University of Manitoba
Power Transformer Transient Modeling Using Frequency Response Analysis
Abstract
dc:description.abstractVector Fitting is employed to approximate the Frequency Response Analysis (FRA) measurement data of a 13.8 kV/136.8 kV, 50-MVA single phase transformer. The frequency response of the primary and secondary coils as well the coupling between the coils have been measured in the frequency range of up to 2 MHz. The measured data includes the stray capacitances that exist between the coils. A circuit synthesis model is used to represent the measured data in the form of a two-port passive RLC network. The derived network is implemented in a commonly used power system transient simulator (PSCAD/EMTDC). The proposed RLC model is passive to ensure the stability of the network. The model can be used to investigate transient response of the transformer including the simulation of switching and lightning overvoltage transients. The results are compared with those derived from existing simple models.
Degree
thesis:*- Level thesis:degree_level
- Master of Science (M.Sc.)
- Discipline thesis:degree_discipline
- Electrical and Computer Engineering
- Year dc:date.issued
- 2014
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Alharbi, Hosam Salem
- Advisor dc:contributor.supervisor
-
- Kordi, Behzad (Electrical and Computer Engineering)
- Committee members dc:contributor.committeemember
-
- Rajapakse, Athula (Electrical and Computer Engineering)
- Hashemian, Fariborz (Civil Engineering)
Subjects
dc:subject × 5Rights
- Language dc:language.iso
- eng
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/1993/23244