. Beitelmal, A. and D. Fabris, Servers and data centers energy performance metrics. Energy and Buildings, 2014. 80: p. 562-569. 44. Wilde, T., A. Auweter, M.K. Patterson, H. Shoukourian, H. Huber, A. Bode, D. Labrenz, and C. Cavazzoni. DWPE, a new data center energy-efficiency metric bridging the gap between infrastructure and workload. in High Performance Computing & Simulation (HPCS), 2014 International Conference on. 2014. IEEE. 45. Sharma, R., A. Shah, C. Bash, T. Christian, and C. Patel. Water efficiency management in datacenters: Metrics and methodology. in Sustainable Systems and Technology, 2009. ISSST'09. IEEE International Symposium on. 2009. IEEE. 46. Azevedo, D., M. Patterson, J. Pouchet, and R. Tipley, Carbon usage effectiveness (CUE): a green grid data center sustainability metric. White Paper, 2010. 32. 47. Li, Z. and S.G. Kandlikar, Current status and future trends in data-center cooling technologies. Heat Transfer Engineering, 2015. 36(6): p. 523-538. 48. Geng, H., Data center handbook. 2014: John Wiley & Sons. 49. Chiriac, V.A. and F. Chiriac. Novel energy recovery systems for the efficient cooling of data centers using absorption chillers and renewable energy resources. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 50. Fakhim, B., M. Behnia, S. Armfield, and N. Srinarayana, Cooling solutions in an operational data centre: A case study. Applied thermal engineering, 2011. 31(14): p. 2279-2291. 51. Oró, E., V. Depoorter, A. Garcia, and J. Salom, Energy efficiency and renewable energy integration in data centres. Strategies and modelling review. Renewable and Sustainable Energy Reviews, 2015. 42: p. 429-445. 52. Committee, A.T., Thermal guidelines for data processing environments-expanded data center classes and usage guidance. Atlanta, 2011. 53. Xu, G., B. Guenin, and M. Vogel. Extension of air cooling for high power processors. in Thermal and Thermomechanical Phenomena in Electronic Systems, 2004. ITHERM'04. The Ninth Intersociety Conference on. 2004. IEEE. 54. Katoh, T., G. Xu, M. Vogel, and S. Novotny. New attempt of forced-air cooling for high heat-flux applications. in Thermal and Thermomechanical Phenomena in Electronic Systems, 2004. ITHERM'04. The Ninth Intersociety Conference on. 2004. IEEE. 55. Zhang, H., S. Shao, H. Xu, H. Zou, and C. Tian, Free cooling of data centers: A review. Renewable and Sustainable Energy Reviews, 2014. 35: p. 171-182. 56. Patankar, S.V. and K.C. Karki, Distribution of Cooling Airflow in a Raised-Floor Data Center. ASHRAE Transactions, 2004. 110(2). 57. Muralidharan, B., M. Ibrahim, S. Shrivistava, S. Alkharabsheh, and B. Sammakia, Impact of cold aisle containment on thermal performance of data center. ASME Paper No. IPACK2013-73201, 2013. 58. Garimella, S.V., L.-T. Yeh, and T. Persoons, Thermal management challenges in telecommunication systems and data centers. IEEE Transactions on Components, Packaging and Manufacturing Technology, 2012. 2(8): p. 1307-1316. 59. Srinarayana, N., B. Fakhim, M. Behnia, and S.W. Armfield, Thermal performance of an air-cooled data center with raised-floor and non-raised-floor configurations. Heat Transfer Engineering, 2014. 35(4): p. 384-397. 60. Walsh, E.J., T.J. Breen, J. Punch, A.J. Shah, and C.E. Bash. From chip to cooling tower data center modeling: Part II influence of chip temperature control philosophy. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2010 12th IEEE Intersociety Conference on. 2010. IEEE. 61. Tuma, P.E. The merits of open bath immersion cooling of datacom equipment. in Semiconductor Thermal Measurement and Management Symposium, 2010. SEMI-THERM 2010. 