Back to search

Iowa State University

Correlation of the transient energy margin to Out-of-step impedance relay operation

Abstract

dc:description.abstract

<p>This research has developed a procedure in which the transient energy margin, for a multimachine power system obtained by the transient energy function method, is related to the apparent impedance of a line protected by the out-of-step relay;In this procedure, only the multimachine system parameters are used, and the conventional intermediate step of forming a two-machine equivalent is eliminated;Two types of energy-based criteria are derived to relate the apparent impedance to the transient energy margin obtained: (i) with the original multimachine system, and (ii) with the inertial equivalents of two groups of machines separated by the line protected by the out-of-step relay;An approximation of the post-disturbance trajectory is developed for the rotor angle positions between the instance of disturbance removal and the controlling u.e.p. Two such approximations are investigated: (i) a linear trajectory, and (ii) the Fourier series approximation. The energy-based criteria are then applied along this approximated trajectory. A technique for generating the swing impedance locus is also presented;The method is tested for a loss of generation distrubance on a 23-generator, 211-bus equivalent of the Florida Power & Light Company network. The results obtained are compared with time simulation results.</p>

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy
Level thesis:degree_level
dissertation
Department dc:contributor.department
Department of Electrical and Computer Engineering
Year dc:date.issued
1986

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Oh, Tae

Rights

Language dc:language.iso
en

Identifiers

dc:identifier.*
Identifier
archive/lib.dr.iastate.edu/rtd/8284/
Dc Identifier Other
9283
6331124
Mods Identifier Filename
archive/lib.dr.iastate.edu/rtd/8284/r_8703743.pdf|||Sat Jan 15 02:09:01 UTC 2022

Chain of custody

source
Harvested from
Iowa State University
Base URL
dr.lib.iastate.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Oh, Tae. Correlation of the transient energy margin to Out-of-step impedance relay operation. dissertation thesis, 1986. https://doi.org/10.31274/rtd-180813-12554