Despacho hidrotérmico de curto prazo na presença de transações de potência /Orrego Palacio, Nolasco de Jesús January 2000 (has links)
Dissertação (Mestrado) - Universidade Federal de Santa Catarina, Centro Tecnológico. / Made available in DSpace on 2012-10-17T19:31:00Z (GMT). No. of bitstreams: 0Bitstream added on 2014-09-25T18:59:18Z : No. of bitstreams: 1
152466.pdf: 3289800 bytes, checksum: 3b727b001899f0f5d4184adaf6dc1ad3 (MD5) / Nesta dissertação o Despacho Hidrotérmico de Curto Prazo na Presença de Transações Bilaterais de Potência (DHCPCT), é formulado como um problema de otimização e resolvido através de um método de Pontos Interiores tipo Primal-Dual. Considerando-se que o mercado de energia siga o modelo pool-bilateral, no modelo são representadas as perdas totais associadas à demanda do pool e a cada transação bilateral. São apresentadas três formas distintas de se operar o sistema: (i) despacho conjunto da potência do pool e dos contratos bilaterais; (ii) despacho com priorização das transações bilaterais e (iii) despacho com priorização da demanda do pool. São analisadas as conseqüências de cada estratégia de operação.
|
2 |
Análise de controle primário de carga-frequencia em ambiente estocástico e determinísticoSilva, José Roberto Pinto da January 1986 (has links)
Dissertação (mestrado) - Universidade Federal de Santa Catarina, Centro Tecnológico. Programa de Pós -Graduação em Engenharia Elétrica. / Made available in DSpace on 2012-10-15T23:57:21Z (GMT). No. of bitstreams: 0Bitstream added on 2016-01-08T15:23:51Z : No. of bitstreams: 1
262694.pdf: 2008469 bytes, checksum: aa5d4149786b9bcdde0108bb40902168 (MD5)
|
3 |
Uso de medição fasorial sincronizada visando a melhoria da estabilidade de sistemas elétricos de potênciaMarini, Robson Luis Valim January 2005 (has links)
Dissertação (mestrado) - Universidade Federal de Santa Catarina, Centro Tecnológico. Programa de Pós-Graduação em Engenharia Elétrica / Made available in DSpace on 2013-07-16T01:09:27Z (GMT). No. of bitstreams: 1
228511.pdf: 2735715 bytes, checksum: bab4d7ec52ce170d392d0a81d8dc2ed4 (MD5)
|
4 |
Análise de alterações em redes de potênciaFlorentin, Carlos Manuel Cardozo January 1985 (has links)
Dissertação (mestrado) - Universidade Federal de Santa Catarina, Centro Tecnológico. Programa de Pós-Graduação em Engenharia Elétrica. / Made available in DSpace on 2012-10-15T23:12:45Z (GMT). No. of bitstreams: 0Bitstream added on 2016-01-08T15:02:44Z : No. of bitstreams: 1
262681.pdf: 7790957 bytes, checksum: 1d6de43a4c4cc1ed3e004c5dcb4a3748 (MD5)
|
5 |
Estudos de acesso de geração distribuída em redes de subtransmissão mediante um aplicativo comercial de fluxo de potência ótimoRibeiro, Darlessandro da Silva January 2009 (has links)
Dissertação (mestrado) - Universidade Federal de Santa Catarina, Centro Tecnológico, Programa de Pós-Graduação em Engenharia Elétrica, Florianópolis, 2009. / Made available in DSpace on 2012-10-24T17:01:59Z (GMT). No. of bitstreams: 1
268490.pdf: 1997712 bytes, checksum: 2e59a392f3cb30b36647b091ab233804 (MD5) / As mudanças recentes de estrutura no sistema elétrico (geração, transmissão, subtransmissão, distribuição e comercialização de energia) têm motivado a interligação da geração distribuída aos sistemas de potência. Outro fato importante é que as empresas e concessionárias de energia elétrica estão constantemente buscando novas alternativas para atuar sobre a correção do perfil de tensão e a minimização de perdas nos alimentadores das redes de distribuição e subtransmissão de energia elétrica. O sistema analisado é uma pequena parte da rede real de distribuição e subtransmissão de energia elétrica do Oeste Catarinense e a ferramenta utilizada para a realização das simulações e obtenção dos resultados foi o simulador de redes: FLUPOT (Fluxo de Potência Ótimo). Como a GD ainda é uma tecnologia recente, existem até então muitas lacunas quanto ao entendimento do impacto desta nova topologia na estabilidade e em outros índices de desempenho em regime permanente do sistema elétrico. Neste trabalho de pesquisa determinou-se o impacto da inserção da geração distribuída em sistemas de potência associados aos seguintes aspectos técnicos: variação do perfil de tensão do sistema em regime permanente, perdas elétricas de potência ativa e reativa, e maximização do carregamento. Diversos cenários e condições de carregamento do sistema foram considerados com o intuito de contribuir quanto ao estudo teórico deste problema, em relação ao comportamento do sistema.
