Back to search

University of Manitoba

Power Transformer Transient Modeling Using Frequency Response Analysis

Abstract

dc:description.abstract

Vector Fitting is employed to approximate the Frequency Response Analysis (FRA) measurement data of a 13.8 kV/136.8 kV, 50-MVA single phase transformer. The frequency response of the primary and secondary coils as well the coupling between the coils have been measured in the frequency range of up to 2 MHz. The measured data includes the stray capacitances that exist between the coils. A circuit synthesis model is used to represent the measured data in the form of a two-port passive RLC network. The derived network is implemented in a commonly used power system transient simulator (PSCAD/EMTDC). The proposed RLC model is passive to ensure the stability of the network. The model can be used to investigate transient response of the transformer including the simulation of switching and lightning overvoltage transients. The results are compared with those derived from existing simple models.

Degree

thesis:*
Level thesis:degree_level
Master of Science (M.Sc.)
Discipline thesis:degree_discipline
Electrical and Computer Engineering
Year dc:date.issued
2014

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Alharbi, Hosam Salem
Advisor dc:contributor.supervisor
  • Kordi, Behzad (Electrical and Computer Engineering)
Committee members dc:contributor.committeemember
  • Rajapakse, Athula (Electrical and Computer Engineering)
  • Hashemian, Fariborz (Civil Engineering)

Subjects

dc:subject × 5

Rights

Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1993/23244

Chain of custody

source
Harvested from
University of Manitoba
Base URL
mspace.lib.umanitoba.ca/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Alharbi, Hosam Salem. Power Transformer Transient Modeling Using Frequency Response Analysis. Master of Science (M.Sc.) thesis, 2014. http://hdl.handle.net/1993/23244