26th Annual IEEE. 2010. IEEE. 62. Tuma, P.E. Design considerations relating to non-thermal aspects of passive 2-phase immersion cooling. in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2011 27th Annual IEEE. 2011. IEEE. 63. El-Genk, M.S., Immersion cooling nucleate boiling of high power computer chips. Energy conversion and management, 2012. 53(1): p. 205-218. 64. Asadi, M., G. Xie, and B. Sunden, A review of heat transfer and pressure drop characteristics of single and two-phase microchannels. International Journal of Heat and Mass Transfer, 2014. 79: p. 34-53. 65. Kadam, S.T. and R. Kumar, Twenty first century cooling solution: Microchannel heat sinks. International Journal of Thermal Sciences, 2014. 85: p. 73-92. 66. Al-Neama, A.F., N. Kapur, J. Summers, and H.M. Thompson, An experimental and numerical investigation of the use of liquid flow in serpentine microchannels for microelectronics cooling. Applied Thermal Engineering, 2017. 116: p. 709-723. 67. Ellsworth, M.J., G.F. Goth, R.J. Zoodsma, A. Arvelo, L.A. Campbell, and W.J. Anderl, An overview of the IBM power 775 supercomputer water cooling system. Journal of Electronic Packaging, 2012. 134(2): p. 020906. 68. Burd, T.D. and R.W. Brodersen, Processor design for portable systems, in Technologies for wireless computing. 1996, Springer. p. 119-137. 69. Sarood, O., A. Gupta, and L.V. Kale. Temperature aware load balancing for parallel applications: Preliminary work. in Parallel and distributed processing workshops and phd forum (IPDPSW), 2011 IEEE international symposium on. 2011. IEEE. 70. Menon, H., B. Acun, S.G. De Gonzalo, O. Sarood, and L. Kalé. Thermal aware automated load balancing for hpc applications. in Cluster Computing (CLUSTER), 2013 IEEE International Conference on. 2013. IEEE. 71. Ge, R., X. Feng, and K.W. Cameron. Performance-constrained distributed dvs scheduling for scientific applications on power-aware clusters. in Supercomputing, 2005. Proceedings of the ACM/IEEE SC 2005 Conference. 2005. IEEE. 72. Meijer, G.I., Cooling energy-hungry data centers. Science, 2010. 328(5976): p. 318-319. 73. Kandlikar, S.G. and C.N. Hayner, Liquid cooled cold plates for industrial high-power electronic devices—Thermal design and manufacturing considerations. Heat Transfer Engineering, 2009. 30(12): p. 918-930. 74. Ouchi, M., Y. Abe, M. Fukagaya, H. Ohta, Y. Shinmoto, M. Sato, and K.-i. Iimura. Thermal management systems for data centers with liquid cooling technique of CPU. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 75. Goth, G.F., A. Arvelo, J. Eagle, M.J. Ellsworth, K.C. Marston, A.K. Sinha, and J.A. Zitz. Thermal and mechanical analysis and design of the IBM Power 775 water cooled supercomputing central electronics complex. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 76. Kheirabadi, A.C. and D. Groulx, Experimental Evaluation of a Thermal Contact Water Cooling System for Server Electronics 2017. 77. Ramakrishnan, B., S. Alkharabsheh, Y. Hadad, B. Sammakia, P.R. Chiarot, M. Seymour, and R. Tipton. Experimental characterization of a cold plate used in warm water cooling of data centers. in 2017 33rd Thermal Measurement, Modeling & Management Symposium (SEMI-THERM). 2017. 78. Inc, C.S., Operation and Maintenance Manual 2015. 79. Sahini, M., U. Chowdhury, A. Siddarth, T. Pradip, D. Agonafer, R. Zeigham, J. Metcalf, and S. Branton. Comparative study of high ambient inlet temperature effects on the performance of air vs. liquid cooled IT equipment. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2017 16th IEEE Intersociety Conference on. 2017. IEEE. 80. Zimmermann, S., I. Meijer, M.K. Tiwari, S. Paredes, B. Michel, and D. Poulikakos, Aquasar: A hot water cooled data center with direct energy reuse. Energy, 2012. 43(1): p. 237-245. 81. Zimmermann, S., M.K. Tiwari, I. Meijer, S. Paredes, B. Michel, and D. Poulikakos, Hot water cooled electronics: exergy analysis and waste heat reuse feasibility. International Journal of Heat and Mass Transfer, 2012. 