University of Alberta
Detecting, Diagnosing and Explaining HVAC Faults: A Series of Case Studies
Abstract
dc:description.abstractBuildings consume a significant portion of global energy, with Heating, Ventilation, and Air Conditioning (HVAC) systems accounting for a large share of operational energy use and maintenance costs. Undetected faults in HVAC systems can lead to excessive energy consumption, occupant discomfort, and degraded indoor air quality. Automatic Fault Detection and Diagnosis (AFDD HVAC) has therefore emerged as a critical research area, particularly through data-driven approaches that leverage Building Management System (BMS) sensor data. This thesis presents a systematic, reproducible, and modular investigation of AFDD HVAC using a Luigi-based pipeline that automates preprocessing, feature engineering, model construction, evaluation, and interpretability. The experimental framework evaluates three representative model families widely validated and documented in AFDD HVAC literature: Random Forest (RF), Fully Connected Neural Networks (FCNN), and stacked Long Short-Term Memory (LSTM) networks. Experiments are conducted on publicly available HVAC datasets of increasing complexity: the MZVAV dataset containing a single injected fault type, the SDAHUlimited dataset with multiple fault types but a matched feature space, and the SDAHUfull dataset with richer sensor coverage. Our experimental results demonstrate that feature engineering and data-splitting strategies significantly influence AFDD HVAC performance across all model architectures. Baseline (imputation and standardization) with One-hot encoding of temporal variables consistently provides the most stable and dominant performance gains, yielding near-perfect accuracy, recall, and F1-scores under stratified splits and significantly improving robustness under time-series splits. Stratified splits tend to produce near-ceiling results due to distributional similarity between training and testing data, whereas time-series splits present a more realistic and challenging evaluation setting, exposing limitations in chronological prediction stability. When transferring the best-performing configurations from the single-fault MZVAV dataset to the multi-fault SDAHUlimited dataset, all three models exhibit strong generalization capability. Notably, detecting normal conditions improves substantially and false positives and false negatives decrease significantly under time-series evaluation. This finding indicates that datasets with diverse fault types and intensities provide clearer discriminative patterns than single-fault scenarios. Experiments with the SDAHUfull dataset reveal that extended sensor coverage produces minimal gains in binary fault detection, as core BAS variables such as temperature sensors, damper positions, and control signals are already sufficient for distinguishing faulty from unfaulted operation. However, additional sensors become more useful when combined with temporal history features in time-series split settings. For multiclass fault detection, the models achieve near-perfect performance under stratified splits but experience performance degradation under time-series splits, confirming the increased difficulty of chronological multiclass classification. Despite this challenge, the FCNN and RF models demonstrate the most stable performance among the evaluated architectures and remains competitive with prior benchmarks on the SDAHUfull dataset. To enhance interpretability, this thesis integrates SHAP-based explanations with a Brick-based model of the building HVAC system, enabling aggregation of feature attributions to sensors and components. This integration supports component-level fault localization by translating model predictions into physical HVAC components. Results show that component-level localization is most reliable for actuator faults with direct physical signatures (e.g., damper faults and cooling-coil leakage), while temperature sensor bias faults yield more distributed attributions consistent with closed-loop control responses. Overall, the proposed pipelines provides a reproducible foundation for benchmarking AFDD HVAC methods under both stratified and time-series evaluation.
Degree
thesis:*- Name thesis:degree_name
- Master of Science
- Level thesis:degree_level
- Master's
- Grantor
- University of Alberta
- Year dc:date.issued
- 2026
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Prodhan, Sadia Zahin
- Advisor dc:contributor.advisor
-
- Stroulia, Eleni (Computing Science)
Subjects
dc:subject × 6Rights
dc:rights- Statement dc:rights
-
- This thesis is made available by the University of Alberta Library with permission of the copyright owner solely for non-commercial purposes. This thesis, or any portion thereof, may not otherwise be copied or reproduced without the written consent of the copyright owner, except to the extent permitted by Canadian copyright law.
- Language dc:language.iso
- en
Identifiers
dc:identifier.*- DOI dc:identifier.doi
- https://doi.org/10.7939/84411