Método para avaliação de conforto térmico em região de clima quente e úmido do Brasil

Tese (doutorado) - Universidade Federal de Santa Catarina, Centro Tecnológico, Programa de Pós-Graduação em Engenharia Civil, Florianópolis, 2009 / Made available in DSpace on 2012-10-24T12:40:35Z (GMT). No. of bitstreams: 1
278919.pdf: 2690739 bytes, checksum: 08fee63006a860ff102e107c7e239fad (MD5) / Atualmente para a avaliação de conforto térmico no ambiente construído é recomendada a aplicação do modelo Fanger ou VMP/PPD, normalizado pela ISO7730. Tal modelo baseia-se no princípio físico do balanço térmico entre o homem e o ambiente, que leva em conta a relação entre as sensações térmicas experimentadas pelas pessoas e a carga térmica que atua sobre seus corpos, essa última definida como a diferença entre a produção interna de calor do corpo - representada pela taxa metabólica - e os mecanismos fisiológicos de transferência desse calor para o ambiente. Ocorre que esse modelo foi desenvolvido a partir de experimento realizado em câmara climatizada, com as variáveis climáticas controladas pelo pesquisador, diferentemente da realidade de campo. Isso tem permitido que com freqüência haja discrepâncias entre as sensações indicadas pelas pessoas e a indicada pelo referido modelo. Essas discrepâncias são observadas em várias regiões do mundo, inclusive no Brasil, conforme relatado nos nossos poucos trabalhos já desenvolvidos. Nesse contexto, o objetivo principal desta tese foi estabelecer modelo alternativo para a avaliação de conforto térmico em ambientes internos de edificações localizadas em região de clima quente do Brasil, com pessoas desenvolvendo atividade sedentária, a partir de dados levantados em 3 ambientes ventilados naturalmente e outro artificialmente climatizado. Para tanto, o modelo resultante empregou dados obtidos a partir de equipamentos de fácil utilização, correntemente encontrados no mercado regional e que não fossem financeiramente dispendiosos. Além disso, aplicou os conceitos da Bioestatística em função do forte e inquestionável
componente psicológico existente na informação das sensações e preferências térmicas humanas. No desenvolvimento da pesquisa, observaram-se contradições a algumas afirmativas existentes no modelo Fanger; por exemplo, a existência no ambiente condicionado artificialmente, em alguns períodos do experimento, de diferenças significativas entre os gêneros dos voluntários. Conclusão ainda mais interessante foi a de que os votos manifestados pelos homens e mulheres no ambiente condicionado artificialmente não revelaram correlação com o índice de isolamento médio das roupas utilizadas, o que sugere novos experimentos. Da mesma forma, verificou-se a existência de diferenças entre as avaliações térmicas manifestadas pelos dois grupos de recrutas e veteranos, o que também contraria o afirmado no embasamento do modelo normalizado, em que se afirma não haverem sido encontradas diferenças significativas entre voluntários de diferentes regiões e idades. / The assessment of thermal comfort in a built environment is currently performed through the application of Fanger model or PMV/PPD model, normalized by ISO7730. Such a model is based on a physical principle of thermal balance between man and the environment, which takes into account the relationship between the thermal sensations experienced by the people and the thermal load that acts upon their bodies, that is defined as the difference between the inner production of the body#s heat # represented by the metabolic rate # and the physiological transference mechanisms of heat to the environment. This model, however, was developed from an experiment conducted in acclimatized chamber with climatic variables controlled by the researcher, differently from the field reality. This has allowed frequent discrepancies between the sensations indicated by the people and that indicated by the model. These discrepancies have been observed in several regions in the world, including Brazil, as reported in the few studies developed. The main objective of this paper is to establish an alternative model to assess thermal comfort in indoor environments of buildings located in a hot region in Brazil, with people developing sedentary activities. Data were collected in one artificially acclimatized environment and in three naturally ventilated ones. In addition, the model obtained data from non costly, easyto- use equipment, currently found in the regional market. The proposed model applied biostatistics concepts because of the sound and undisputable psychological component existing in the information of human sensations and thermal preferences. During the development of the research, contradictions were observed to some affirmations in the Fanger model; for example, significant differences between the gender of the participants were seen in conditioned environment in some periods of experiment. A more interesting conclusion was that the votes manifested by males and females did not show correlation with the index of mean thermal isolation of the clothes worn, which suggests new experiments. Likewise, differences between the thermal assessments of the two groups (recruits and veterans) were seen, which also disproves the standardized model, which affirms that no significant differences were seen between voluntaries of different regions and ages. Thus, the results presented in this work should contribute to research on thermal comfort developed in Brazil. In addition to proposing an alternative model of assessment in naturally conditioned environments, they reveal new contradictions to the standardized model.

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.ufsc.br:123456789/92816
Date24 October 2012
CreatorsAndreasi, Wagner Augusto
ContributorsUniversidade Federal de Santa Catarina, Lamberts, Roberto
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/doctoralThesis
Format204 p.| il., grafs., tabs.
Sourcereponame:Repositório Institucional da UFSC, instname:Universidade Federal de Santa Catarina, instacron:UFSC
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0021 seconds