Back to search

Environmental Design

Occupant Satisfaction with Underfloor Air Distribution Systems in a Cold Climate: A Field Study

Abstract

dc:description.abstract

The demand to reduce GHG emissions and corporate rethinking of interior environments has encouraged the use of underfloor air distribution systems (UFAD). This relatively new space conditioning system is believed to provide benefits of better energy performance, improved indoor air quality, workplace flexibility, higher levels of occupant comfort and personal control. However most of the research on this technology and its relation to occupant comfort has been limited to laboratory settings and use of Fanger’s heat balance model to determine whether the system provides acceptable thermal comfort. The later fails to confirm that the conditions provided by UFAD are satisfactory to occupants in-situ. This field study of the City of Calgary’s Water Center examined UFAD in terms of occupant comfort in a cold climate. Both physical measurements and occupant response was collected. Overall the findings were very positive. Occupant responses indicated participants were generally satisfied with their comfort level and indoor air temperature. The median PMV value also indicated that the thermal conditions were within the acceptable range.

Degree

thesis:*
Name thesis:degree_name
Master of Environmental Design (MEDes)
Grantor dc:publisher.institution
Environmental Design
Year dc:date.issued
2013

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Bos, Megan
Advisor dc:contributor.advisor
  • Love, James

Subjects

dc:subject × 4

Rights

dc:rights
Statement dc:rights
  • University of Calgary graduate students retain copyright ownership and moral rights for their thesis. You may use this material in any way that is permitted by the Copyright Act or through licensing that has been assigned to the document. For uses that are not allowable under copyright legislation or licensing, you are required to seek permission.
Language dc:language.iso
eng

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
University of Calgary
Base URL
ucalgary.scholaris.ca/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Bos, Megan. Occupant Satisfaction with Underfloor Air Distribution Systems in a Cold Climate: A Field Study. Environmental Design, 2013. http://hdl.handle.net/11023/610