55(23): p. 6391-6399. 82. Addagatla, A., J. Fernandes, D. Mani, D. Agonafer, and V. Mulay. Effect of warm water cooling for an isolated hybrid liquid cooled server. in Thermal Measurement, Modeling & Management Symposium (SEMI-THERM), 2015 31st. 2015. IEEE. 83. Druzhinin, E., A. Shmelev, A. Moskovsky, Y. Migal, V. Mironov, and A. Semin. High temperature coolant demonstrated for a computational cluster. in High Performance Computing & Simulation (HPCS), 2016 International Conference on. 2016. IEEE. 84. Druzhinin, E.A., A.B. Shmelev, A.A. Moskovsky, V.V. Mironov, and A. Semin, Server Level Liquid Cooling: Do Higher System Temperatures Improve Energy Efﬁciency? Supercomputing frontiers and innovations, 2016. 3(1): p. 67-74. 85. Garraghan, P., Y. Al-Anii, J. Summers, H. Thompson, N. Kapur, and K. Djemame. A unified model for holistic power usage in cloud datacenter servers. in Proceedings of the 9th International Conference on Utility and Cloud Computing. 2016. ACM. 86. Zeighami, R., W.A. Saunders, H. Coles, and S. Branton. Thermal performance modeling of hybrid liquid-air cooled servers. in Thermal and thermomechanical phenomena in electronic systems (itherm), 2014 ieee intersociety conference on. 2014. IEEE. 87. Li, L., W. Zheng, X. Wang, and X. Wang. Placement optimization of liquid-cooled servers for power minimization in data centers. in Green Computing Conference (IGCC), 2014 International. 2014. IEEE. 88. Ovaska, S.J., R.E. Dragseth, and S.A. Hanssen. Impact of retrofitted CPU water cooling on supercomputer performance and power consumption. in SoutheastCon, 2016. 2016. IEEE. 89. Ovaska, S.J., R.E. Dragseth, and S.A. Hanssen, Direct-to-chip liquid cooling for reducing power consumption in a subarctic supercomputer centre. International Journal of High Performance Computing and Networking, 2016. 9(3): p. 242-249. 90. Kelkar, K.M. and S.V. Patankar. Analysis and design of liquid-cooling systems using flow network modeling (FNM). in ASME 2003 International Electronic Packaging Technical Conference and Exhibition (InterPACK2003). 2003. 91. Ellsworth, M.J. Flow network analysis of the IBM power 775 supercomputer water cooling system. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on. 2014. IEEE. 92. Alkharabsheh, S., B. Ramakrishnan, and B. Sammakia. Pressure drop analysis of direct liquid cooled (DLC) rack. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2017 16th IEEE Intersociety Conference on. 2017. IEEE. 93. Sahini, M., C. Kshirsagar, M. Kumar, D. Agonafer, J. Fernandes, J. Na, V. Mulay, P. McGinn, and M. Soares. Rack-level study of hybrid cooled servers using warm water cooling for distributed vs. centralized pumping systems. in 2017 33rd Thermal Measurement, Modeling & Management Symposium (SEMI-THERM). 2017. 94. Chu, R.C., M.K. Iyengar, V. Kamath, and R.R. Schmidt, Energy efficient apparatus and method for cooling an electronics rack. 2010, Google Patents. 95. Iyengar, M., M. David, P. Parida, V. Kamath, B. Kochuparambil, D. Graybill, M. Schultz, M. Gaynes, R. Simons, and R. Schmidt. Server liquid cooling with chiller-less data center design to enable significant energy savings. in Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2012 28th Annual IEEE. 2012. IEEE. 96. David, M.P., M.K. Iyengar, P. Parida, R.E. Simons, M. Schultz, M. Gaynes, R. Schmidt, and T. Chainer. Impact of operating conditions on a chiller-less data center test facility with liquid cooled servers. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 97. Iyengar, M., M. David, P. Parida, V. Kamath, B. Kochuparambil, D. Graybill, M. Schultz, M. Gaynes, R. Simons, and R. Schmidt. Extreme energy efficiency using water cooled servers inside a chiller-less data center. