Back to search

Iowa State University

In-tube evaporation and condensation heat transfer of refrigerant mixtures

Abstract

dc:description.abstract

The purpose of this study was to evaluate five different HFC refrigerants which are potential replacements for the chlorine-based refrigerants, which are R-22 and R-502. Heat transfer coefficient data were taken during in-tube evaporation and condensation of refrigerant mixtures in a 9.5 mm (3/8") O.D. smooth copper tube. The data were taken at temperatures of -2.0°C and 4.0°C for evaporation and 30°C and 40°C for condensation. Three nonazeotropic refrigerant mixtures and R-125 were tested and compared against baseline data for R-22. One non-azeotropic refrigerant mixture was tested and compared against baseline data for R-502. Four different mass fluxes ranging from 125 to 375 kg/s-m² were tested. On a mass basis, the mixtures tested and compared against R-22 were: R-134a(75%) / R-32 (25%) R-134a (90%) / R-32 (10%) R-32 (30%) / R-125 (10%) / R-134a (60%) The mixture tested and compared against R-502 was R-404A which has mass components of: R-125 (44%) / R-143a (52%) / R-134a (4%) When the R-22 substitute refrigerants were compared for evaporation on an equal mass flux basis, the performances ranged from 12% less than R-22 to 7% larger than R-22. The mixture R-32 (30%) / R-125 (10%) / R-134a (60%) performed the best while R-32(10%) / R134a(90%) performed the worst. The pressure drops measured ranged from half that of R-22 to 1.3 times that of R-22. During condensation, none of the refrigerant mixtures evaluated had heat transfer coefficients higher than R-22. During evaporation for the R-502 substitute, namely R-404A, the heat transfer coefficient was 23% higher and the pressure drop was 2.8% lower for a mass flux of 300 kg/s-m² and a temperature of 4°C compared to R-502. When compared on an equal cooling capacity basis, during evaporation, R-404A had a heat transfer coefficient 21% higher than R-502 at 4.0 °C and 45 kW/m². For condensation the mixture had a heat transfer coefficient 3% higher than R-502 for a temperature of 40 °C. When compared on an equal heating capacity basis during condensation, R-404A had a heat transfer coefficient 6% larger than R-502 at 30 °C and 30 kW/m².

Degree

thesis:*
Name thesis:degree_name
Master of Science
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Mechanical Engineering
Department thesis:degree_department
Department of Mechanical Engineering
Year dc:date.issued
1997

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Doerr, Thomas Michael
Advisor dc:contributor.advisor
  • Pate, Michael B.

Rights

Language dc:language.iso
en

Identifiers

dc:identifier.*

Chain of custody

source
Harvested from
Iowa State University
Base URL
dr.lib.iastate.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Doerr, Thomas Michael. In-tube evaporation and condensation heat transfer of refrigerant mixtures. Masters thesis, 1997. https://doi.org/10.31274/td-20250603-167