Διερεύνηση του φαινομένου της εκκένωσης κορώνα σε γραμμές μεταφοράς
Abstract
dc:descriptionThe salient characteristics of corona discharge on overhead transmission lines have been investigated. This was achieved with the aid of corona inception models that were developed based on the physical processes involved in electrical discharges and take into account the form of corona discharge (glow or streamer). Thus, insight into the corona inception mechanism, as influenced by the geometric field distribution around the stressed electrode, form and polarity of the applied voltage and atmospheric conditions, has been gained. The estimated corona inception characteristics have been assessed and discussed through comparisons with literature experimental data and also validated against results obtained through scale model experiments by using the coaxial cylindrical electrode arrangement. Approximate expressions for the estimation of the corona inception field strength under steady or slowly varying electric fields have been proposed, which account accurately for the effects of voltage polarity, conductor radius and atmospheric conditions. An empirical expression has been proposed for the irregularity factor of stranded conductors, accounting well for the effects of conductor geometry and relative air density. Corona inception voltage of bundle conductors can be satisfactorily estimated by using the maximum value of the geometric field strength on the surface of the bundle conductors and the corona inception field strength of a single conductor of the same radius. Under DC voltages higher than the threshold value required for corona inception, corona current, thus also the associated power losses, can be well estimated through an approximate expression that considers the amplitude and polarity of the applied voltage, conductor geometry, outer cylinder radius and relative air density. The developed corona inception models can be used for the assessment of the characteristics of corona discharge on overhead transmission lines; this was shown for typical 150 kV overhead lines of the Hellenic transmission system. Under slowly varying overvoltages and standard atmospheric conditions, the corona inception voltage was found about 60% higher than the maximum value of the phase-to-ground voltage of the transmission lines. The irregularity factors of the line conductors can be estimated on the safe side by using the empirical expression derived based on scale model experiments. Corona inception voltages higher than that estimated under slowly varying overvoltages can be obtained under fast-front overvoltage surges with steepness higher than a threshold value; the latter, as also the rate of increase of corona inception voltage with overvoltage steepness, depends mainly on the conductor radius. This dependence of the corona inception voltage on the steepness of the overvoltage waveform must be considered in insulation coordination studies, where the attenuation and distortion of overvoltage surges propagating along overhead transmission lines due to corona effects is concerned.
Degree
thesis:*- Grantor dc:publisher
- Aristotle University Of Thessaloniki (AUTH)
- Year dc:date
- 2014
Author and committee
dc:creator, dc:contributor.*- Authors dc:creator
-
- Zagkanas, Vasileios
- Ζαγκανάς, Βασίλειος
Subjects
dc:subject × 12- Εκκένωση κορώνα
- Εναέριες γραμμές μεταφοράς
- Ηλεκτρικές εκκενώσεις
- Υψηλές τάσεις
- Corona discharge
- Overhead transmission lines
- Electrical discharges
- High voltage
- Επιστήμες Μηχανικού και Τεχνολογία
- Επιστήμη Ηλεκτρολόγου Μηχανικού, Ηλεκτρονικού Μηχανικού, Μηχανικού Η/Υ
- Engineering and Technology
- Electrical Engineering, Electronic Engineering, Information Engineering
Rights
- Language dc:language
- gre
Identifiers
dc:identifier.*- Identifier
- 10.12681/eadd/39717