At nuclear power plants, electrical valve actuators are important for ensuring that the reactor core is water covered and the pressure in the reactor tank and containment is limited. The electrical actuators are provided with overload protection in case of drawing higher current then the motors are rated for. When safety manoeuvres are needed, the overload protection must not trig and cause the valve to stop before completing the manoeuvre. Analyses have showed that the current settings of the overload protection may cause an illegitimate trig at the worst theoretically possible accident. A new method has been developed with conservative assumptions and applies overload protections for all electrical valve actuators at the three reactors in Forsmark.
Identifer | oai:union.ndltd.org:UPSALLA1/oai:DiVA.org:uu-176740 |
Date | January 2012 |
Creators | Bajramovic, Azur |
Publisher | Uppsala universitet, Institutionen för fysik och astronomi |
Source Sets | DiVA Archive at Upsalla University |
Language | Swedish |
Detected Language | English |
Type | Student thesis, info:eu-repo/semantics/bachelorThesis, text |
Format | application/pdf |
Rights | info:eu-repo/semantics/openAccess |
Page generated in 0.0017 seconds