Design and analysis of a system consisting of a variable-speed synchronous generator that supplies an active dc load (inverter) through a three-phase diode rectifier requires adequate modeling in both time and frequency domain. In particular, the system's control-loops, responsible for stability and proper impedance matching between generator and load, are difficult to design without an accurate small-signal model. A particularity of the described system is strong non-ideal operation of the diode rectifier, a consequence of the large value of generator's synchronous impedance. This non-ideal behavior influences both steady state and transient performance. This thesis presents a new, average model of the system. The average model accounts, in a detailed manner, for dynamics of generator and load, and for effects of the non-ideal operation of diode rectifier. The model is non-linear, but time continuous, and can be used for large- and small-signal analysis.
The developed model was verified on a 150 kW generator set with inverter output, whose dc-link voltage control-loop design was successfully carried out based on the average model. / Master of Science
Identifer | oai:union.ndltd.org:VTETD/oai:vtechworks.lib.vt.edu:10919/36549 |
Date | 25 March 1998 |
Creators | Jadric, Ivan |
Contributors | Electrical and Computer Engineering, Boroyevich, Dushan, Lindner, Douglas K., Lee, Fred C. |
Publisher | Virginia Tech |
Source Sets | Virginia Tech Theses and Dissertation |
Detected Language | English |
Type | Thesis |
Format | application/pdf |
Rights | In Copyright, http://rightsstatements.org/vocab/InC/1.0/ |
Relation | etdtext.pdf |
Page generated in 0.002 seconds