The purpose of this thesis is to validate generator models for dynamic studies of power systems using PSS/E (Power System Simulator for Engineering), EMTP (ElectroMagnetic Transient Program), and Hypersim. To thoroughly evaluate the behavior of a power system in the three specified software packages, it is necessary to have an accurate model for the power system, especially the generator which is of interest. The effect of generator modeling on system response under normal conditions and under faulted conditions is investigated in this work. A methodology based on sensitivity analysis of generator model parameters is proposed aiming to homogenize the behavior of the same power system that is modeled in three software packages. Standard IEEE 14-Bus system is used as a test case for this investigation. Necessary changes in the exciter parameters are made using the proposed methodology so that the system behaves identical across all three software platforms.
Identifer | oai:union.ndltd.org:uno.edu/oai:scholarworks.uno.edu:td-3321 |
Date | 13 May 2016 |
Creators | Munukuntla, Sowmya |
Publisher | ScholarWorks@UNO |
Source Sets | University of New Orleans |
Detected Language | English |
Type | text |
Format | application/pdf |
Source | University of New Orleans Theses and Dissertations |
Page generated in 0.0014 seconds