Back to search

Iowa State University

Slow coherency grouping based islanding using minimal cutsets and generator coherency index tracing using the continuation method

Abstract

dc:description.abstract

<p>Power systems are under increasing stress as deregulation introduces several new economic objectives for operation. Since power systems are being operated close to their limits, weak connections, unexpected events, hidden failures in protection system, human errors, and a host of other factors may cause a system to lose stability and even lead to catastrophic failure. Therefore, the need for a systematic study and design of a comprehensive system control strategy is gaining more attention. Among these control methods, controlled system islanding is deemed as the final resort to save the system from a blackout.;In the literature, many approaches have been proposed to undertake this task. However, some of these approaches only take static power flow into consideration; others require a great deal of computational effort. It has been observed that following large disturbances, groups of generators tend to swing together. Attention has thus been drawn to the stability of inter-area oscillations between groups of machines. The slow-coherency based generator grouping, which has been widely studied in the literature, provides a potential method for capturing the movement of generators between groups under disturbance. The issue becomes on how to take advantage of slow coherency generator grouping and island the system by finding the set of lines to be tripped. Furthermore, through various simulations and analysis, it has been found that generator grouping indeed changes with respect to large changes in system load conditions.;In this dissertation, a comprehensive approach has been proposed to conduct slow coherency based controlled power system islanding using the minimal cutset technique from graph theory with the transition from calculating real power imbalance within the island to calculating the net flow through the cutset. Furthermore, a novel approach has been developed to trace the loci of the coherency indices of the slow modes in the system with respect to variation in system conditions to obtain the updated coherency information between generators using continuation method. Finally, the approach has been applied to a 10 generator 39 bus New England system, and a 29 generator 179 bus model of the WECC system.</p>

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy
Level thesis:degree_level
dissertation
Department dc:contributor.department
Department of Electrical and Computer Engineering
Year dc:date.issued
2005

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Wang, Xiaoming
Advisor dc:contributor.advisor
  • Vijay Vittal

Rights

Language dc:language.iso
en

Identifiers

dc:identifier.*
Identifier
archive/lib.dr.iastate.edu/rtd/1603/
Dc Identifier Other
2602
6095137
Mods Identifier Filename
archive/lib.dr.iastate.edu/rtd/1603/r_3184661.pdf|||Fri Jan 14 20:54:11 UTC 2022

Chain of custody

source
Harvested from
Iowa State University
Base URL
dr.lib.iastate.edu/server/oai/request
Last updated
2026-11-18
Source record
OAI-PMH GetRecord
related terms
citation

Wang, Xiaoming. Slow coherency grouping based islanding using minimal cutsets and generator coherency index tracing using the continuation method. dissertation thesis, 2005. https://dr.lib.iastate.edu/handle/20.500.12876/69724