Modeling of High Voltage Pollution Discharge to Investigate Hot Stick Flashover

Abstract

dc:description.abstract

Electric “flashover” or insulation breakdown has occurred on “hot stick” safety tools used on live AC transmission lines at Manitoba Hydro in 1997 and 2002. Investigations showed pollution flashover as the cause, whereby leakage currents cascade into flashover. Prior to reinstating live-line work with mitigation procedures, DC voltage experiments suggested an atypical flashover uncharacteristic of pollution flashover without leakage currents, which may require a different mitigation strategy. In this thesis, statistical analysis shows that relative humidity has a greater correlation than voltage with the type of flashover. Labeled a “fast flashover”, it seems to be distinct from pollution flashover, although not statistically significant. A time-stepping computer model was developed to calculate a critical voltage for flashover as a function of relative humidity. However, lack of data prevents the model from making firm conclusions. A list of recommended research is proposed to remedy these deficiencies to allow future model refinement.

Degree

thesis:*
Level thesis:degree_level
Master of Science (M.Sc.)
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Year dc:date.issued
2013

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Reske, Dean
Advisor dc:contributor.supervisor
  • Kordi, Behzad (Electrical and Computer Engineering) Swatek, David (Electrical and Computer Engineering)
Committee members dc:contributor.committeemember
  • Oliver, Derek (Electrical and Computer Engineering)
  • Major, Arkady (Electrical and Computer Engineering)
  • Jafari Jozani, Mohammad (Statistics)

Subjects

dc:subject × 2

Rights

Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1993/18487

Chain of custody

source
Harvested from
University of Manitoba
Base URL
mspace.lib.umanitoba.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Reske, Dean. Modeling of High Voltage Pollution Discharge to Investigate Hot Stick Flashover. Master of Science (M.Sc.) thesis, 2013. http://hdl.handle.net/1993/18487