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on. 2012. IEEE. 98. Parida, P.R., T. Chainer, M. Iyengar, M. David, M. Schultz, M. Gaynes, V. Kamath, B. Kochuparambil, R. Simons, and R. Schmidt. System-Level Design for Liquid Cooled Chiller-Less Data Center. in ASME 2012 International Mechanical Engineering Congress and Exposition. 2012. American Society of Mechanical Engineers. 99. Parida, P.R., T.J. Chainer, M.D. Schultz, and M.P. David. Cooling Energy Reduction during dynamically controlled data center operation. in ASME 2013 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems. 2013. American Society of Mechanical Engineers. 100. Meyer, N., M. Ries, S. Solbrig, and T. Wettig. iDataCool: HPC with hot-water cooling and energy reuse. in International Supercomputing Conference. 2013. Springer. 101. Douchet, F., D. Nortershauser, S. Le Masson, and P. Glouannec, Experimental and numerical study of water-cooled datacom equipment. Applied Thermal Engineering, 2015. 84: p. 350-359. 102. Schmidt, R., R.C. Chu, M. Ellsworth, M. Iyengar, D. Porter, V. Kamath, and B. Lehman. Maintaining datacom rack inlet air temperatures with water cooled heat exchanger. in Asme 2005 pacific rim technical conference and exhibition on integration and packaging of mems, nems, and electronic systems collocated with the asme 2005 heat transfer summer conference. 2005. American Society of Mechanical Engineers. 103. Schmidt, R., M. Iyengar, D. Porter, G. Weber, D. Graybill, and J. Steffes. Open side car heat exchanger that removes entire server heat load without any added fan power. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2010 12th IEEE Intersociety Conference on. 2010. IEEE. 104. Gao, T., E. Samadiani, B. Sammakia, and R. Schmidt. Comparative thermal and energy analysis of a hybrid cooling data center with rear door heat exchangers. in ASME 2013 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems. 2013. American Society of Mechanical Engineers. 105. Wemhoff, A.P. and A. Ortega. An exergy-based analysis of the effects of rear door heat exchange systems on data center energy efficiency. in Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2014 IEEE Intersociety Conference on. 2014. IEEE. 106. Mulay, V., D. Agonafer, and R. Schmidt. Liquid Cooling for Thermal Management of Data Centers. in ASME 2008 International Mechanical Engineering Congress and Exposition. 2008. American Society of Mechanical Engineers. 107. Ellsworth, M., L. Campbell, R. Simons, M. Iyengar, R. Schmidt, and R. Chu. The evolution of water cooling for IBM large server systems: Back to the future. in Thermal and Thermomechanical Phenomena in Electronic Systems, 2008. ITHERM 2008. 11th Intersociety Conference on. 2008. IEEE. 108. Schmidt, R. and M. Iyengar. Server rack rear door heat exchanger and the new ASHRAE recommended environmental guidelines. in ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability. 2009. American Society of Mechanical Engineers. 109. Almoli, A., A. Thompson, N. Kapur, J. Summers, H. Thompson, and G. Hannah, Computational fluid dynamic investigation of liquid rack cooling in data centres. Applied energy, 2012. 89(1): p. 150-155. 110. Gao, T., M. David, J. Geer, R. Schmidt, and B. Sammakia, Experimental and numerical dynamic investigation of an energy efficient liquid cooled chiller-less data center test facility. Energy and Buildings, 2015. 91: p. 83-96. 111. Sun Microsystems, I., Sun Fire V20z and Sun Fire V40z Servers. 2005. 112. Minyard, C., IPMI–A Gentle Introduction with OpenIPMI. 2004. 113. CoolIT. 2012; Available from: http://www.coolitsystems.com/. 114. Delta. FFB 40 X 40 X 25 mm series. 2017; Available from: http://www.deltaww.com/. 115. Al-Anii, Y.T.S., Holistic and Energy-Efficient Management of Datacentres. 