Back to search

University of Alberta

Developing a Methodology for Optimal Design of the Combined System of Pleated Air Filters and Heating Elements for Filter Disinfection

Abstract

dc:description.abstract

Improper design and operation of heating, ventilation, and air conditioning (HVAC) systems can contribute to the transmission of pathogenic microorganisms in indoor environments. While air filters are traditionally deployed to control airborne pathogens' virulence, they can accumulate microbes over time and become breeding grounds for bacteria and fungi. To address this challenge, this thesis proposes a novel energy-efficient air disinfection approach that combines air filtration with thermal inactivation by heat. To maintain continuous filtration during operation, the system incorporates two side-by-side filtration units with identical filters that operate in sequence. While one unit undergoes thermal disinfection within an insulated enclosure, the other remains in service. Three design concepts are developed and evaluated based on their mode of heat transfer and application strategy. The first concept is a fanless configuration that relies primarily on natural convection to disinfect a single-stage filter. The second concept employs forced convection using recirculating warm air to disinfect a single-stage filter. The third concept extends the warm-air-recirculation approach to two-stage filtration systems. An experimental test rig is constructed to monitor the heat transfer performance of each design and to quantify the time and energy required to achieve the literature-based inactivation condition of maintaining a filter temperature of 65 °C for 10 minutes. Furthermore, a closed-loop aerosol wind tunnel accommodating the prototype of the disinfection unit is constructed to evaluate the system's particle removal efficiency and pressure drop at different duct airflow rates. The setup follows the ASHRAE 52.2 general requirements for measuring filter efficiency. Computational Fluid Dynamics (CFD) simulations are first conducted to identify heating-element configurations that promote uniform temperature distribution within the enclosure. The 2D unsteady turbulent buoyancy-driven flow is simulated using Ansys Fluent 2023 R2. Five configurations are examined by varying the number of tubular heating elements, their spatial arrangement, and the enclosure geometry through the addition of a heating chamber. The numerical results indicate that incorporating a heating chamber beneath the frame and redistributing the heating elements to enhance preheating and mixing near the bottom of the enclosure significantly reduces temperature non-uniformity. Configurations demonstrating improved thermal uniformity are subsequently selected for experimental investigation with filters. Next, prototypes of the natural-convection-based system, including a pleated filter with a minimum efficiency reporting value (MERV) of 11 and tubular heating elements, are manufactured and experimentally evaluated. Three configurations are tested over a range of heater set-point temperatures. The results reveal that the optimal configuration substantially reduces thermal non-uniformity across the filter surface, enabling the entire filter to reach the literature-based thermal exposure condition within approximately 35 minutes, with an energy consumption of 0.10 kWh per cycle. Flow characterization tests further demonstrate that the modifications do not significantly affect filtration efficiency and results in only a minor increase in pressure drop during normal operation. To reduce the disinfection period, prototypes of a forced-convection-based system for disinfecting a single-stage MERV 11 filter are developed. The impacts of warm inlet temperature and air recirculation rate within the disinfection units on the heat transfer performance of the system are experimentally investigated. The results show that under optimal operating conditions, the filter reached disinfection condition within 13 minutes, with a total energy consumption of 0.11 kWh per cycle. During normal operation, when both units remain open, the system maintains filtration efficiency equivalent to that of a standalone filter, with a negligible increase in pressure drop. During the disinfection period, when one unit is isolated, the submicron particle removal efficiency decreases, while large-particle removal increases, and the pressure drop rises significantly for only a short period, resulting in a minimal impact on the overall HVAC fan energy use. Finally, the forced convection system is used for two-stage filtration systems, comprising a MERV 8 pre-filter and either a MERV 11 or a MERV 13 main filter. The heat transfer and filtration performance of the system are evaluated experimentally at three inter-filter distances. The results indicate that changing the inter-filter distance has relatively minor impacts on the overall filtration efficiency and pressure drop compared to its effect on the disinfection process. Consequently, the energy performance of the disinfection system should be considered the primary criterion when determining the optimal distance between the pre-filter and the main filter.

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy
Level thesis:degree_level
Doctoral
Grantor
University of Alberta
Year dc:date.issued
2026

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Mirzazade Akbarpoor, Ali
Advisors dc:contributor.advisor
  • Alireza Nouri (Civil and Environmental Engineering Dept)
  • Mahdi Shahbakhti (Mechanical Engineering)

Subjects

dc:subject × 8

Rights

dc:rights
Statement dc:rights
  • This thesis is made available by the University of Alberta Library with permission of the copyright owner solely for non-commercial purposes. This thesis, or any portion thereof, may not otherwise be copied or reproduced without the written consent of the copyright owner, except to the extent permitted by Canadian copyright law.
Language dc:language.iso
en

Identifiers

dc:identifier.*
DOI dc:identifier.doi
https://doi.org/10.7939/86196

Chain of custody

source
Harvested from
University of Alberta
Base URL
era.library.ualberta.ca/oai
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
citation

Mirzazade Akbarpoor, Ali. Developing a Methodology for Optimal Design of the Combined System of Pleated Air Filters and Heating Elements for Filter Disinfection. Doctoral thesis, University of Alberta, 2026. https://doi.org/10.7939/86196