Two impacts of wind penetration: Transient frequency response and load following requirements

Abstract

dc:description.abstract

<p>Wind power installation in U.S. has increased tremendously in 2007, twice as much as the increase in 2006. With more and more wind power being integrated into power systems, it is important to investigate the wind integration effect with respect to increasing wind penetration levels. In the past few years lots much research has been performed in this area.</p> <p>In this study, two parallel approaches, transient simulation and statistical analysis, are used to study the influence of increasing wind power penetration levels within a power system. Both of these methods support identification of the maximum wind penetration level in an existing power system.</p> <p>The transient simulation study provides a procedure for modeling user-defined wind generators using PSS/E 29.5 and Compaq Compiler 6.5. Three ways to increase wind penetration level are introduced. Under the same contingencies, a set of simulations is performed to compare the grid frequency response when wind penetration levels are increased from 2% to 8%.</p> <p>In the statistical analysis, first wind power capacity in each season and month is calculated based on one year wind data. Second, combined load-wind variability is calculated with respect to three time scales: hour to hour, ten-minute to ten-minute, and one-minute to one-minute. Operational suggestions are provided in terms of operation services such as scheduling, load following, and regulation. Finally a storage system that provides a solution for mitigating the increasing load-wind variability when wind penetration level is increased is studied.</p>

Degree

thesis:*
Name thesis:degree_name
Master of Science
Level thesis:degree_level
thesis
Department dc:contributor.department
Department of Electrical and Computer Engineering
Year dc:date.issued
2009

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Zhang, Shuyang
Advisors dc:contributor.advisor
  • James D. Mccalley
  • Venkataramana Ajjarapu

Rights

Language dc:language.iso
en

Identifiers

dc:identifier.*
Identifier
archive/lib.dr.iastate.edu/etd/11994/
Dc Identifier Other
2980
2808178
Mods Identifier Filename
archive/lib.dr.iastate.edu/etd/11994/Zhang_iastate_0097M_10245.pdf|||Fri Jan 14 19:02:55 UTC 2022

Chain of custody

source
Harvested from
Iowa State University
Base URL
dr.lib.iastate.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Zhang, Shuyang. Two impacts of wind penetration: Transient frequency response and load following requirements. thesis thesis, 2009. https://doi.org/10.31274/etd-180810-387