Back to search

Georgia Institute of Technology

Impact of increasing amounts of distributed generation on transient behavior of the distribution system

Abstract

dc:description.abstract

To investigate the impact of increasing penetration levels of PV in a distribution feeder under different environmental conditions was proposed in this research. A NEETRAC member Feeder was imported from OpenDSS into the DIgSILENT PowerFactory software, and its voltage transient stability was investigated under different environmental conditions. ANSI 105% voltage threshold violations were observed in the feeder when all PV inverters were controlled in Unity Power Factor mode. To mitigate this violation, a Volt-Var control mode with ± 2 % deadband, 0.95 pu lower limit, and 1.05 pu upper limit was used. This control scheme mitigated the ANSI 105% voltage violations on NEETRAC member Feeder during different environmental conditions. The IEEE 13 Node Test Feeder was modeled in Matlab/Simulink software. PV systems with a total penetration level of 120 % were installed at different nodes of the feeder, and frequency transient stability of the system was investigated. It was observed that higher penetration of PVs in the feeder adversely affect the frequency stability of the system during sudden load changes. To mitigate this frequency instability, a battery management system with modified Frequency-Watt function was developed and installed at the substation of the feeder. This battery management system emulated inertia and provided the necessary real power to stabilize the frequency of the system.

Degree

thesis:*
Level thesis:degree_level
Doctoral
Department dc:contributor.department
Electrical and Computer Engineering
Grantor dc:publisher
Georgia Institute of Technology
Year dc:date.issued
2017

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Regassa, Raeey A.
Advisor dc:contributor.advisor
  • Saeedifard, Maryam
Committee members dc:contributor.committeemember
  • Harley, Ronald G.
  • Habetler, Thomas G.
  • Graber, Lukas
  • Mayor, Rhett

Subjects

dc:subject × 6

Rights

Language dc:language.iso
en_US

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1853/58283

Chain of custody

source
Harvested from
Georgia Tech
Base URL
repository.gatech.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Regassa, Raeey A.. Impact of increasing amounts of distributed generation on transient behavior of the distribution system. Doctoral thesis, Georgia Institute of Technology, 2017. http://hdl.handle.net/1853/58283