Investigation of alternative current measurements in high-voltage applications

ABB:s MACH2 system uses a number of currents to ignite thyristors for AC/DC-trassfformation and they are measured for control and protection. The measurement methods used today has major drawbacks. Two alternative techniques are investigated, one based on the Hall-Effect (HED) and the other based on Anisotropic Magnetoreistanse (AMR), both techniques sensing the magnetic field produced by currents in a conductor. The HED hawe low sensitivity so some kind of flux concentrators is needed. This adds volume, costs and complexity to the device. The AMR technique is much more sensitive than the HED. Unfortunately AMR are also much more sensitive for high over currents that may damage the devise, and they are not as common on te market. By testing linearity, step response and frequency dependency for some components, my conclusion is that HED components with toroidal flux concentrators utilizing magnetic feedback (Closed Loop, CL) may be used in this particular application. A drawback with CL are that they, when measuring sharp edged step signals, suffer from overshoots at the output that might activate the over current protection.