A study on low voltage ride-through capability improvement for doubly fed induction generator

Since large scale unscheduled tripping of wind power generation could lead to power system stability problem. Thus network interconnection regulations become more rigid when the wind power penetration reaches a non-neglible portion of the total power generation. This thesis presents a comparison of five different low voltage ride through (LVRT) capability enhancement technologies, i.e., additional rotor resistance, DC bus chopper, crowbar on rotor, the combination of above schemes, and grid voltage support by controlling grid side converter. System simulations are performed under Digsilent environment with model and control blocks provided by
the package. Additional models are developed to implement the LVRT enhancement schemes studied. A Doubly-Fed Induction Generator (DFIG) with pitch control is used to simulate different system fault scenarios with different voltage sag magnitude and duration time. Simulation results indicate that different enhancement schemes provide various levels in relieving DC bus overvoltage, rotor winding overcurrent, and overspeed problems, and the method combines all tested schemes seems to provide the best result.

Identiferoai:union.ndltd.org:NSYSU/oai:NSYSU:etd-0902110-102732
Date02 September 2010
CreatorsLin, Xiao-Chiu
ContributorsTzung-Lin Lee, Le-Ren Chang-Chien, Chih-Wen Liu, Chan-Nan Lu
PublisherNSYSU
Source SetsNSYSU Electronic Thesis and Dissertation Archive
LanguageCholon
Detected LanguageEnglish
Typetext
Formatapplication/pdf
Sourcehttp://etd.lib.nsysu.edu.tw/ETD-db/ETD-search/view_etd?URN=etd-0902110-102732
Rightsunrestricted, Copyright information available at source archive