2017, University of Leeds. 116. 3COM, SuperStack® 3 Switch 3870 Family Getting Started Guide, 3COM, Editor. 2004. 117. Airedale International Air Conditioning Limited. 2015; Available from: http://www.airedale.com/. 118. Wang, C.-C., J.-Y. Chang, and N.-F. Chiou, Effects of waffle height on the air-side performance of wavy fin-and-tube heat exchangers. Heat Transfer Engineering, 1999. 20(3): p. 45-56. 119. Wang, C.-C. and K.-Y. Chi, Heat transfer and friction characteristics of plain fin-and-tube heat exchangers, part I: new experimental data. International Journal of Heat and Mass Transfer, 2000. 43(15): p. 2681-2691. 120. Wongwises, S. and Y. Chokeman, Effect of fin pitch and number of tube rows on the air side performance of herringbone wavy fin and tube heat exchangers. Energy Conversion and Management, 2005. 46(13): p. 2216-2231. 121. Youn, B. and N. Kim, An experimental investigation on the airside performance of fin-and-tube heat exchangers having sinusoidal wave fins. Heat and Mass Transfer, 2007. 43(12): p. 1249-1262. 122. Wang, C.-C., J.-S. Liaw, and B.-C. Yang, Airside performance of herringbone wavy fin-and-tube heat exchangers–data with larger diameter tube. International Journal of Heat and Mass Transfer, 2011. 54(5): p. 1024-1029. 123. Pongsoi, P., S. Pikulkajorn, C.-C. Wang, and S. Wongwises, Effect of number of tube rows on the air-side performance of crimped spiral fin-and-tube heat exchanger with a multipass parallel and counter cross-flow configuration. International Journal of Heat and Mass Transfer, 2012. 55(4): p. 1403-1411. 124. Yu, R., A. Sommers, and N. Okamoto, Effect of a micro-grooved fin surface design on the air-side thermal-hydraulic performance of a plain fin-and-tube heat exchanger. International Journal of Refrigeration, 2013. 36(3): p. 1078-1089. 125. Ma, X., G. Ding, Y. Zhang, and K. Wang, Airside characteristics of heat, mass transfer and pressure drop for heat exchangers of tube-in hydrophilic coating wavy fin under dehumidifying conditions. International Journal of Heat and Mass Transfer, 2009. 52(19): p. 4358-4370. 126. Min, J., X. Wu, L. Shen, and F. Gao, Hydrophilic treatment and performance evaluation of copper finned tube evaporators. Applied Thermal Engineering, 2011. 31(14): p. 2936-2942. 127. Wang, C.-C. and C.-T. Chang, Heat and mass transfer for plate fin-and-tube heat exchangers, with and without hydrophilic coating. International Journal of Heat and Mass Transfer, 1998. 41(20): p. 3109-3120. 128. Kim, H.-Y. and B. Kang, Effects of hydrophilic surface treatment on evaporation heat transfer at the outside wall of horizontal tubes. Applied thermal engineering, 2003. 23(4): p. 449-458. 129. Hwang, Y., S. Popli, and R. Radermacher, Enhancement of Round Tube and Flat Tube-Louver Fin Heat Exchanger Performance Using Deluge Water Cooling, in International Refrigeration and Air Conditioning Conference 2012: Purdue University. 130. Bogan, N. and C. Park, Effects of Tube Row on Heat Transfer and Surface Wetting of Microscale Porous-Layer Coated, Horizontal-Tube, Falling-Film Evaporator. Journal of Heat Transfer (ASME), 2013. 131. Popli, S., Y. Hwang, and R. Radermacher. Performance Enhancement of Enhanced Herringbone Wavy-Fin Round Tube Inclined Heat Exchangers With and Without Hydrophilic Coating Using Evaporative Spray and Deluge Cooling. in ASME 2013 International Mechanical Engineering Congress and Exposition. 2013. American Society of Mechanical Engineers. 132. Wang, C., P. Chen, and J. Jang, Heat transfer and friction characteristics of convex-louver fin-and-tube heat exchangers. Experimental heat transfer, 1996. 9(1): p. 61-78. 133. Wang, C., W. Fu, and C. Chang, Heat transfer and friction characteristics of typical wavy fin-and-tube heat exchangers. Experimental thermal and fluid science, 1997. 