|
6 |
Programas de participação de consumidores aliados a outras ações de controle para alívio de condições operacionais críticas em sistemas elétricos de potênciaNakanishi, Sandra Hitomi January 2006 (has links)
Dissertação (mestrado) - Universidade Federal de Santa Catarina, Centro Tecnológico. Programa de Pós-Graduação em Engenharia Elétrica. / Made available in DSpace on 2012-10-22T16:52:17Z (GMT). No. of bitstreams: 0 / O objetivo desta dissertação é a aplicação de programas de gerenciamento pelo lado da demanda baseados em incentivos, denominados de Programas de Participação dos Consumidores (PPCs), em sistemas elétricos de potência. Estes programas propõem reduções incentivadas de demanda de consumidores em situações operacionais adversas. O aplicativo implementado é baseado em Fluxo de Potência Ótimo Dinâmico pelo método Primal-Dual de Pontos Interiores e a função-objetivo busca minimizar simultaneamente os custos de geração e os custos de não-faturamento decorrentes das reduções de consumo. O aplicativo computacional representa a rede elétrica através de um modelo não-linear, permitindo a avaliação da influência do PPC e de transformadores de comutação sob carga no perfil de tensão, que é hoje um dos problemas freqüentes na operação do sistema elétrico enfrentado pelas concessionárias. O resultado deste aplicativo informa quais consumidores no sistema devem reduzir suas cargas, bem como a potência a ser reduzida. Os resultados apresentados nesta dissertação mostram situações de problemas de perfil de tensão no sistema elétrico em que o PPC e/ou os transformadores de taps varáveis são acionados. A análise dos resultados obtidos mostra as vantagens operacionais e econômicas que uma concessionária pode obter com o uso do PPC, considerando a ação simultânea de outros dispositivos de controle.
|
7 |
Análise modal aplicada à estabilidade de tensão com a inclusão de modelos dinâmicos de cargasLerm, Andre Arthur Perleberg January 1995 (has links)
Dissertação (mestrado) - Universidade Federal de Santa Catarina, Florianópolis, 1995. / Made available in DSpace on 2013-12-05T20:22:47Z (GMT). No. of bitstreams: 1
99962.pdf: 3723446 bytes, checksum: 9d1d1ab36554cdf3d77b4ee5a91a9a04 (MD5)
Previous issue date: 1995 / Este trabalho aborda a estabilidade de tensão através da metodologia dinâmica, baseada na análise modal da matriz de estados do sistema. A análise dos autovalores da matriz de estados permite avaliar a condição de operação dinâmica estável, ou não, do sistema, sob condições estipuladas. O uso dos fatores de participação, por sua vez, permite a identificação das variáveis de estado com maior influência nos possíveis modos instáveis. O trabalho indica um índice de estabilidade medido em termos da demanda máxima que pode ser acrescentada ao sistema sem que este saia da condição de operação estável. A maior contribuição desta dissertação encontra-se na inclusão do comportamento dinâmico da carga, inédita neste tipo de abordagem. Apresenta os modelos de carga, entre estáticos e dinâmicos, que segundo o autor, são os mais importantes dentre os apresentados na literatura. Efetua várias simulações em dois diferentes sistemas, envolvendo diversos modelos de carga. Os resultados obtidos ressaltam a importância de uma modelagem realista da carga nos estudos de estabilidade de tensão. Através destes, ainda, a análise modal demonstra ser um método eficiente na determinação da estabilidade dinâmica de tensão em um sistema elétrico de potência.
