Sensitivity and Uncertainty Analysis of Occupancy-related Parameters in Energy Modeling of Unt Zero Energy Lab

The study focuses on the sensitivity and uncertainty analysis of occupancy-related parameters using Energyplus modeling method. The model is based on a real building Zero Energy Lab in Discovery Park, at University of North Texas. Four categories of parameters are analyzed: heating/cooling setpoint, lighting, equipment and occupancy. Influence coefficient (IC) is applied in the sensitivity study, in order to compare the impact of individual parameter on the overall building energy consumption. The study is conducted under Texas weather file as well as North Dakota weather file in order to find weather’s influence of sensitivity. Probabilistic collocation method (PCM) is utilized for uncertainty analysis, with an aim of predicting future energy consumption based on history or reference data set. From the study, it is found that cooling setpoint has the largest influence on overall energy consumption in both Texas and North Dakota, and occupancy number has the least influence. The analysis also indicates schedule’s influence on energy consumption. PCM is able to accurately predict future energy consumption with limited calculation, and has great advantage over Monte Carlo Method. The polynomial equations are generated in both 3-order and 6-order, and the 6-order equation is proved to have a better result, which is around 0.1% compared with real value.

Identiferoai:union.ndltd.org:unt.edu/info:ark/67531/metadc499991
Date08 1900
CreatorsXiong, Guangyuan
ContributorsTao, Yong X., Wan, Yan, Rayegan, Rambod
PublisherUniversity of North Texas
Source SetsUniversity of North Texas
LanguageEnglish
Detected LanguageEnglish
TypeThesis or Dissertation
FormatText
RightsPublic, Xiong, Guangyuan, Copyright, Copyright is held by the author, unless otherwise noted. All rights Reserved.

Page generated in 0.0022 seconds