This dissertation proposes a power management and control strategy for islanded microgrids,
which consist of multiple electronically-interfaced distributed energy resource (DER) units, to achieve a prescribed load sharing scheme. This strategy provides i) a power management system to specify voltage set points based on a classical power flow analysis; 2) DER local controllers, designed based on a robust, decentralized, servomechanism approach, to track the set points; and 3) a frequency control and synchronization scheme. This strategy is then
generalized to incorporate both power-controlled and voltage-controlled DER units.
Since the voltage-controlled DER units do not use inner current control loops, they are vulnerable to overcurrent/overload transients subsequent to system severe disturbances, e.g., faults and overloading conditions. To prevent DER unit trip-out or damage under these conditions, an overcurrent/overload protection scheme is proposed that detects microgrid abnormal conditions, modifies the terminal voltage of the corresponding VSC to limit DER unit output current/power within the permissible range, and restores voltage controllers subsequently. Under certain circumstances, e.g., microgrid islanding and communication failure, there is a need to switch from an active to a latent microgrid controller. To minimize the resultant transients, control transition should be performed smoothly. For the aforementioned two circumstances, two smooth control transition techniques, based on 1) an observer and 2) an auxiliary tracking controller, are proposed to achieve a smooth control transition. A typical microgrid system that adopts the proposed strategy is investigated. The microgrid dynamics are investigated based on eigenvalue sensitivity and robust analysis studies to evaluate the performance of the closed-loop linearized microgrid. Extensive case studies, based on time-domain simulations in the PSCAD/EMTDC platform, are performed to evaluate
performance of the proposed controllers when the microgrid is subject to various disturbances, e.g., load change, DER abrupt outage, configuration change, faults, and overloading conditions. Real-time hardware-in-the-loop case studies, using an RTDS system and NI-cRIO industrial controllers, are also conducted to demonstrate ease of hardware implementation, validate controller performance, and demonstrate its insensitivity to hardware implementation issues, e.g., noise, PWM nonidealities, A/D and D/A conversion errors and delays.
Identifer | oai:union.ndltd.org:TORONTO/oai:tspace.library.utoronto.ca:1807/33989 |
Date | 11 December 2012 |
Creators | Etemadi, Amir Hossein |
Contributors | Iravani, Mohammad Reza |
Source Sets | University of Toronto |
Language | en_ca |
Detected Language | English |
Type | Thesis |