Return to search

Estudo experimental de técnicas de medição de descargas parciais nos enrolamentos estatóricos de hidrogeradores / Experimental study of techniques for partial discharges measurements in the stator windings of hydrogenerators

Submitted by Edisangela Bastos (edisangela@ufpa.br) on 2014-01-13T19:23:18Z
No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Dissertacao_EstudoExperimentalTecnicas.pdf: 7117519 bytes, checksum: fb5695be8f32467589254855458aa5bd (MD5) / Approved for entry into archive by Ana Rosa Silva(arosa@ufpa.br) on 2014-01-16T14:10:58Z (GMT) No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Dissertacao_EstudoExperimentalTecnicas.pdf: 7117519 bytes, checksum: fb5695be8f32467589254855458aa5bd (MD5) / Made available in DSpace on 2014-01-16T14:10:58Z (GMT). No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Dissertacao_EstudoExperimentalTecnicas.pdf: 7117519 bytes, checksum: fb5695be8f32467589254855458aa5bd (MD5)
Previous issue date: 2013 / Este trabalho tem como objetivo geral analisar experimentalmente técnicas para medição de descargas parciais nos enrolamentos estatóricos de hidrogeradores. Para atingir
o objetivo proposto, primeiramente foi realizado um estudo bibliográfico sobre como é a
estrutura dos enrolamentos do estator, com ênfase na isolação elétrica, assim como os
conceitos de descargas parciais e técnicas empregadas para medição em hidrogeradores.
Em seguida, foi montado em laboratório um arranjo experimental para o estudo das técnicas
de medição de descargas parciais nos enrolamentos do estator utilizando seis acopladores
diferentes, sendo quatro acopladores capacitivos convencionais de 80, 220, 500 e 1000 pF,
e dois sistemas experimentais, uma antena SSC fabricada com microfita e um cabo coaxial
RG 58, desencapado, utilizado como antena. A avaliação da sensibilidade destes seis
sistemas foi divida em duas etapas: primeiro foi analisada a resposta dos acopladores à
aplicação de um sinal conhecido de calibração e, em seguida, foi analisada a resposta dos
mesmos durante ensaios com alta tensão. Para aplicação de um sinal conhecido de
calibração os acopladores capacitivos apresentaram maior sensibilidade em relação à
antena e ao cabo coaxial. Já a resposta durante os ensaios com alta tensão mostrou que a
sensibilidade da antena é maior que a do método convencional de medição de descargas
parciais em hidrogeradores, baseado em acopladores capacitivos de 80 e 220 pF. Os
resultados obtidos em laboratório mostraram que a medição de descargas parciais através
da antena pode ser realizada de forma satisfatória na avaliação da condição operacional dos
enrolamentos do estator de hidrogeradores, sem perda significativa de informação e com
aumento significativo de sensibilidade na quantificação do fenômeno, cerca de duas vezes
maior que a sensibilidade do acoplador de 220 pF e quatro vezes a do acoplador de 80 pF. / This paper aims at analyzing experimental techniques for partial discharges
measuring in the stator windings of hydrogenerators. To reach the goal, first proposed a
study of the literature on how the structure of the stator windings, with an emphasis on
electrical insulation, as well as the concepts of partial discharges and techniques used for
measuring in hydrogenerators. It was then mounted in a laboratory arrangement for studying
techniques for measuring partial discharges in the stator winding using six different couplers,
four conventional capacitive couplers 80, 220, 500 and 1000 pF, and two experimental
systems, an antenna, ribbon coaxial cable and RG 58, bare used with the antenna function.
The evaluation of the sensitivity of these six systems has been divided in two steps: first
were analyzed the responses of couplers applying a known calibration signal, and then
analyzed the response of the same high voltage during testing. For application of a known
signal calibration the capacitive couplers showed greater sensitivity than antenna and coaxial
cable. Already during the response tests showed that the High Voltage sensitivity of the
antenna tape is larger than the conventional method of measuring partial discharges in hydro
using capacitive couplers 80 and 220 pF. The results obtained in the laboratory showed that
the measurement of partial discharges through the antenna tape can be performed
satisfactorily in the evaluation of the operating condition of the stator windings of hydro,
without either significant loss of sensitivity information or the quantification of the
phenomenon.

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.ufpa.br:2011/4612
Date10 July 2013
CreatorsBRASIL, Fernando de Souza
ContributorsDMITRIEV, Victor Alexandrovich
PublisherUniversidade Federal do Pará, Programa de Pós-Graduação em Engenharia Elétrica, UFPA, Brasil, Instituto de Tecnologia
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Repositório Institucional da UFPA, instname:Universidade Federal do Pará, instacron:UFPA
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0022 seconds