14(2): p. 174-186. 134. Wang, C.-C., W.-S. Lee, W.-J. Sheu, and Y.-J. Chang, A comparison of the airside performance of the fin-and-tube heat exchangers in wet conditions; with and without hydrophilic coating. Applied Thermal Engineering, 2002. 22(3): p. 267-278. 135. Liu, L., Effects of air-side surface wettability on the performance of dehumidifying heat exchangers. 2011, University of Illinois at Urbana-Champaign. 136. KG, e.-p.M.G.C.; Available from: www.ebmpapst.com. 137. ebmpapst, EC axial fan - HyBlade. 2015. 138. CAREL. optiMist evaporative cooling 2013; Available from: http://www.carel.com/. 139. GRUNDFOS. CME 1-2 A-R-I-E-AQQE. Available from: http://www.grundfos.com/. 140. Books, H., Legionnaires’ disease: Technical guidance. 141. Clifton, J.R., W.J. Rossiter, and P.W. Brown, Degraded aqueous glycol solutions: pH values and the effects of common ions on suppressing pH decreases. Solar energy materials, 1985. 12(1): p. 77-86. 142. Rossiter, W.J., M. Godette, P.W. Brown, and K.G. Galuk, An investigation of the degradation of aqueous ethylene glycol and propylene glycol solutions using ion chromatography. Solar Energy Materials, 1985. 11(5-6): p. 455-467. 143. Note, T.A., Traversing a Duct to Determine Average Air Velocity. TI-106, 2014. 144. SPEC2008. Standard Performance Evaluation Corporation. 2017; Available from: https://www.spec.org/sfs2008/. 145. SPEC, S., Power and Performance, Benchmark Methodology V2. 1. 2011. 146. Voltech, PM1000+ POWER ANALYZER USER MANUAL. 2011. 147. Rossman, L.A., EPANET 2: users manual. 2000. 148. Cengel, Y.A. and J.M. Cimbala, Fluid Mechanics. Vol. 1. 2006, Tata McGraw-Hill Education, New York. 149. Xylem Inc. Electronically commutated spherical motor with permanent magnet rotor/impeller. Available from: www.xyleminc.com/brands/laingthermotech. 150. Gorti, N.P.K., Application aware performance, power consumption, and reliability tradeoff. 2014, Iowa State University. 151. Cader, T., V. Sorel, L. Westra, and A. Marquez, Liquid Cooling in Data Centers. ASHRAE Transactions, 2009. 115(1). 152. Dhavaleswarapu, H.K., C.P. Migliaccio, S.V. Garimella, and J.Y. Murthy, Experimental investigation of evaporation from low-contact-angle sessile droplets. Langmuir, 2009. 26(2): p. 880-888. 153. Kumari, N. and S.V. Garimella, Characterization of the heat transfer accompanying electrowetting or gravity-induced droplet motion. International Journal of Heat and Mass Transfer, 2011. 54(17): p. 4037-4050. 154. Nguyen, T.A., A.V. Nguyen, M.A. Hampton, Z.P. Xu, L. Huang, and V. Rudolph, Theoretical and experimental analysis of droplet evaporation on solid surfaces. Chemical Engineering Science, 2012. 69(1): p. 522-529. 155. Onan, C., D.B. Ozkan, and S. Erdem, CFD and Experimental Analysis of a Falling Film outside Smooth and Helically Grooved Tubes. Advances in Mechanical Engineering, 2014. 2014. 156. Wang, X. and A.M. Jacobi, A Thermodynamic Basis for Predicting Falling-Film Mode Transitions. International Journal of Refrigeration, 2014. 157. Paterson, C., Thin fluid films subject to external airflows. 2013, University of Strathclyde. 158. Wang, X., P. Hrnjak, S. Elbel, A. Jacobi, and M. He, Heat transfer performance for a falling-film on horizontal flat tubes. Journal of Heat Transfer, 2013. 135(7): p. 072901. 159. Jani, S. and M. Amini, Heat Transfer Analysis of Falling Film Evaporation on a Horizontal Elliptical Tube. Journal of Heat Transfer, 2012. 134(6): p. 064505. 160. David, S., K. Sefiane, and L. Tadrist, Experimental investigation of the effect of thermal properties of the substrate in the wetting and evaporation of sessile drops. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2007. 298(1): p. 108-114. 