Abstract

dc:description

This thesis copes with thermal phenomena occurring in distribution lines, medium and low voltage, as well as low voltage lines within residential areas, in relation to the occurrence of fire. Chapter 1 provides an introduction to the great problem of wildland fires and indoor fires, as well as the relationships that govern their transmission. Also, reference is made to the relationships that calculate the temperature increase in conductors, in case of overcurrent or short circuit. In Chapter 2 the purpose of this thesis is analyzed. In Chapter 3, the electric arc and short circuit in the medium and low voltage distribution lines of the Hellenic Electricity Distribution Network are analyzed. Chapter 4 examines the creation of copper molten particles, their fall to the ground, and their temperatures during their fall and during their contact with the ground. Next, the possibility of starting a fire on a wooden floor (plywood) due to its contact with the beads under study is examined. Chapter 5 gives the conclusions of the calculations for the aluminum conductors of the distribution network and the copper conductors of the internal electrical installations. Finally, Chapter 6 refers to the contribution of the work to research and practical applications. The research showed that during the short circuit between medium and low voltage distribution conductors no beads are created, because the resulting temperatures are very low. Within inhabited areas and mainly factories, where the height can be approximately 15-20 meters, beads of 0.5, 1, 2 or even 3 mm in diameter can be created, which under certain conditions can cause a fire if they come into contact with suitable material. The following two Appendices facilitate the reader's understanding of basic concepts mentioned in the text, but they are an independent scientific field, but necessary, such as the ionization of atmospheric air (Appendix I) and heat transfer phenomena (Appendix II).

Degree

thesis:*
Grantor dc:publisher
National Technical University of Athens (NTUA)
Year dc:date
2024

Author and committee

dc:creator, dc:contributor.*
Authors dc:creator
  • Mouzakitis, Panagiotis
  • Μουζακίτης, Παναγιώτης

Subjects

dc:subject × 16

Rights

Language dc:language
gre

Identifiers

dc:identifier.*
Identifier
10.12681/eadd/56733

Chain of custody

source
Harvested from
Greek National Archive of PhD Theses
Base URL
phdtheses.ekt.gr/eadd_oai/request
Last updated
2026-11-18
Source record
OAI-PMH GetRecord
citation

Mouzakitis, Panagiotis; Μουζακίτης, Παναγιώτης. Διερεύνηση λειωμένου αγωγού διανομής ηλεκτρικής ενέργειας ή εσωτερικής ηλεκτρικής εγκατάστασης κτηρίου σε περιβάλλον πυρκαγιάς, ως προς το ενδεχόμενο να είναι θύμα ή θύτης αυτής. National Technical University of Athens (NTUA), 2024. http://hdl.handle.net/10442/hedi/56733