Carleton University
The Design and Experimental Analysis of an Air Source Heat Pump for Extreme Cold Weather Operation
Abstract
dc:description.abstractThis research evaluates one method of increasing the performance of an air sourced heat pump to extend its operating range and eliminate the need for a backup heating system. A study was conducted using the Engineering Equation Solver software package to identify the performance improvements that are attainable with variations of a two stage heat pump cycle. An experimental apparatus was constructed to compare the performance of the best performing variation - a two stage economized cycle - to that of a traditional single stage heat pump. The two stage economized heat pump had a measured coefficient of performance of 1.45 when it was operated at an outdoor temperature of -31C making it an energy efficient option for most Canadian climates. In addition, the heating capacity of the system was increased by a factor of 2.5 when compared to the single stage system.
Degree
thesis:*- Name thesis:degree_name
- Master of Applied Science (M.App.Sc.)
- Level thesis:degree_level
- Master's
- Discipline thesis:degree_discipline
- Engineering, Mechanical
- Grantor dc:publisher
- Carleton University
- Year dc:date.issued
- 2016
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Mackintosh, Tom
Subjects
dc:subject × 3Rights
dc:rights- Statement dc:rights
-
- Copyright © 2016 the author(s). Theses may be used for non-commercial research, educational, or related academic purposes only. Such uses include personal study, research, scholarship, and teaching. Theses may only be shared by linking to Carleton University Institutional Repository and no part may be used without proper attribution to the author. No part may be used for commercial purposes directly or indirectly via a for-profit platform; no adaptation or derivative works are permitted without consent from the copyright owner.
- Language dc:language.iso
- en