dc:description.abstractThe purpose of this thesis is to experimentally determine the feasibility of an ejector based, waste heat recovery driven refrigeration system applied to the data center environment in order to reduce operational cooling costs. A comprehensive literature review is detailed to determine the current state of the ejector refrigeration research and assess the initial direction of this thesis. A simplified model was created to perform preliminary performance estimations and system sizing before constructing an experimental system apparatus to evaluate the model predictions. The pressures and temperatures used in the model and instituted in the experimental system are based on the maximum temperatures typically observed in computing servers (50-75°C). Precision controlled heaters are used to simulate the computer server heat, and R245fa is used as the working fluid. Performance results ranged from 0.06 to 0.13.
Degree
thesis:*- Department dc:contributor.department
- Mechanical Engineering
- Grantor dc:publisher
- Georgia Institute of Technology
- Year dc:date.issued
- 2011
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Sharp, Joshua Glenn
- Advisor dc:contributor.advisor
-
- Joshi, Yogendra
- Committee members dc:contributor.committeemember
-
- Mostafa Ghiaasiaan
- Pramod Kumar
- Sheldon Jeter
Subjects
dc:subject × 6Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/1853/41060