Spelling suggestions: "subject:"paraguaios dde óxido dde cinco"" "subject:"paraguaios dde óxido dde zinco""
1 |
Estudo de metodologia para modelagem e simulação de tensões induzidas de origem atmosférica em linhas de distribuição protegidas por para-raios de \'ZN\'O\' / Study of methodology for modeling and simulation of induced voltages of atmospheric origin in distribution lines protected by \'ZN\'O\' surge arrestersAraújo, Marcel Ayres de 18 July 2013 (has links)
As tensões induzidas e sobretensões geradas por descarga atmosféricas diretas e indiretas são um dos principais causadores de desligamentos não programados em redes de transmissão e distribuição. Estes desligamentos comprometem o fornecimento de energia a milhares de consumidores, sobretudo em regiões com constantes variações climáticas e com características orográficas bastante diversificadas, como apresentado no território brasileiro. Desse modo, cada vez mais esses fenômenos são estudados a fim de desenvolverem-se procedimentos para proteção contra distúrbios causados por descargas atmosféricas. Neste contexto, esta pesquisa contempla o estudo do estabelecimento das descargas atmosféricas indiretas e das tensões por elas induzidas em linhas de distribuição, assim como o assentamento das mesmas nestas redes de energia. Não obstante, utilizando-se um software capaz de representar transitórios eletromagnéticos são modelados e implementados um alimentador teste de distribuição e um sistema para estimação de tensões induzidas no domínio do tempo baseado no modelo de Sune Rusck. Também são modelados e implementados para-raios de óxido de zinco, de forma a representar suas características dinâmicas, para proteger a linha sob apreciação dos distúrbios provocados pelas tensões induzidas. A partir de uma análise comparativa entre a operação do sistema de distribuição em regime permanente e frente aos desdobramentos promovidos pelas tensões induzidas, é determinada a melhor configuração, localização e quantificação dos para-raios a serem instalados para proteção do sistema teste. Por meio da avaliação dos resultados das simulações computacionais observa-se a robustez da subestação e quais os ramos e cargas mais suscetíveis a perturbações frente às tensões induzidas, bem como a maior proteção oferecida pelos para-raios aos elementos conectados próximos aos seus nós de alocação. / The induced voltages and overvoltages generated by direct and indirect lightning are a major cause of not programmed shutdowns in transmission and distribution networks. These shutdowns compromise the power supply of thousands of consumers, especially in regions with frequent climatic variations and quite diverse orographic characteristics, as occurred on Brazilian soil. Thus, these phenomena are more and more studied in order to develop procedures for protection against disturbances caused by lightning. In this context, this research focuses on the study of the establishment of indirect lightning and the voltage induced by them on distribution lines, as well as their settlement on energy networks. However, using a software able to represent electromagnetic transients, a distribution test feeder and a system for estimating induced voltages in the time domain based on the Sune Rusck model are modeled and implemented. In addition, metal oxide surge arresters are modeled and implemented to represent its dynamic characteristics, in order to protect the line under consideration of disturbances caused by induced voltages. From a comparative analysis between the operation of the distribution system in steady state and facing the developments promoted by induced voltages, it is determined the best configuration, as well as the location and quantification of the surge arrester to be installed to protect the test system. Through evaluation of the results of computer simulations, it is observed the robustness of the substation and which branches and loads are more susceptible to the disturbances facing the induced voltages, and the greater protection offered by the surge arresters elements connected near to its nodes allocation.
|
2 |
Estudo de metodologia para modelagem e simulação de tensões induzidas de origem atmosférica em linhas de distribuição protegidas por para-raios de \'ZN\'O\' / Study of methodology for modeling and simulation of induced voltages of atmospheric origin in distribution lines protected by \'ZN\'O\' surge arrestersMarcel Ayres de Araújo 18 July 2013 (has links)
As tensões induzidas e sobretensões geradas por descarga atmosféricas diretas e indiretas são um dos principais causadores de desligamentos não programados em redes de transmissão e distribuição. Estes desligamentos comprometem o fornecimento de energia a milhares de consumidores, sobretudo em regiões com constantes variações climáticas e com características orográficas bastante diversificadas, como apresentado no território brasileiro. Desse modo, cada vez mais esses fenômenos são estudados a fim de desenvolverem-se procedimentos para proteção contra distúrbios causados por descargas atmosféricas. Neste contexto, esta pesquisa contempla o estudo do estabelecimento das descargas atmosféricas indiretas e das tensões por elas induzidas em linhas de distribuição, assim como o assentamento das mesmas nestas redes de energia. Não obstante, utilizando-se um software capaz de representar transitórios eletromagnéticos são modelados e implementados um alimentador teste de distribuição e um sistema para estimação de tensões induzidas no domínio do tempo baseado no modelo de Sune Rusck. Também são modelados e implementados para-raios de óxido de zinco, de forma a representar suas características dinâmicas, para proteger a linha sob apreciação dos distúrbios provocados pelas tensões induzidas. A partir de uma análise comparativa entre a operação do sistema de distribuição em regime permanente e frente aos desdobramentos promovidos pelas tensões induzidas, é determinada a melhor configuração, localização e quantificação dos para-raios a serem instalados para proteção do sistema teste. Por meio da avaliação dos resultados das simulações computacionais observa-se a robustez da subestação e quais os ramos e cargas mais suscetíveis a perturbações frente às tensões induzidas, bem como a maior proteção oferecida pelos para-raios aos elementos conectados próximos aos seus nós de alocação. / The induced voltages and overvoltages generated by direct and indirect lightning are a major cause of not programmed shutdowns in transmission and distribution networks. These shutdowns compromise the power supply of thousands of consumers, especially in regions with frequent climatic variations and quite diverse orographic characteristics, as occurred on Brazilian soil. Thus, these phenomena are more and more studied in order to develop procedures for protection against disturbances caused by lightning. In this context, this research focuses on the study of the establishment of indirect lightning and the voltage induced by them on distribution lines, as well as their settlement on energy networks. However, using a software able to represent electromagnetic transients, a distribution test feeder and a system for estimating induced voltages in the time domain based on the Sune Rusck model are modeled and implemented. In addition, metal oxide surge arresters are modeled and implemented to represent its dynamic characteristics, in order to protect the line under consideration of disturbances caused by induced voltages. From a comparative analysis between the operation of the distribution system in steady state and facing the developments promoted by induced voltages, it is determined the best configuration, as well as the location and quantification of the surge arrester to be installed to protect the test system. Through evaluation of the results of computer simulations, it is observed the robustness of the substation and which branches and loads are more susceptible to the disturbances facing the induced voltages, and the greater protection offered by the surge arresters elements connected near to its nodes allocation.