|
8 |
Desenvolvimento de um LaboratÃrio Virtual para capacitaÃÃo TecnolÃgica a DistÃncia em ProteÃÃo de Sistemas ElÃtricos / Development of a Virtual Laboratory for Distance Training in Protection of Electrical SystemsCarlos Henrique de Castro Silva 14 November 2011 (has links)
CoordenaÃÃo de AperfeiÃoamento de Pessoal de NÃvel Superior / Com o aumento na demanda de energia elÃtrica e a exigÃncia de maior confiabilidade, seguranÃa e eficiÃncia na operaÃÃo de sistemas elÃtricos de potÃncia por parte dos ÃrgÃos reguladores, aumentou a necessidade por profissionais cada vez mais qualificados em planejamento e operaÃÃo dos sistemas de potÃncia. No entanto, com a necessidade de atualizaÃÃo tÃcnica continuada e em decorrÃncia da polÃtica de racionalizaÃÃo de custos e de disponibilizaÃÃo de pessoal, as tÃcnicas de ensino a distÃncia tÃm evoluÃdo e alcanÃado abrangÃncia nas mais diferentes Ãreas do conhecimento. Este trabalho apresenta um Simulador para Treinamento Presencial e a DistÃncia em OperaÃÃo e ProteÃÃo de Sistemas ElÃtricos (STOP). O simulador STOP à desenvolvido em Java, podendo ser utilizado em ambientes: Unix, Linux, Windows, MacOS. O STOP pode ser aplicado em treinamento presencial e a distÃncia e està voltado à capacitaÃÃo de estudantes de engenharia, tÃcnicos e profissionais da Ãrea de sistemas elÃtricos de potÃncia. O STOP està integrado a um Ambiente Virtual de Aprendizagem (AVA), o Moodle. A integraÃÃo enriquece o ensino-aprendizado tornando-o mais efetivo com o uso de uma ferramenta capaz de simular situaÃÃes reais. Os simuladores em ambientes virtuais sÃo alternativas para a reduÃÃo de custos em empresas e instituiÃÃes de ensino. O simulador STOP à um software composto de diagramas unifilares, com a representaÃÃo dos principais componentes do sistema de proteÃÃo, tornando possÃvel ao usuÃrio simular faltas e reconfigurar o sistema elÃtrico, por meio de ajustes de relÃs para coordenaÃÃo da proteÃÃo e redefiniÃÃo de parÃmetros. / As the demand for electrical energy increases and requirements from regulatory agencies for improved reliability, security and efficiency on the operation of electric power systems, the need for professionals ever more qualified on planning and operation power systems also increases. However, with the need for continued technical update and as a result of rationalization policies of costs and provision of personnel for training, the distance learning techniques have evolved and reached different areas of knowledge. This work presents a Simulator for Presence and Distance Learning about Operation and Protection of Electric Systems (STOP). The STOP Simulator is developed in Java, which enables it to be used in the following systems: Unix, Linux, Windows, MacOS. The STOP can be applied in class as well as distance training and is directed to the training of engineering students, technicians and professionals specialized on electric power systems. The STOP is integrated to a Learning Virtual Environment (AVA), the Moodle. The integration enhances the teaching-learning process making it more effective by using a tool able to simulate real life situations. Simulators in virtual environments are an alternative to reducing costs in companies and educational institutions. The STOP is a software tool featuring one-line diagrams with the main components of the protection system, short-circuits simulation and reconfiguration of the system by setting relays for coordination of the system protection and redefinition of parameters.