161. Mollaret, R., K. Sefiane, J. Christy, and D. Veyret, Experimental and numerical investigation of the evaporation into air of a drop on a heated surface. Chemical Engineering Research and Design, 2004. 82(4): p. 471-480. 162. Sobac, B. and D. Brutin, Thermal effects of the substrate on water droplet evaporation. Physical Review E, 2012. 86(2): p. 021602. 163. Shin, D.H., S.H. Lee, J.-Y. Jung, and J.Y. Yoo, Evaporating characteristics of sessile droplet on hydrophobic and hydrophilic surfaces. Microelectronic Engineering, 2009. 86(4): p. 1350-1353. 164. Gelderblom, H., A.G. Marin, H. Nair, A. van Houselt, L. Lefferts, J.H. Snoeijer, and D. Lohse, How water droplets evaporate on a superhydrophobic substrate. Physical Review E, 2011. 83(2): p. 026306. 165. Yu, Y.-S., Z. Wang, and Y.-P. Zhao, Experimental and theoretical investigations of evaporation of sessile water droplet on hydrophobic surfaces. Journal of Colloid and Interface Science, 2012. 365(1): p. 254-259. 166. Dash, S. and S.V. Garimella, Droplet evaporation on heated hydrophobic and superhydrophobic surfaces. Physical Review E, 2014. 89(4): p. 042402. 167. Sefiane, K., L. Tadrist, and M. Douglas, Experimental study of evaporating water–ethanol mixture sessile drop: Influence of concentration. International Journal of Heat and Mass Transfer, 2003. 46(23): p. 4527-4534. 168. Sefiane, K. and L. Tadrist, Experimental investigation of the de-pinning phenomenon on rough surfaces of volatile drops. International Communications in Heat and Mass Transfer, 2006. 33(4): p. 482-490. 169. Lee, K., C. Cheah, R. Copleston, V. Starov, and K. Sefiane, Spreading and evaporation of sessile droplets: Universal behaviour in the case of complete wetting. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2008. 323(1): p. 63-72. 170. Dunn, G., S. Wilson, B. Duffy, S. David, and K. Sefiane, The strong influence of substrate conductivity on droplet evaporation. Journal of Fluid Mechanics, 2009. 623: p. 329-351. 171. Stauber, J., S. Wilson, B. Duffy, and K. Sefiane, On the lifetimes of evaporating droplets. Journal of Fluid Mechanics, 2014. 744: p. R2. 172. Deegan, R.D., O. Bakajin, T.F. Dupont, G. Huber, S.R. Nagel, and T.A. Witten, Contact line deposits in an evaporating drop. Physical Review E, 2000. 62(1): p. 756. 173. Popov, Y.O., Evaporative deposition patterns: spatial dimensions of the deposit. Physical Review E, 2005. 71(3): p. 036313. 174. Dash, S. and S.V. Garimella, Droplet evaporation dynamics on a superhydrophobic surface with negligible hysteresis. Langmuir, 2013. 29(34): p. 10785-10795. 175. Gleason, K. and S.A. Putnam, Microdroplet evaporation with a forced pinned contact line. Langmuir, 2014. 30(34): p. 10548-10555. 176. Pan, Z., S. Dash, J.A. Weibel, and S.V. Garimella, Assessment of water droplet evaporation mechanisms on hydrophobic and superhydrophobic substrates. Langmuir, 2013. 29(51): p. 15831-15841. 177. Carle, F., B. Sobac, and D. Brutin, Experimental evidence of the atmospheric convective transport contribution to sessile droplet evaporation. Applied Physics Letters, 2013. 102(6): p. 061603. 178. Chen, Y., W. Hu, J. Wang, F. Hong, and P. Cheng, Transient effects and mass convection in sessile droplet evaporation: The role of liquid and substrate thermophysical properties. International Journal of Heat and Mass Transfer, 2017. 108: p. 2072-2087. 179. Park, J.K., J. Ryu, B.C. Koo, S. Lee, and K.H. Kang, How the change of contact angle occurs for an evaporating droplet: effect of impurity and attached water films. Soft Matter, 2012. 8(47): p. 11889-11896. 180. Nguyen, T.A. and A.V. Nguyen, Increased evaporation kinetics of sessile droplets by using nanoparticles. Langmuir, 2012. 28(49): p. 16725-16728. 181. Pittoni, P.G., C.-C. Chang, T.-S. Yu, and S.