Fault Detection and Diagnostics in Single-Duct Multiple-Zone Variable Air Volume Air Handling Unit Systems
Abstract
dc:description.abstractVariable air volume (VAV) air handling unit (AHU) systems are the most common heating, ventilation, and air conditioning (HVAC) configuration in North America's commercial buildings. They account for a large fraction of sensors and actuators and are prone to faults due to their control systems' complexity. This research fills the gap in VAV AHU fault detection and diagnostics (FDD) through four parts. First, inverse model-based virtual sensors are developed to detect actuator faults in AHUs. Three algorithms are explored to compensate for the lack of reliable intermediate sensor data for five AHUs. Results indicate that although generated models can act as virtual sensors to identify hard faults, they cannot isolate faults' root causes. To address this uncertainty, the second part introduces a holistic sequential hierarchical FDD framework considering the significance of zone-to-system hard and sequencing logic fault interactions in AHUs and VAVs. The proposed framework follows this fault-checking order: AHU hard faults, VAV hard faults, AHU sequencing logic faults, and VAV sequencing logic faults. Faults are detected by visualizing the discrepancies between the expected and measured operational behaviour. The third part focuses on VAV AHU control systems (sensors, actuators, and sequencing logic), studying human errors during design, installation, and operation. Human errors are identified through a literature review and interviews with control specialists. The most common errors are classified, and interview examples are listed for different building life cycle phases. Since a commonly reported error by interviewees is thermostat misplacement, resulting in negative impacts on AHU supply air temperature (SAT) setpoint, the last step of this research investigates the robustness of sequences of operation to such errors. Fault tolerance of the most vulnerable sequences: SAT setpoint, duct static pressure (DSP) setpoint and mode of operation (MOP) to zone-level faults is studied. Customized sequences are defined in EnergyPlus, and common actuator/sensor faults are injected to determine the most efficient fault-tolerant scenario. Results indicate that the ASHRAE Guideline 36 trim and respond reset logic capable of eliminating rogue zones is the most fault-tolerant scenario for SAT and DSP setpoints. Moreover, an average temperature-based control scenario for MOP significantly reduces HVAC energy use.
Degree
thesis:*- Name thesis:degree_name
- Doctor of Philosophy (Ph.D.)
- Level thesis:degree_level
- Doctoral
- Discipline thesis:degree_discipline
- Engineering, Building
- Grantor dc:publisher
- Carleton University
- Year dc:date.issued
- 2023
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Torabi, Narges
Subjects
dc:subject × 3Rights
dc:rights- Statement dc:rights
-
- Copyright © 2023 the author(s). Theses may be used for non-commercial research, educational, or related academic purposes only. Such uses include personal study, distribution to students, research and scholarship. Theses may only be shared by linking to the Carleton University Institutional Repository and no part may be copied without proper attribution to the author; no part may be used for commercial purposes directly or indirectly via a for-profit platform; no adaptation or derivative works are permitted without consent from the copyright owner.
- Language dc:language.iso
- en