This work deals with the problem of choosing the correct heating curve for a certain building package (envelope plus distribution system). This topic is particularly relevant in countries like Sweden where heating curve is the most common way to control heat pumps. The analysis, involving four building models with respective distribution systems (two have floor heating and two radiators) and a variable speed GSHP, shows how, for a fixed location, the proper heating curve changes considering different building envelopes and different emitters. It is highlighted, therefore, how the adoption of a generic heating curve for all the buildings can cause discomfort and energy inefficiency. An algorithm to adjust the curve is then presented, and the results are compared with the reference case. The algorithm manages to improve comfort considerably and, for the A-class building, also SPF increases a lot (12.5%). The whole study was performed by means of TRNSYS® neglecting the DHW demand. / EffSys Expand P18: Smart Control Strategies for Heat Pump Systems
Identifer | oai:union.ndltd.org:UPSALLA1/oai:DiVA.org:kth-240070 |
Date | January 2018 |
Creators | Andricciola, Antonio |
Publisher | KTH, Tillämpad termodynamik och kylteknik |
Source Sets | DiVA Archive at Upsalla University |
Language | English |
Detected Language | English |
Type | Student thesis, info:eu-repo/semantics/bachelorThesis, text |
Format | application/pdf |
Rights | info:eu-repo/semantics/openAccess |
Relation | TRITA-ITM-EX ; 2018:739 |