|
3 |
Monitoramento de Para-raios de Óxido de Zinco em campo. / Monitoring of Zinc Oxide surge arresters in the field.LIMA JÚNIOR, Geraldo Bezerra. 21 April 2018 (has links)
Submitted by Johnny Rodrigues (johnnyrodrigues@ufcg.edu.br) on 2018-04-21T14:21:51Z
No. of bitstreams: 1
GERALDO BEZERRA LIMA JÚNIOR - DISSERTAÇÃO PPGEE 2014..pdf: 4130681 bytes, checksum: 7aa2b6dbcd9d18892be46ec5c14536b6 (MD5) / Made available in DSpace on 2018-04-21T14:21:51Z (GMT). No. of bitstreams: 1
GERALDO BEZERRA LIMA JÚNIOR - DISSERTAÇÃO PPGEE 2014..pdf: 4130681 bytes, checksum: 7aa2b6dbcd9d18892be46ec5c14536b6 (MD5)
Previous issue date: 2014-09-02 / Nos dias atuais a confiabilidade e a continuidade no fornecimento de energia elétrica
são cada vez mais exigidos. Os para-raios tem uma importante função neste
processo que é de proteger os demais equipamentos integrantes da rede elétrica de
sobretensões atmosféricas e de manobra. Quando falham, normalmente provocam o
desligamento de linhas de transmissão ou de transformadores, penalizando
severamente a concessionária pela indisponibilidade ou por multas impostas pela
agência reguladora. Como todo equipamento importante para o sistema elétrico, os
para-raios necessitam de técnicas eficazes de monitoramento. Na literatura e na
indústria podem ser encontradas diversas técnicas, procedimentos ou equipamentos
destinados ao seu monitoramento. Todos os procedimentos ou equipamentos
possuem suas limitações, vantagens e desvantagens, sejam elas técnicas,
econômicas ou operacionais. Visando suplantar algumas das limitações existentes
nas técnicas e procedimentos normalmente empregados no setor elétrico, encontrase
proposto neste trabalho uma metodologia de análise da condição operacional de
para-raios em campo, com base em medições da corrente de fuga total. Com esta
metodologia pretende-se minimizar as dificuldades operacionais relacionadas às
atividades de monitoramento, uma vez que será medida apenas a corrente de fuga
total, diferentemente de técnicas e procedimentos usuais que requerem também a
medição da tensão aplicada. Um banco de dados de correntes de fuga foi obtido
com medições realizadas em 05 (cinco) subestações. As medições foram agrupadas
por modelo/fabricante e tempo de operação dos para-raios. O instrumento de
medição utilizado é composto de um amperímetro do tipo alicate e um osciloscópio
digital portátil. O processo de medição em campo mostrou-se efetivo e prático
devido à facilidade de manuseio do instrumento utilizado. Ensaios em laboratório
foram realizados para avaliação da metodologia e dos instrumentos de medição. A
partir da base de dados produzida, foi possível com emprego de técnicas de
processamento de sinais e estatística, observar o comportamento gaussiano dos
dados e o crescimento do valor médio da componente de 3ª harmônica da corrente
total em função do tempo de operação, evidenciando, assim, a correlação entre a
elevação da corrente de fuga e a diminuição da vida útil dos para-raios. / Nowadays the reliability and continuity in the electricity supply are increasingly
required. The surge arresters has an important function in this process, which is to
protect the other utility equipment against lightning and switching surges. When they
fail, usually causing the shutdown of transmission lines or transformers, severely
penalizing the power utility for the unavailability or regulator fines. As any important
equipment for the electrical system, surge arresters need effective monitoring
techniques. In the literature and industry several techniques, procedures or
equipment for their monitoring can be found. All procedures or devices have their
limitations, advantages and disadvantages, whether technical, economic or
operational. Aiming to overcome some of the limitations in existing techniques and
procedures commonly employed in the electrical industry, a methodology for
analyzing the surge arrester operational condition based on measurements of total
leakage current is proposed in this paper. With this methodology is intended to
minimize operational difficulties associated with monitoring activities, since it will only
measure the total leakage current unlike the usual techniques and procedures, which
require the measurement of the applied voltage, too. A database of leakage currents
with measurements performed in five (05) power substations was obtained.
Measurements were grouped by arresters model/manufacturer and operation time.
The measuring instrument used consists of a clamp type ammeter and a portable
digital oscilloscope. The process of field measurement was effective and practical
due to the ease of handling of the used instrument. Laboratory tests were performed
to evaluate the methodology and measuring instruments. From the database
produced, it was possible through the use of techniques of signal processing and
statistical observe the Gaussian behavior of the data and the average increase of the
3rd harmonic component of the total current as a function of operating time, which
highlights thus, the correlation between the increase of the leakage current and the
decrease of the lifetime of the surge arrester.
|
Page generated in 0.1012 seconds