-Y. Lin, Evaporation of water drops on polymer surfaces: pinning, depinning and dynamics of the triple line. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2013. 432: p. 89-98. 182. Putnam, S.A., A.M. Briones, L.W. Byrd, J.S. Ervin, M.S. Hanchak, A. White, and J.G. Jones, Microdroplet evaporation on superheated surfaces. International Journal of Heat and Mass Transfer, 2012. 55(21-22): p. 5793-5807. 183. Bormashenko, E., A. Musin, and M. Zinigrad, Evaporation of droplets on strongly and weakly pinning surfaces and dynamics of the triple line. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2011. 385(1-3): p. 235-240. 184. Blake, T. and J. De Coninck, The influence of solid–liquid interactions on dynamic wetting. Advances in colloid and interface science, 2002. 96(1-3): p. 21-36. 185. Anantharaju, N., M. Panchagnula, and S. Neti, Evaporating drops on patterned surfaces: Transition from pinned to moving triple line. Journal of colloid and interface science, 2009. 337(1): p. 176-182. 186. Kulinich, S. and M. Farzaneh, Effect of contact angle hysteresis on water droplet evaporation from super-hydrophobic surfaces. Applied Surface Science, 2009. 255(7): p. 4056-4060. 187. Stauber, J.M., S.K. Wilson, B.R. Duffy, and K. Sefiane, On the lifetimes of evaporating droplets with related initial and receding contact angles. Physics of Fluids, 2015. 27(12): p. 122101. 188. Hu, D. and H. Wu, Volume evolution of small sessile droplets evaporating in stick-slip mode. Physical Review E, 2016. 93(4): p. 042805. 189. Sefiane, K. and R. Bennacer, Nanofluids droplets evaporation kinetics and wetting dynamics on rough heated substrates. Advances in Colloid and Interface Science, 2009. 147: p. 263-271. 190. Bazargan, V., Effect of substrate cooling and droplet shape and composition on the droplet evaporation and the deposition of particles, in 2014, The University Of British Columbia. p. 120. 191. Srinivasan, S., G.H. McKinley, and R.E. Cohen, Assessing the accuracy of contact angle measurements for sessile drops on liquid-repellent surfaces. Langmuir, 2011. 27(22): p. 13582-13589. 192. Lopes, M.C., E. Bonaccurso, T. Gambaryan-Roisman, and P. Stephan, Influence of the substrate thermal properties on sessile droplet evaporation: Effect of transient heat transport. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2013. 432: p. 64-70. 193. Berthier, J., Micro-drops and digital microfluidics. 2012: William Andrew. 194. Oxford nanoSystems. Available from: http://oxfordnanosystems.com/. 195. FTA4000. Available from: http://www.firsttenangstroms.com. 196. Lebedev, N.N., Special functions and their applications, ed. R.A. Silverman. 1965, United States of America: Prentice-Hall, Inc. 322. 197. MATLAB, Reference manual. The Mathworks Inc. Natick, Massachusetts, United States, 2013. 198. Incropera, F.P., Fundamentals of heat and mass transfer. 2011: John Wiley & Sons. 199. Cengel, Y.A. and M.A. Boles, Thermodynamics: an engineering approach. Sea, 2002. 1000: p. 8862. 200. Marrero, T.R. and E.A. Mason, Gaseous diffusion coefficients. Journal of Physical and Chemical Reference Data, 1972. 1(1): p. 3-118. 201. Faghri, A. and Y. Zhang, Transport phenomena in multiphase systems. 2006: Academic Press. 202. Girard, F., M. Antoni, S. Faure, and A. Steinchen, Influence of heating temperature and relative humidity in the evaporation of pinned droplets. Colloids and Surfaces A: Physicochemical and Engineering Aspects, 2008. 323(1): p. 36-49. Appendix A -"],"dcterms:accessrights":["public"],"dc:title":["Holistic Study of Thermal Management in Direct Liquid Cooled Data Centres: from the Chip to the Environment"],"dc:type":["Thesis"],"dc:type.qualificationlevel":["doctoral"],"dc:type.qualificationname":["Ph.D"]},"updated_at":"2026-11-18T22:28:23Z"}