|
9 |
Estudo experimental de técnicas de medição de descargas parciais nos enrolamentos estatóricos de hidrogeradores / Experimental study of techniques for partial discharges measurements in the stator windings of hydrogeneratorsBRASIL, Fernando de Souza 10 July 2013 (has links)
Submitted by Edisangela Bastos (edisangela@ufpa.br) on 2014-01-13T19:23:18Z
No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Dissertacao_EstudoExperimentalTecnicas.pdf: 7117519 bytes, checksum: fb5695be8f32467589254855458aa5bd (MD5) / Approved for entry into archive by Ana Rosa Silva(arosa@ufpa.br) on 2014-01-16T14:10:58Z (GMT) No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Dissertacao_EstudoExperimentalTecnicas.pdf: 7117519 bytes, checksum: fb5695be8f32467589254855458aa5bd (MD5) / Made available in DSpace on 2014-01-16T14:10:58Z (GMT). No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Dissertacao_EstudoExperimentalTecnicas.pdf: 7117519 bytes, checksum: fb5695be8f32467589254855458aa5bd (MD5)
Previous issue date: 2013 / Este trabalho tem como objetivo geral analisar experimentalmente técnicas para medição de descargas parciais nos enrolamentos estatóricos de hidrogeradores. Para atingir
o objetivo proposto, primeiramente foi realizado um estudo bibliográfico sobre como é a
estrutura dos enrolamentos do estator, com ênfase na isolação elétrica, assim como os
conceitos de descargas parciais e técnicas empregadas para medição em hidrogeradores.
Em seguida, foi montado em laboratório um arranjo experimental para o estudo das técnicas
de medição de descargas parciais nos enrolamentos do estator utilizando seis acopladores
diferentes, sendo quatro acopladores capacitivos convencionais de 80, 220, 500 e 1000 pF,
e dois sistemas experimentais, uma antena SSC fabricada com microfita e um cabo coaxial
RG 58, desencapado, utilizado como antena. A avaliação da sensibilidade destes seis
sistemas foi divida em duas etapas: primeiro foi analisada a resposta dos acopladores à
aplicação de um sinal conhecido de calibração e, em seguida, foi analisada a resposta dos
mesmos durante ensaios com alta tensão. Para aplicação de um sinal conhecido de
calibração os acopladores capacitivos apresentaram maior sensibilidade em relação à
antena e ao cabo coaxial. Já a resposta durante os ensaios com alta tensão mostrou que a
sensibilidade da antena é maior que a do método convencional de medição de descargas
parciais em hidrogeradores, baseado em acopladores capacitivos de 80 e 220 pF. Os
resultados obtidos em laboratório mostraram que a medição de descargas parciais através
da antena pode ser realizada de forma satisfatória na avaliação da condição operacional dos
enrolamentos do estator de hidrogeradores, sem perda significativa de informação e com
aumento significativo de sensibilidade na quantificação do fenômeno, cerca de duas vezes
maior que a sensibilidade do acoplador de 220 pF e quatro vezes a do acoplador de 80 pF. / This paper aims at analyzing experimental techniques for partial discharges
measuring in the stator windings of hydrogenerators. To reach the goal, first proposed a
study of the literature on how the structure of the stator windings, with an emphasis on
electrical insulation, as well as the concepts of partial discharges and techniques used for
measuring in hydrogenerators. It was then mounted in a laboratory arrangement for studying
techniques for measuring partial discharges in the stator winding using six different couplers,
four conventional capacitive couplers 80, 220, 500 and 1000 pF, and two experimental
systems, an antenna, ribbon coaxial cable and RG 58, bare used with the antenna function.
The evaluation of the sensitivity of these six systems has been divided in two steps: first
were analyzed the responses of couplers applying a known calibration signal, and then
analyzed the response of the same high voltage during testing. For application of a known
signal calibration the capacitive couplers showed greater sensitivity than antenna and coaxial
cable. Already during the response tests showed that the High Voltage sensitivity of the
antenna tape is larger than the conventional method of measuring partial discharges in hydro
using capacitive couplers 80 and 220 pF. The results obtained in the laboratory showed that
the measurement of partial discharges through the antenna tape can be performed
satisfactorily in the evaluation of the operating condition of the stator windings of hydro,
without either significant loss of sensitivity information or the quantification of the
phenomenon.
