Previous issue date: 2008-03-14 / CNPq / Neste trabalho é apresentada uma técnica de estimação de parâmetros para um modelo
dinâmico de pára-raios de óxido de zinco (ZnO). Esta técnica baseia-se no ajuste das
formas de onda da tensão residual fornecida pelo modelo de pára-raios de ZnO e aquela
medida em laboratório, para um impulso de corrente atmosférico (forma de onda 8/20 /xs)
de 10 kA. Os resultados fornecidos pelo modelo ajustado demonstraram boa concordância com os dados medidos. Avaliou-se também, o comportamento do modelo de pára-raios, com os parâmetros ajustados, diante impulsos de alta corrente (forma de onda 4/10 /us), os quais são transitórios mais severos do que aqueles utilizados para estimar os parâmetros do modelo. Os resultados obtidos neste estudo apresentaram boa precisão. Por fim, é apresentado um estudo comparativo dos resultados fornecidos pelo modelo de pára-raios, ajustado através da técnica de estimação de parâmetros, com aqueles fornecidos por modelos e procedimentos de ajuste comumente empregados na literatura. Os resultados fornecidos pela técnica de estimação proposta foram mais precisos que todos os demais, além de apresentar as vantagens de dispensar o conhecimento das características físicas dos pára-raios de ZnO e o uso de procedimentos manuais que visam o ajuste dos parâmetros do modelo através de tentativas e erros. / In this work is shown a parameter identification technique for a dynamic metal-oxide
surge arrester model. This technique was based on the fitting of the residual voltages
measured and obtained from the surge arrester model, from the 10 kA lighting current
impulse (waveshape 8/20 //s). The results obtained from the fitted surge arrester model
presented a very good accuracy. It was also evaluated, the behavior of the fitted arrester
model under high current impulse (waveshape 4/10 (is), which are most severe transients
than those used to estimate the arrester model parameters. The results obtained in
that study presented good agreement compared to the measured data. At last, it was
presented a comparative study of the results provided by the fitted surge arrester model
with those provided by models e adjust procedures usually made in the literature. The
results provided by the proposed parameter identification technique were more accuratc
than the results obtained from the other procedures. Besides, the technique has the
advantages of no need to know the metal oxide surge arresters physical characteristics
and no use manual procedures, based on try and error, to adjust the arrester model
parameters.

Identiferoai:union.ndltd.org:IBICT/oai:localhost:riufcg/1890
Date03 October 2018
CreatorsLIRA, George Rossany Soares de.
ContributorsCOSTA, Edson Guedes da., FERNANDES JÚNIOR, Damásio., NAIDU, Sreeramulu Raghuram., NEVES, Washington Luiz Araújo.
PublisherUniversidade Federal de Campina Grande, PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA, UFCG, Brasil, Centro de Engenharia Elétrica e Informática - CEEI
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Biblioteca de Teses e Dissertações da UFCG, instname:Universidade Federal de Campina Grande, instacron:UFCG
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0025 seconds