Trimming of a ground source heat pump system in Saltsjöbaden

The real performance of ground source heat pumps systems are not precisely highlighted in most cases, especially when it comes to installations older than the contractors guarantee period of 5 years. This project analyses measured data, constructs durability diagrams and establishes an energy balance of a whole heating system located in Saltsjöbaden. The system, composed of 3 heat pumps with a total heating power of 270kW and an oil burner, is used to deliver comfort heat through radiators and ventilation as well as tap warm water production. The installation was originally designed with two oil burners now used as an auxiliary heat supplier. Two heat pumps were installed in 1999 and a third unit was added in 2009. However, the oil consumption has been higher than expected. An experiment with controlled oil burner operation confirmed the need of implementing a control strategy. Some weaknesses in the system are pointed out.