Abstract
dc:description.abstract<p>Today's laboratory buildings are large consumers of energy. The ventilation requirements of these buildings mandate that large quantities of outside air be brought into the building. The advent of air-to-air heat recovery systems has been proven to significantly decrease the energy input needed to condition outside air. This project is a detailed energy simulation of a laboratory building on the campus of Iowa State University in Ames, Iowa. Using Trane TRACE 700 software, a detailed model of the building was created, and energy efficient measures were simulated. These simulations include the proper control of outside air flow rates, the installation of enthalpy wheels, and recovery of heat from fume hood exhaust. With each simulation, detailed energy and cost savings numbers were tabulated. It was found that through these simulations, a total of 15 percent energy savings could be achieved.</p>
Degree
thesis:*- Name thesis:degree_name
- Master of Science
- Level thesis:degree_level
- thesis
- Department dc:contributor.department
- Department of Mechanical Engineering
- Year dc:date.issued
- 2008
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Milbrandt, Robert
- Advisor dc:contributor.advisor
-
- Gregory Maxwell
Rights
- Language dc:language.iso
- en
Identifiers
dc:identifier.*- Identifier URI
- https://dr.lib.iastate.edu/handle/20.500.12876/68489
- Identifier
- archive/lib.dr.iastate.edu/rtd/14910/
- Dc Identifier Other
-
15909
7008076 - Mods Identifier Filename
- archive/lib.dr.iastate.edu/rtd/14910/1450156.PDF|||Fri Jan 14 20:28:42 UTC 2022