|
10 |
Identificação de correntes de inrush na proteção diferencial de transformadores de potência através do gradiente da corrente diferencial e de mapas auto-organizáveisALENCAR, Raidson Jenner Negreiros de 10 June 2013 (has links)
Submitted by Edisangela Bastos (edisangela@ufpa.br) on 2014-01-13T19:13:15Z
No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Tese_IdentificacaoCorrentesInrush.pdf: 2054419 bytes, checksum: 36597eb5c3f5ca05153702c4e53b98db (MD5) / Approved for entry into archive by Ana Rosa Silva(arosa@ufpa.br) on 2014-01-15T13:17:40Z (GMT) No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Tese_IdentificacaoCorrentesInrush.pdf: 2054419 bytes, checksum: 36597eb5c3f5ca05153702c4e53b98db (MD5) / Made available in DSpace on 2014-01-15T13:17:40Z (GMT). No. of bitstreams: 2
license_rdf: 23898 bytes, checksum: e363e809996cf46ada20da1accfcd9c7 (MD5)
Tese_IdentificacaoCorrentesInrush.pdf: 2054419 bytes, checksum: 36597eb5c3f5ca05153702c4e53b98db (MD5)
Previous issue date: 2013 / A principal dificuldade encontrada na proteção diferencial de transformadores de potência é a correta distinção entre as correntes de inrush e as correntes de faltas internas. Tradicionalmente os relés diferenciais executam esta tarefa utilizando a técnica de restrição por harmônicos baseada na premissa de que as correntes de inrush possuem alta concentração de componentes harmônicas de segunda ordem, contudo essa técnica nem sempre é eficaz. O presente trabalho tem como objetivo apresentar a proposta de duas novas metodologias capazes de realizar a identificação e distinção entre as correntes de inrush das correntes de faltas internas na proteção diferencial de transformadores de potência através de metodologias que não dependem do conteúdo de harmônicos do sinal da corrente diferencial. A primeira metodologia proposta, denominada de método do gradiente da corrente diferencial, é baseada no comportamento do vetor gradiente, obtido através da diferenciação numérica do sinal da corrente diferencial. O critério de distinção utilizado é baseado no desvio padrão do ângulo do vetor gradiente que apresenta comportamento diferenciado para correntes de inrush e correntes de curto-circuito. A segunda metodologia proposta é baseada na capacidade de reconhecimento e classificação de padrões das redes neurais de Mapeamento Auto-organizável de Kohonen. Como padrão de entrada e de treinamento da rede neural é utilizado um vetor contendo quatro níveis do espectro do desvio padrão do ângulo do vetor gradiente da corrente diferencial nas três fases do transformador de potência. A eficácia dos métodos foi testada através da simulação de diversas situações de faltas internas e correntes de inrush, incluindo situações de “Sympathetic Inrush”, em um transformador de potência usando o software EMTP/ATP e através da implementação do algoritmo em MATLAB®, apresentando resultados altamente promissores. / A principal dificuldade encontrada na proteção diferencial de transformadores de potência é a correta distinção entre as correntes de inrush e as correntes de faltas internas. Tradicionalmente os relés diferenciais executam esta tarefa utilizando a técnica de restrição por harmônicos baseada na premissa de que as correntes de inrush possuem alta concentração de componentes harmônicas de segunda ordem, contudo essa técnica nem sempre é eficaz. O presente trabalho tem como objetivo apresentar a proposta de duas novas metodologias capazes de realizar a identificação e distinção entre as correntes de inrush das correntes de faltas internas na proteção diferencial de transformadores de potência através de metodologias que não dependem do conteúdo de harmônicos do sinal da corrente diferencial. A primeira metodologia proposta, denominada de método do gradiente da corrente diferencial, é baseada no comportamento do vetor gradiente, obtido através da diferenciação numérica do sinal da corrente diferencial. O critério de distinção utilizado é baseado no desvio padrão do ângulo do vetor gradiente que apresenta comportamento diferenciado para correntes de inrush e correntes de curto-circuito. A segunda metodologia proposta é baseada na capacidade de reconhecimento e classificação de padrões das redes neurais de Mapeamento Auto-organizável de Kohonen. Como padrão de entrada e de treinamento da rede neural é utilizado um vetor contendo quatro níveis do espectro do desvio padrão do ângulo do vetor gradiente da corrente diferencial nas três fases do transformador de potência. A eficácia dos métodos foi testada através da simulação de diversas situações de faltas internas e correntes de inrush, incluindo situações de “Sympathetic Inrush”, em um transformador de potência usando o software EMTP/ATP e através da implementação do algoritmo em MATLAB®, apresentando resultados altamente promissores.
|