In this report a phase locked loop (PLL) system for grid voltage phase tracking has been investigated. The grid voltage phase angle contains critical information for connecting a power plant, such as a wave energy converter, to the grid. A synchronous reference frame PLL system with PI-regulator gains calculated with the symmetrical optimum method has been designed and simulations in SIMULINK have been made. For ideal grid conditions the phase angle was tracked fast and accurate. For non-ideal conditions the phase angle was tracked but with less accuracy, due to slow dynamics of the system, but still within acceptable margins. In order to test this system further it has to be implemented in a control system and tested when connected to the grid.
Identifer | oai:union.ndltd.org:UPSALLA1/oai:DiVA.org:uu-156145 |
Date | January 2010 |
Creators | Ögren, Jim |
Publisher | Uppsala universitet, Teknisk-naturvetenskapliga vetenskapsområdet |
Source Sets | DiVA Archive at Upsalla University |
Language | English |
Detected Language | English |
Type | Student thesis, info:eu-repo/semantics/bachelorThesis, text |
Format | application/pdf |
Rights | info:eu-repo/semantics/openAccess |
Relation | TVE ; 11 008 |
Page generated in 0.0011 seconds