Back to search

Chalmers University of Technology

Environmental and economic investigation of telecom site back-up power systems

Abstract

dc:description.abstract

Diesel generators and lead-acid batteries are currently used as telecom site back-up power in areas where the local electricity grid is not always available. Fuel cell systems are an interesting alternative. In this study, environmental and economic aspects of the following five power back-up systems have been investigated: a diesel generator system, a lead-acid battery system, a fuel cell system with H2 from steel bottles (produced from central electrolysis), a fuel cell system with on-site electrolysis, and a fuel cell system with on-site reforming of methanol. Calculations have been performed for different combinations of power demands (1.5 kW, 3 kW, 5 kW, 8 kW) and electricity grid availabilities (99.9%, 99%, 95%, 90%, 75%). The fuel/electricity use is an important factor in the environmental investigation. Based on the four chosen impact categories (abiotic depletion potential, acidification potential, eutrophication potential, and global warming potential), the battery system and the fuel cell system with a reformer have lower potential environmental impact than the diesel system. The two fuel cell systems with H2 from electrolysis could have better environmental performance than the diesel system if the electricity is based on a significant share of renewable energy. However, it is important to remember that the choice of weighting factors has a significant impact on the ranking of the different power systems. The battery system is the cheapest for most of the combinations of power demand and grid availability, especially when there is no need for a change of batteries. Fuel cell systems with H2 bottles or reformer can be a cost-competitive option for smaller power demands and grid availabilities down to 95%, if the site conditions are inappropriate for battery systems and if the investment cost for the fuel cells is lowered. It is suggested that calculations should be performed for a variety of site locations, in order to eliminate some of the uncertainties in the estimates and to be able to identify sites were fuel cell systems can be used. A study capturing a bigger variety in battery configurations should also be executed.

Degree

thesis:*
Level thesis:degree_level
H
Department dc:contributor.department
Chalmers tekniska högskola / Institutionen för energi och miljö
Year dc:date.issued
2010

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Erström, Caroline

Subjects

dc:subject × 8

Rights

Language dc:language.iso
eng

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
Chalmers University of Technology
Base URL
odr.chalmers.se/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Erström, Caroline. Environmental and economic investigation of telecom site back-up power systems. H thesis, 2010. https://hdl.handle.net/20.500.12380/136346