[pt] ESTUDO EXPERIMENTAL DA INFLUÊNCIA DO COBRIMENTO NA INTERAÇÃO AÇO-CONCRETO EM ELEMENTOS SUJEITOS À COMPRESSÃO / [en] EXPERIMENTAL STUDY ON THE INFLUENCE OF CONCRETE COVER ON THE INTERACTION BETWEEN STEEL BARS AND CONCRETE IN ELEMENTS SUBJECTED TO COMPRESSION

[pt] O presente trabalho trata da influência do cobrimento da armadura longitudinal sobre a resistência de aderência em regiões de emenda por
traspasse de elementos de concreto armado comprimidos. Neste estudo foram ensaiados dezoito pilares de concreto armado com seção
transversal de 200 mm x 150 mm e comprimento de 1100 mm, com armadura longitudinal composta de barras de aço CA-50 com diâmetro nominal de 12,5 mm e estribos de 5 mm. O arranjo da armadura longitudinal definiu três séries de pilares, sendo a Série 1 composta por seis pilares com a armadura longitudinal contínua, e as Séries 2 e 3 cada uma composta por seis pilares com a armadura longitudinal, tendo uma emenda por traspasse localizada na região da metade da altura do pilar de 470 cm e 235 mm de comprimento, respectivamente.
Os ensaios consistiram na aplicação de uma força de compressão com uma excentricidade de 20 mm, sendo tal excentricidade aplicada apenas na direção da menor dimensão da seção transversal. Para os seis pilares de cada série o cobrimento da armadura longitudinal variou de 25 mm até que a metade do diâmetro da barra longitudinal ficasse exposta. Os resultados obtidos indicam que a influência
do cobrimento sobre a capacidade do pilar resistir às solicitações torna-se visível quando a relação da espessura do cobrimento c e do
diâmetro da barra fi é inferior a 0,4. Para pilares com barras emendadas por traspasse e com armadura exposta até a metade de seu diâmetro, a aderência na zona da emenda foi substancialmente afetada, provocando a ruptura do pilar sob forças inferiores às alcançadas em pilares com cobrimento adequado. / [en] The present work describes the influence of the concrete
cover of the
longitudinal reinforcement on the bond strength along the
overlapping splice
zones of compressed elements. Tests have been carried out
on eighteen
reinforced concrete columns, with cross section of 200 mm x
150 mm and 1100
mm of length. The longitudinal reinforcement consisted of
CA-50 steel bars with
nominal diameter of 12,5 mm and stirrups of 5 mm. Three
series of columns
(Serie 1, Serie 2 and Serie 3) were defined according to
the arrangements of the
longitudinal reinforcement: Series 1 composed by six
columns with continuous
longitudinal reinforcement; Series 2 and 3 composed by six
columns each,
presenting an overlapping splice of 470 mm and 235 mm of
lenght, respectively.
The columns were submited to a load apllied with an
eccentricity of 20 mm in the
direction of the smallest dimension of the cross section.
In each series, the
concrete cover varied from 25 mm to a value corresponding
to the situation in
which half of the diameter of the longitudinal bar was
exposed. The results
showed that the influence of the concrete cover on the
column strength becomes
relevant when the ratio c/ Ø of the cover thickness c to
the bar diameter Ø is less
than 0,4. For columns with overlapping splice and
reinforcement exposed up to
the half of diameter, the bond along the overlapping zone
has been substancially
affected, resulting in the column failure at lower loads
when compared to columns
with proper value of concrete cover.