Back to search

Iowa State University

Modelling and evaluation of a cistern-based ground-coupled heat pump: its implications in reducing energy in a commercial swine operation

Abstract

dc:description.abstract

<p>This research details the analysis of a ground-coupled heat pump system which utilizes a 20,000 gallon well-water storage tank as a source of heating and cooling. It addresses the feasibility of such a system and discusses the system in terms of energy efficiency--first law conservation analysis. The potential use of this type of system for the control of sensitive thermal environments involving swine is also evaluated;The goal of this research was to investigate ISU's SNMRC heat pump system. Specific objectives were: (1) To evaluate the system in terms of heat exchanger and heat pump efficiencies. (2) To develop a mathematical model which simulates the heat pump system, accounting for energy gains/losses throughout, and which is capable of predicting energy availability based upon various heat exchanger coil lengths, cistern sizes, heat pump sizes and well water flow rates. (3) To evaluate the system in terms of its ability to provide energy. (4) To investigate the potential of the heat pump system for control of sensitive thermal environments for swine;Investigations of this system were conducted both experimentally, and numerically through a mathematical model. Experimentally, the tank heat exchanger efficiencies were determined to average 0.71 during the heating mode and 0.99 during the cooling mode. From the mathematical model, the efficiencies were 0.72 and 1.00 for the heating and cooling modes, respectively. The model predicted heat pump coefficients of performance from 3.5 to 4.8 for heating and 2.4 to 4.0 for cooling. Results indicated that appropriately sized heat pump, heat exchanger coil and cistern were a source of supplemental heating, are energy conservative and offer control of sensitive thermal environments for specific applications involving swine.</p>

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy
Level thesis:degree_level
dissertation
Department dc:contributor.department
Department of Agricultural and Biosystems Engineering (ENG)
Year dc:date.issued
1994

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Leary, James
Advisor dc:contributor.advisor
  • Dwaine S. Bundy

Rights

Language dc:language.iso
en

Identifiers

dc:identifier.*
Identifier
archive/lib.dr.iastate.edu/rtd/10491/
Dc Identifier Other
11490
6405221
Mods Identifier Filename
archive/lib.dr.iastate.edu/rtd/10491/r_9503576.pdf|||Fri Jan 14 18:21:48 UTC 2022

Chain of custody

source
Harvested from
Iowa State University
Base URL
dr.lib.iastate.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Leary, James. Modelling and evaluation of a cistern-based ground-coupled heat pump: its implications in reducing energy in a commercial swine operation. dissertation thesis, 1994. https://dr.lib.iastate.edu/handle/20.500.12876/63643