Includes bibliographical references. / Harmonic distortion of three phase power systems is caused by large amounts of electric power consumers using power electronic installations (e.g. drives and rectifiers). It has a number of undesirable consequences and has become an increasingly important problem with the rapid growth and ready availability of the power electronic devices and installations. A famous mathematical technique called "symmetrical components" was used to model the fundamental components of three phase systems. This method was extended to various harmonics. The aim of this thesis is to measure both the magnitude and phase angles of various harmonics which exist in three phase power systems, and to express them in symmetrical components. A digital electronics and microprocessor-based instrument was designed and constructed using the novel signal modulation technique called "+1 and -1" which was developed by the author of this thesis. This instrument was employed to achieve the above objectives.