Back to search

Kansas State University

Relay in the loop test procedures for adaptive overcurrent protection

Abstract

dc:description.abstract

Microgrids with distributed generators have changed how protection and control systems are designed. Protection systems in conventional U.S. distribution systems are radial with the assumption that current flows always from the utility source to the end user. However, in a microgrid with distributed generators, currents along power lines do not always flow in one direction. Therefore, protection systems must be adapted to different circuit paths depending on distributed generator sites in the microgrid and maximum fuse ampere ratings on busses. Adaptive overcurrent protection focuses on objectives and constraints based on operation, maximum load demand, equipment, and utility service limitations. Adaptive overcurrent protection was designed to protect the power lines and bus feeders of the microgrid with distributed generators by coordinating fuses and relays in the microgrid. Adaptive overcurrent protection was based on the relay setting group and protection logic methods. Non-real-time simulator (NRTS) and real-time simulator (RTS) experiments were performed with computer-based simulators. Tests with two relays in the loop proved that primary relays tripped faster than backup relays for selectivity coordination in the adaptive overcurrent protection system. Relay test results from tripping and non-tripping tests showed that adaptive inverse time overcurrent protection achieved selectivity, speed, and reliability. The RTS and NRTS with two relays in the loop techniques were described and compared in this work. The author was the first graduate student to implement real-time simulation with two relays in the loop at the Burns & McDonnell - K-State Smart Grid Laboratory. The RTS experimental circuit and project are detailed in this work so other graduate students can apply this technique with relays in the loop in smart grid research areas such as phasor measurement units, adaptive protection, communication, and cyber security applications.

Degree

thesis:*
Level thesis:degree_level
Doctoral
Department dc:contributor.department
Electrical and Computer Engineering
Grantor dc:publisher
Kansas State University
Year dc:date.issued
2015

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Piesciorovsky, Emilio C.
Advisors dc:description.advisor
  • Anil Pahwa
  • Noel N. Schulz

Subjects

dc:subject × 6

Rights

dc:rights
Statement dc:rights
  • © the author. This Item is protected by copyright and/or related rights. You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).
Language dc:language.iso
en_US

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/2097/20537

Chain of custody

source
Harvested from
Kansas State University
Base URL
krex.k-state.edu/server/oai/request
Last updated
2026-11-26
Source record
OAI-PMH GetRecord
citation

Piesciorovsky, Emilio C.. Relay in the loop test procedures for adaptive overcurrent protection. Doctoral thesis, Kansas State University, 2015. https://hdl.handle.net/2097/20537