Abstract
dc:description.abstractThis thesis presents the experimental testing results of a novel triple-state sorption chiller with integrated cold storage. The performance of the chiller was measured for hot water inlet temperatures between 65°C and 95°C, heat rejection inlet temperatures between 15°C and 35°C, and chilled water inlet temperatures between 10°C and 25°C. The performance data collected during these tests were then used to develop a Microsoft Excel-based model for implementation in the TRNSYS simulation software. The output of the model was then compared to the results of a five hour experimental charge test in which the inlet temperatures were varied throughout the experiment, resulting in a 0.7% error in the heat input energy and a 1.3% error in the heat rejection energy.
Degree
thesis:*- Name thesis:degree_name
- Master of Applied Science (M.App.Sc.)
- Level thesis:degree_level
- Master's
- Discipline thesis:degree_discipline
- Engineering, Sustainable Energy
- Grantor dc:publisher
- Carleton University
- Year dc:date.issued
- 2016
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Bowie, Daniel
Subjects
dc:subject × 2Rights
dc:rights- Statement dc:rights
-
- Copyright © 2016 the author(s). Theses may be used for non-commercial research, educational, or related academic purposes only. Such uses include personal study, research, scholarship, and teaching. Theses may only be shared by linking to Carleton University Institutional Repository and no part may be used without proper attribution to the author. No part may be used for commercial purposes directly or indirectly via a for-profit platform; no adaptation or derivative works are permitted without consent from the copyright owner.
- Language dc:language.iso
- en