<p>In this bachelor thesis, cable fault locators are studied for use on the overhead electrode lines in the HVDC (High Voltage Direct Current) Light project Caprivi Link. The cable fault locators studied operates with the principle of travelling waves, where a pulse is sent in the tested conductor. The time difference is measured from the injection moment to the reflection is received. If the propagation speed of the pulse is known the distance to the fault can be calculated. This type of unit is typically referred to as a TDR (Time Domain Reflectometer). The study is performed as a computer simulation where a simplified model of a TDR unit is created and applied to an electrode line model by using PSCAD/EMTDC. Staged faults of open circuit and ground fault types are placed at three distances on the electrode line model, different parameters of the TDR units such as pulse width and pulse amplitude along with its connection to the electrode line are then studied and evaluated. The results of the simulations show that it is possible to detect faults of both open circuit and ground fault types with a suitable TDR unit. Ground faults with high resistance occurring at long distances can be hard to detect due to low reflection amplitudes from the injections. This problem can somewhat be resolved with a function that lets the user compare an old trace of a “healthy” line with the new trace. The study shows that most of the faults can be detected and a distance to the fault can be calculated within an accuracy of ± 250 m. The pulse width of the TDR needs to be at least 10 μs, preferable 20 μs to deliver high enough energy to the fault to create a detectable reflection. The pulse amplitude seams to be of less significance in this simulation, although higher pulse amplitude is likely to be more suitable in a real measurement due to the higher energy delivered to the fault. The Hipotronics TDR 1150 is a unit that fulfil these requirements and should therefore be able to work as a line fault locator on the electrode line.</p>

Identiferoai:union.ndltd.org:UPSALLA/oai:DiVA.org:hv-2620
Date January 2010
CreatorsHermansson, Andreas
PublisherUniversity West, Department of Engineering Science
Source SetsDiVA Archive at Upsalla University
LanguageEnglish
Detected LanguageEnglish
TypeStudent thesis, text

Page generated in 0.0021 seconds