Previous issue date: 2014-09-02 / Nos dias atuais a confiabilidade e a continuidade no fornecimento de energia elétrica
são cada vez mais exigidos. Os para-raios tem uma importante função neste
processo que é de proteger os demais equipamentos integrantes da rede elétrica de
sobretensões atmosféricas e de manobra. Quando falham, normalmente provocam o
desligamento de linhas de transmissão ou de transformadores, penalizando
severamente a concessionária pela indisponibilidade ou por multas impostas pela
agência reguladora. Como todo equipamento importante para o sistema elétrico, os
para-raios necessitam de técnicas eficazes de monitoramento. Na literatura e na
indústria podem ser encontradas diversas técnicas, procedimentos ou equipamentos
destinados ao seu monitoramento. Todos os procedimentos ou equipamentos
possuem suas limitações, vantagens e desvantagens, sejam elas técnicas,
econômicas ou operacionais. Visando suplantar algumas das limitações existentes
nas técnicas e procedimentos normalmente empregados no setor elétrico, encontrase
proposto neste trabalho uma metodologia de análise da condição operacional de
para-raios em campo, com base em medições da corrente de fuga total. Com esta
metodologia pretende-se minimizar as dificuldades operacionais relacionadas às
atividades de monitoramento, uma vez que será medida apenas a corrente de fuga
total, diferentemente de técnicas e procedimentos usuais que requerem também a
medição da tensão aplicada. Um banco de dados de correntes de fuga foi obtido
com medições realizadas em 05 (cinco) subestações. As medições foram agrupadas
por modelo/fabricante e tempo de operação dos para-raios. O instrumento de
medição utilizado é composto de um amperímetro do tipo alicate e um osciloscópio
digital portátil. O processo de medição em campo mostrou-se efetivo e prático
devido à facilidade de manuseio do instrumento utilizado. Ensaios em laboratório
foram realizados para avaliação da metodologia e dos instrumentos de medição. A
partir da base de dados produzida, foi possível com emprego de técnicas de
processamento de sinais e estatística, observar o comportamento gaussiano dos
dados e o crescimento do valor médio da componente de 3ª harmônica da corrente
total em função do tempo de operação, evidenciando, assim, a correlação entre a
elevação da corrente de fuga e a diminuição da vida útil dos para-raios. / Nowadays the reliability and continuity in the electricity supply are increasingly
required. The surge arresters has an important function in this process, which is to
protect the other utility equipment against lightning and switching surges. When they
fail, usually causing the shutdown of transmission lines or transformers, severely
penalizing the power utility for the unavailability or regulator fines. As any important
equipment for the electrical system, surge arresters need effective monitoring
techniques. In the literature and industry several techniques, procedures or
equipment for their monitoring can be found. All procedures or devices have their
limitations, advantages and disadvantages, whether technical, economic or
operational. Aiming to overcome some of the limitations in existing techniques and
procedures commonly employed in the electrical industry, a methodology for
analyzing the surge arrester operational condition based on measurements of total
leakage current is proposed in this paper. With this methodology is intended to
minimize operational difficulties associated with monitoring activities, since it will only
measure the total leakage current unlike the usual techniques and procedures, which
require the measurement of the applied voltage, too. A database of leakage currents
with measurements performed in five (05) power substations was obtained.
Measurements were grouped by arresters model/manufacturer and operation time.
The measuring instrument used consists of a clamp type ammeter and a portable
digital oscilloscope. The process of field measurement was effective and practical
due to the ease of handling of the used instrument. Laboratory tests were performed
to evaluate the methodology and measuring instruments. From the database
produced, it was possible through the use of techniques of signal processing and
statistical observe the Gaussian behavior of the data and the average increase of the
3rd harmonic component of the total current as a function of operating time, which
highlights thus, the correlation between the increase of the leakage current and the
decrease of the lifetime of the surge arrester.
Identifer | oai:union.ndltd.org:IBICT/oai:localhost:riufcg/448 |
Date | 21 April 2018 |
Creators | LIMA JÚNIOR, Geraldo Bezerra. |
Contributors | COSTA, Edson Guedes da., LIRA, George Rossany Soares de., NEVES, Washington Luiz Araújo., DANTAS, Karcius Marcellus Colaço. |
Publisher | Universidade Federal de Campina Grande, PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA, UFCG, Brasil, Centro de Engenharia Elétrica e Informática - CEEI |
Source Sets | IBICT Brazilian ETDs |
Language | Portuguese |
Detected Language | Portuguese |
Type | info:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis |
Source | reponame:Biblioteca de Teses e Dissertações da UFCG, instname:Universidade Federal de Campina Grande, instacron:UFCG |
Rights | info:eu-repo/semantics/openAccess |
Page generated in 0.0025 seconds