Baylor University.
Characterization of fan coils units with electrically commutated motors.
Abstract
dc:description.abstractThe data from five manufacturers were obtained for the purpose of developing of a method for generalizing fan coil units (FCUs) with electronically commutated motors (ECMs. In addition, the University of Louisiana at Lafayette (ULL) provided data for 40 more units. Three methods were tested for levels of variation in results and consistency between various types of ECM FCUs. First, units were analyzed by their fan efficacy: The Fan Efficacy Method, the Constant ESP method, and finally, the System ESP method. The success of the constant ESP method proved overall indifferent to variations between different ECM FCUs such as ESP, horizontal versus vertical, manufacturer, setting, and motor size. This model was capable of producing airflow and power versus ESP curves at a given setting, using only the design airflow and ESP.
Degree
thesis:*- Name thesis:degree_name
- M.S.M.E.
- Level thesis:degree_level
- Masters
- Department thesis:degree_department
- Dept. of Mechanical Engineering.
- Grantor
- Baylor University.
- Year dc:date.issued
- 2019
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Cramer, Jessica, 1993-
- Advisor dc:contributor.advisor
-
- O'Neal, Dennis.
Subjects
dc:subject × 6Rights
dc:rights.accessrights- Statement dc:rights.accessrights
-
- Worldwide access
- Baylor University works are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. Contact libraryquestions@baylor.edu for inquiries about permission.
- Language dc:language.iso
- en
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- https://hdl.handle.net/2104/10782