Previous issue date: 2016-07-05 / Uma técnica auto-adaptativa que torna a obtenção dos ajustes de coordenação de relés de sobre corrente instantânea para sistemas de distribuição uma tarefa automática, sem a necessidade de intervenção humana e nem a interrupção do fornecimento de energia elétrica ou do monitoramento da rede é proposta. Usando uma arquitetura distribuída, formada por três camadas conectadas através de canal de comunicação, modificações topológicas como entrada/saída de linhas, e/ou nos perfis de carga e geração do sistema elétrico terão seus efeitos automaticamente refletidas nos ajustes dos dispositivos de proteção. O método proposto usa a corrente de carga
como item principal para a determinação dos ajustes das unidades instantâneas de sobre corrente em redes de distribuição de média tensão com e sem apresentação geração distribuída.
Por meio do cálculo online dos equivalentes de rede a técnica proposta necessita de baixos níveis de intervenção humana para a realização dos estudos de coordenação e seletividade. Os resultados obtidos comprovam a viabilidade técnica da metodologia proposta e corrobora com o estado da arte no tocante ao desenvolvimento das redes elétricas inteligentes. / A self-adaptive technique that improves the instantaneous overcurrent relay settings determination an automatic task, without human intervention neither interruption on electric supply or grid monitoring is proposed. An architecture designed by three layers connected using a communication channel provides that modificationon power electric grid as connection/disconnection of transmissionlines, and/or on generator or load profiles will be automatically reflected on protective device settings. Load current has been used to determine the reach of instantaneous over current relay settings in a médium voltage distribution system considering cases with and without distributed generation connected on the grid. The possibility of online determination at Thevenin equivalent circuit low human interventions to execute coordination study. Obtained results demonstrate the viability of proposed technique an dincrease with state of art a bout improvements of smart electric grids.
Identifer | oai:union.ndltd.org:IBICT/oai:localhost:riufcg/1417 |
Date | 13 August 2018 |
Creators | SOUZA JÚNIOR, Francisco das Chagas. |
Contributors | SOUZA, Benemar Alencar de., OLESKOVICZ, Mário., BRITO, Núbia Silva Dantas., MOTA, Wellington Santos., MEDEIROS JÚNIOR, Manoel Firmino de. |
Publisher | Universidade Federal de Campina Grande, PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA, UFCG, Brasil, Centro de Engenharia Elétrica e Informática - CEEI |
Source Sets | IBICT Brazilian ETDs |
Language | Portuguese |
Detected Language | Portuguese |
Type | info:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/doctoralThesis |
Source | reponame:Biblioteca de Teses e Dissertações da UFCG, instname:Universidade Federal de Campina Grande, instacron:UFCG |
Rights | info:eu-repo/semantics/openAccess |
Page generated in 0.0025 seconds