Experimental evaluation of heat transfer impacts of tube pitch on highly enhanced surface tube bundle.

Abstract

dc:description.abstract

The current research presents the experimental investigation of the effect of tube pitch on enhanced tube bundles’ performance. The typical application of this research is flooded refrigerant evaporators. Boosting evaporator’s performance through optimizing tube spacing reduces cost and energy consumption. R-134a with the enhanced tube Turbo BII-HP and R-123 with Turbo BII-LP were used in this study. Three tube pitches were tested P/D 1.167, P/D 1.33, and P/D 1.5. Each tube bundle includes 20 tubes (19.05 mm outer diameter and 1 m long each) constructed in four passes. The test facility’s design allows controlling three variables, heat flux, mass flux, and inlet quality. The type of analysis used is local to one location in the bundle. This was accomplished by measuring the water temperature drop in the four passes. The water-side pressure drop is included in the data analysis. A new method called the EBHT (Enthalpy Based Heat Transfer) was introduced, which uses the water-side pressure drop in performing the heat transfer analysis. The input variables ranges are: 15-55 kg/m².s for mass flux, 5-60 kW/m² for heat flux, and 10-70% for inlet quality. The effect of local heat flux, local quality, and mass flux on the local heat transfer coefficient was investigated. The comparison between the bundle performance and single tube performance was included in the results of each tube bundle. The smallest tube pitch has the lowest performance in both refrigerants, with a significantly lower performance in the case of R-134a. However, the two bigger tube pitches have very similar performance at low heat flux. Moreover, the largest tube pitch performance approaches that of the single tube at medium and high heat fluxes. For the R-123 study, the smallest tube bundle experienced quick decease in performance at high qualities, exhibiting tube enhancement dry-out at certain flow rates and high qualities. The flow pattern effect was demonstrated by the dry-out phenomena. At medium and high heat fluxes, as the tube pitch increases, the performance approaches that of the single tube. All tube bundles experience quick decrease in performance at high qualities. Evidently, P/D 1.33 is the optimum tube pitch for the studied refrigerants and enhanced tubes combinations.

Degree

thesis:*
Level thesis:degree_level
Doctoral
Department dc:contributor.department
Department of Mechanical and Nuclear Engineering
Grantor dc:publisher
Kansas State University
Year dc:date.issued
2011

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Gorgy, Evraam
Advisor dc:description.advisor
  • Steven J. Eckels

Subjects

dc:subject × 6

Rights

dc:rights
Statement dc:rights
  • © the author. This Item is protected by copyright and/or related rights. You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).
Language dc:language.iso
en_US

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/2097/11995

Chain of custody

source
Harvested from
Kansas State University
Base URL
krex.k-state.edu/server/oai/request
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
citation

Gorgy, Evraam. Experimental evaluation of heat transfer impacts of tube pitch on highly enhanced surface tube bundle.. Doctoral thesis, Kansas State University, 2011. https://hdl.handle.net/2097/11995