Abstract
dc:description.abstractAir-cooled condensers (ACCs) offer an alternative heat rejection method for thermal power plants, reducing the required water withdrawal for conventional wet-cooled plants. However, ACCs suffer from lower efficiencies and higher capital costs compared to once-through and evaporative condensers. A heat exchanger representative of ACC geometry was manufactured and tested in a wind tunnel to quantify the thermal-hydraulic performance of an ACC at representative operating conditions. Autonomously fluttering reeds (AFRs) are installed on the air-side of these condensers and their performance is measured. The experiments showed an average of 25% enhancement in heat transfer coefficient, with a 40% increase in pressure drop due to the installation of the AFRs. The data were incorporated into a Rankine cycle power plant model, which predicted a ~0.4% cycle efficiency increase based on tradeoffs between increased fan power and lower turbine outlet pressure due to AFR enhancement.
Degree
thesis:*- Level thesis:degree_level
- Masters
- Department dc:contributor.department
- Mechanical Engineering
- Grantor dc:publisher
- Georgia Institute of Technology
- Year dc:date.issued
- 2017
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Kunke, Taylor Steven
- Advisor dc:contributor.advisor
-
- Garimella, Srinivas
- Committee members dc:contributor.committeemember
-
- Loutzenhiser, Peter
- Jeter, Sheldon
Subjects
dc:subject × 6Rights
- Language dc:language.iso
- en_US
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/1853/59184