Return to search

Análise de sistemas de aterramento com hastes concretadas submetidos a correntes impulsivas.

Submitted by Lucienne Costa (lucienneferreira@ufcg.edu.br) on 2018-04-25T17:58:53Z
No. of bitstreams: 1
GABRIEL VIDAL NEGREIROS BEZERRA – DISSERTAÇÃO (PPGEE) 2017.pdf: 5032226 bytes, checksum: 900940f480110db5450f19583af7d19d (MD5) / Made available in DSpace on 2018-04-25T17:58:53Z (GMT). No. of bitstreams: 1
GABRIEL VIDAL NEGREIROS BEZERRA – DISSERTAÇÃO (PPGEE) 2017.pdf: 5032226 bytes, checksum: 900940f480110db5450f19583af7d19d (MD5)
Previous issue date: 2017-03-30 / CNPq / Neste trabalho é realizada uma avaliação da resposta impulsiva de aterramento com
haste concretada, considerando o efeito da ionização do solo. Para isso, o aterramento
foi representado e simulado utilizando uma ferramenta computacional de simulação em
três dimensões por meio do método dos elementos finitos. A representação computacional, bem como a validação da mesma, foi feita tomando-se como base dados experimentais apresentados na literatura. O fenômeno da ionização do solo foi implementado ponto a ponto, utilizando o equacionamento do modelo dinâmico de ionização do solo, possibilitando que aterramentos com diferentes formatos geométricos sejam avaliados. Avaliou-se a impedância transitória de uma haste concretada padronizada para solos com diferentes resistividades. Além disso, procedeu-se com uma análise da resposta impulsiva da haste concretada para diferentes parâmetros geométricos, a saber: raio do concreto envolvente, comprimento vertical da haste concretada, comprimento vertical do concreto envolvente e profundidade da haste concretada em relação ao nível do solo. Por fim, propõem-se limites práticos e sugestões de dimensões para a haste concretada, de forma que a reposta impulsiva seja otimizada. / In this research, was performed an impulsive response evaluation of concrete encased
groundings, considering de soil ionization effect. In order to achive this, the grouding was
represented and simulated in three dimensions using a finite element method software.
The computational representation and validation were performed using experimental data
presented in the literature. The soil ionization effect was implemented in a point form,
allowing evaluate groudings with different geometric formats. It was studied the transient
impedance of a standard concrete encased rod placed in soils with different resistivity
values. Furthermore, was performed a transient response analysis for different geometric
parameters of the concrete encased rod, namely: the concrete radius, the vertical length of
the concrete encased rod, the vertical length of the concrete encased rod, the surrounding
concrete and the depth of the concrete encased rod in relation to the soil surface. Finally,
practical limits and suggested dimensions for the concrete encased rod are proposed, in
order to optimize the impulse response.

Identiferoai:union.ndltd.org:IBICT/oai:localhost:riufcg/492
Date25 April 2018
CreatorsBEZERRA, Gabriel Vidal Negreiros.
ContributorsCOSTA, Edson Guedes da., PEREIRA, Helder Alves., SERRES, Alexandre Jean René., LIRA, George Rossany Soares de., FREIRE, Raimundo Carlos Silvério.
PublisherUniversidade Federal de Campina Grande, PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA, UFCG, Brasil, Centro de Engenharia Elétrica e Informática - CEEI
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Biblioteca de Teses e Dissertações da UFCG, instname:Universidade Federal de Campina Grande, instacron:UFCG
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0021 seconds