A Model for Analyzing Heating and Cooling Demand for Atria Between Tall Buildings
Abstract
dc:description.abstractThe heating and air-conditioning energy demand of skyscrapers with atria between buildings is explored. Radiation, conduction, convection, and ventilation were evaluated to determine annual heating and cooling energy demands for a 100-building city located in Provo, Utah. Spreadsheets models were developed and calibrated with a computational fluid dynamics model. Three spreadsheet model cases were examined: a baseline no-atrium case, a conditioned atrium case, and an unconditioned atrium case. The energy demands and atrium temperatures were compared between the different cases. The research concludes that atria can be used between buildings to reduce the heating and cooling energy demands. The exposed surface area of the city was reduced by 73.7%. This resulted in a 49.7% reduction in heating and cooling energy consumption for the unconditioned atrium case and a 16.0% reduction in energy consumption for the conditioned atrium case.
Degree
thesis:*- Name thesis:degree_name
- MS
- Grantor dc:publisher
- Brigham Young University - Provo
- Year dc:date
- 2014
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Christensen, Samuel David
Subjects
dc:subject × 6Rights
- Licence dc:rights.license
- Language dc:language
- English
Identifiers
dc:identifier.*- Repository record dc:identifier
- https://scholarsarchive.byu.edu/etd/4211