National Technical University of Athens (NTUA)
Development and experimental investigation of innovative fully automated reversible heat pump/organic Rankine cycle systems for trigeneration and energy storage
Abstract
dc:descriptionThe increasing penetration of renewable power generation into the global energy mix, coupled with the significant demand for heating (both space heating and domestic hot water) and cooling, necessitates the electrification of the heating and cooling sectors alongside advancements in electricity storage solutions. Concurrently, the rising electricity demand gives prominence to decentralized power production for electricity self-consumption. Within the framework of heat pumps emerging adoption, reversible heat pump/ORC (RHP/ORC) systems constitute a promising technology to address these objectives, as both thermal (heating or cooling) and electrical power can be provided by a single system. In energy storage applications, the RHP/ORC system utilizes excess renewable electricity to generate and store high-temperature heat through heat pump operation. During peak electricity demand periods, this stored heat is discharged via ORC operation, facilitating peak shaving services. Regarding trigeneration, the system functions as a heat pump for heating or cooling provision when thermal demand exists, while low-grade heat (below 120 °C) can be converted into electricity when power is requested. Despite the theoretical advantages highlighted in literature, experimental research is scarce, particularly in energy storage. Moreover, reported RHP/ORC systems are mainly experimental and therefore employ basic automation and control. In this perspective, the present thesis investigates the development of innovative, fully automated reversible heat pump/organic Rankine cycle systems for energy storage and trigeneration applications. The first part of the thesis (Chapter 2) centers on the experimental characterization of the first known proof of concept of RHP/ORC for electricity storage. The 2 kWe/10 kWhth prototype was designed and built by the Thermodynamics Laboratory of the University of Liège, Belgium. The system underwent testing in both charging and discharging modes, exploring the effect of low-grade heat integration across a wide range of operating conditions. The experimental evaluation confirmed the feasibility of thermally integrated RHP/ORC technology for pumped thermal energy storage, achieving a power-to-power efficiency of 70.9%, thanks to thermal integration, which enabled high efficiency in heat pump mode, reaching a maximum coefficient of performance (COP) of 14.2 at a temperature lift of 8 K. The second part of the thesis focuses on the development of fully automated RHP/ORC trigeneration systems for integration with multiple heat sources and heat sinks, including an adsorption chiller for improved cooling performance. The initial step towards this direction involves the development of a small-scale vapor compression chiller utilizing the environmentally friendly refrigerant R1234ze(E) to validate the suitability of the selected refrigerant for low-capacity cooling outputs and demonstrate the feasibility of cascade coupling with an adsorption chiller (Chapter 3). The chiller was tested under different heat sink conditions, simulating both cascade and stand-alone chiller operation. Overall, the system exhibited stable performance, successfully mitigating fluctuations associated with the adsorption chiller, and achieved a maximum energy efficiency ratio (EER) of 5.9. After verifying the validity of cascade chiller operation, two fully automated small-scale (5 kWth/1 kWe) RHP/ORC trigeneration prototypes were designed and constructed. Chapter 4 introduces the system’s design specifications and emphasizes the design process and automation and control features. Subsequently, laboratory tests were conducted to characterize the system in all operating modes, including stand-alone heat pump, cascade chiller and ORC modes (Chapter 5). Maximum heating and cooling outputs of 6.6 kW and 5.5 kW were recorded, with respective COP and EER values of 5.1 and 4.5, while adsorption chiller integration enhanced EER to 5.5 under moderate heat sink temperatures. In ORC mode, net electrical ORC efficiencies up to 2.65% were attained. A dedicated analysis highlighted the importance of induction motor sizing for efficient compressor and expander operation in all modes, whereas a cavitation assessment revealed a correlation between cavitation and subcooling degree, specifying a lower subcooling threshold of 5 K for stable pump operation. Fully automated RHP/ORC operation necessitates proper switching between all operating modes. However, the different refrigerant charge required in each case poses a major challenge. This issue is addressed in Chapter 6 with the development of a novel, automated active charge regulation system that dynamically controls system’s refrigerant charge based on a dedicated charge control strategy. This configuration was embedded into the RHP/ORC prototypes, and experimental investigation of the integrated system demonstrated its effectiveness in facilitating smooth mode transitions and stable system operation. The comprehensive investigation of the RHP/ORC prototypes entails field testing within an extended renewables-based trigeneration system. In this context, an automated pilot system integrating multiple renewable thermal systems such as evacuated tube solar collectors, a biomass boiler, and an adsorption chiller was developed, along with a low energy demand pilot building where heating, cooling, and electricity are provided. Chapter 7 presents the design and structure of the overall system and details the automation architecture and control strategy. The complete system was evaluated over a four-month timeframe and the key operating modes are discussed in Chapter 8. The global system successfully met its design specifications, covering all thermal demands. The experimental evaluation showcased the seamless integration and operation of all subsystems under the supervisory controller. Focusing on the RHP/ORC, sufficient performance was achieved with a seasonal COP (SCOP) and seasonal EER (SEER) of 3.23 and 2.98, respectively, while cascade chiller operation exhibited limited benefits under high ambient temperatures. Finally, Chapter 9 presents simulations of a scaled-up global system for multi-family buildings across five European cities, using calibrated models based on laboratory and field test data. The simulation outcomes include the optimal system sizing in each case and highlight its potential, achieving total energy coverage of up to 72.1% in locations with high heating demands and low cooling needs. However, despite its advantages, the system's electricity generation is limited due to the prioritization of thermal demands, indicating the need for alternative layouts and control strategies for its further uptake. In summary, this research provides a comprehensive, experimental overview of RHP/ORC systems for both energy storage and trigeneration and establishes experimentally validated control strategies and charge regulation techniques for their full automation. The main conclusions of the present thesis and future work recommendations are summarized in Chapter 10.
Degree
thesis:*- Grantor dc:publisher
- National Technical University of Athens (NTUA)
- Year dc:date
- 2025
Author and committee
dc:creator, dc:contributor.*- Authors dc:creator
-
- Charalampidis, Antonios
- Χαραλαμπίδης, Αντώνιος
Subjects
dc:subject × 17- Αντλία θερμότητας
- ORC
- Αντιστρεπτή αντλία θερμότητας/ORC
- Τριπαραγωγή
- Αποθήκευση ενέργειας
- Heat pump
- Reversible heat pump/ORC
- Trigeneration
- Energy storage
- Επιστήμη Μηχανολόγου Μηχανικού
- Επιστήμες Μηχανικού και Τεχνολογία
- Θερμοδυναμική
- Μηχανολογία
- Mechanical Engineering
- Engineering and Technology
- Thermodynamics
- Mechanics
Rights
- Language dc:language
- eng
Identifiers
dc:identifier.*- Identifier
- 10.12681/eadd/59636