Desempenho tÃcnico-financeiro de sistema hÃbrido eÃlico-solar aplicado ao bombeamento de Ãgua / Technical and financial performance of wind-solar hybrid system applied to water pumping

A presente dissertaÃÃo apresenta como objetivo principal a instalaÃÃo e avaliaÃÃo de desempenho tÃcnico-financeiro de um sistema hÃbrido eÃlico-fotovoltaico aplicado ao bombeamento de Ãgua. Adicionalmente, à proposta uma metodologia de dimensionamento de sistema hÃbrido de geraÃÃo baseado em fontes renovÃveis em funÃÃo do menor custo e do potencial disponÃvel. O sistema de geraÃÃo hÃbrido foi instalado na jusante do aÃude do Campus do Pici da Universidade Federal do Cearà (UFC), em Fortaleza/CE, Brasil. O sistema hÃbrido à composta por 01 aerogerador de 1 kW, 04 mÃdulos fotovoltaicos de 87 Wp, sistema de banco de baterias com 05 unidades de 150 Ah. O sistema de bombeamento à composto por um conjunto moto-bomba de 0,5 cv. A anÃlise tÃcnica foi efetuada mediante anÃlise dos dados (elÃtricos e nÃo elÃtricos) coletados atravÃs de sensores instalados a um sistema supervisÃrio. Os resultados indicam que a variaÃÃo do recurso eÃlico para o local à mais elevada, quando comparado ao recurso solar, e que a disponibilidade do potencial de ambos os recursos sÃo praticamente concomitantes ao longo do perÃodo diurno, caracterÃstica esta tambÃm observada no perÃodo analisado. O sistema de geraÃÃo com banco de baterias, operando tanto na configuraÃÃo hÃbrida ou individual, assegurou o fornecimento de eletricidade para o sistema de bombeamento no perÃodo de funcionamento da carga. A partir dos indicadores de eficiÃncia, verificou-se que as unidades de conversÃo apresentaram divergÃncia entre a geraÃÃo de eletricidade estimada e a mensurada, tendo a unidade eÃlica a qual apresentou maior divergÃncia. O custo da energia elÃtrica do sistema hÃbrido instalado (eÃlico-solar) com banco de baterias à de 0,86 R$/kWh. O dimensionamento do sistema de geraÃÃo indicou que a configuraÃÃo hÃbrida para o local nÃo se ajusta em virtude do elevado potencial solar disponÃvel e da baixa disponibilidade do recurso eÃlico no 1 trimestre do ano. O dimensionamento indicou que a configuraÃÃo hÃbrida foi a de menor custo (1,52 R$/kWh) quando dimensionada em funÃÃo dos recursos do mÃs de Outubro. Indicando assim que quando mais de uma fonte renovÃvel se destaca a configuraÃÃo hÃbrida pode ser sim uma alternativa viÃvel. / This work has as main objective the installation and technical
-
financial
evaluation of
a hybrid
wind
-
photovoltaic
system
applied to water
pumping
. In addition, a sizing methodology
is
proposed
based on renewable sources
considering low
cost and
available
potential. The hybrid
system
was installed in front of the Pici Campus
reservoir
of the Federal Univers
ity of CearÃ
(UFC) in Fortaleza
/CE, Brazil.
The hybrid system consists of 01 wind turbine of 1 kW, 04
photovoltaic modules of 87 Wp, a battery
bank with 05
units of 150 Ah.
The pumping system
con
sists of a motor
-
pump 0,
5 cv
.
Technical analysis was performed by analyzing the data
(electric and non
-
electric) collected by sensors to a supervisory
system.
The results indicate
that the wind resource variation for the
site
is higher, when compared to the solar resource,
and the availability
of
the potential of both resources are concomitant during the daytime
period, a characteristic also observed in the anal
yzed period.
T
he generation system with
battery bank, operating in
either the hybrid configuration or
individual, assured the supply of
electricity to the pumping system
during
operating time
.
From the indicators of efficiency, it
was found that the conver
sion units showed divergence between estimated
and measured
electricity generation, and wind unit which presented greater divergence.
The
electricity
cost
of
the hybrid system (wind
-
solar)
installed with battery bank is 0.86 R$/kWh.
The sizing
of
the generating system indicated
that the hybrid configuration at
the
site
does not fit due to the
high solar potential available and the low availability of wind resources in the 1
st
trimester
of
the year
.
The
sizing generation system indicated that th
e
hybrid configuration has the lowest
cost (1.52 R$/kWh) when sizing with the
resources of
October
month
.
Indicating thus
,
that
when more than one renewable source stands out
,
the hybrid configuration can be viable
alternative

Identiferoai:union.ndltd.org:IBICT/oai:www.teses.ufc.br:9924
Date05 August 2015
CreatorsMarcelo Ferreira de Arruda
ContributorsPaulo CÃsar Marques de Carvalho, Daniel Albiero, SÃrgio Daher, Francisco KlÃber de AraÃjo Lima
PublisherUniversidade Federal do CearÃ, Programa de PÃs-GraduaÃÃo em Engenharia ElÃtrica, UFC, BR
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Formatapplication/pdf
Sourcereponame:Biblioteca Digital de Teses e Dissertações da UFC, instname:Universidade Federal do Ceará, instacron:UFC
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0022 seconds