Back to search

Chalmers University of Technology

Risker för föroreningsspridning i lokaler med krav på renhet. Kartläggning och analys av ventilationssystems inverkan

Abstract

dc:description.abstract

This master thesis studies the design and function of HVAC-systems in hospital wards concerning the risk of pollutant spreading. From a survey of an existing hospital building the study aims to identify risks for this spreading and illustrate the connection between pressure differences and directional airflow. An operating room and its direct surroundings have been studied closer. A clean indoor environment in hospitals is of great importance. Health care activities generate pollutants that can affect humans negatively and nosocomial infections are common among hospital treated patients. HVAC-systems design and function, together with hospital routines and the building design play important parts in the prevention of pollutant spreading. Differences in air pressure are the driving force for airflow. Pressure relationships between rooms are mainly created by HVAC-systems and by balancing the airflow to and from a room a positive or negative pressure relationship to adjoining rooms can be created. By this control of supply and exhaust air one can also control the direction of airflow between adjacent rooms. Airflow in ducts to operating rooms and pressure relationships between rooms in a hospital ward have been measured. Tests to investigate the airflow through openings in a closed door at various pressure differences have been performed. The test doors represent the real doors to operating rooms in the existing hospital.

Degree

thesis:*
Level thesis:degree_level
H
Department dc:contributor.department
Chalmers tekniska högskola / Institutionen för energi och miljö
Year dc:date.issued
2006

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Martin, Carl

Subjects

dc:subject × 2

Rights

Language dc:language.iso
swe

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
Chalmers University of Technology
Base URL
odr.chalmers.se/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Martin, Carl. Risker för föroreningsspridning i lokaler med krav på renhet. Kartläggning och analys av ventilationssystems inverkan. H thesis, 2006. https://hdl.handle.net/20.500.12380/25602